02.06.2014 Views

comparison of practical fault ride-through capability for mv - PSCC

comparison of practical fault ride-through capability for mv - PSCC

comparison of practical fault ride-through capability for mv - PSCC

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

COMPARISON OF PRACTICAL FAULT RIDE-THROUGH CAPABILITY<br />

FOR MV-CONNECTED DG-UNITS<br />

Edward Coster<br />

ENECO NetBeheer/Eindhoven University <strong>of</strong> Technology,<br />

Rotterdam/Eindhoven, The Netherlands<br />

e.j.coster@eneco.nl / e.j.coster@tue.nl<br />

Johanna Myrzik<br />

Eindhoven University <strong>of</strong> Technology,<br />

Eindhoven, The Netherlands<br />

j.m.a.myrzik@tue.nl<br />

Abstract – Nowadays amount <strong>of</strong> distributed generation<br />

(DG) units is increasing rapidly. Most <strong>of</strong> them are represented<br />

by combined heat and power (CHP) plants and<br />

wind turbines. At this moment there are no requirements<br />

defined <strong>for</strong> short-circuit behavior <strong>of</strong> such generators connected<br />

to MV-grid. However, in the future this situation<br />

will be not acceptable anymore, since with the present<br />

protection settings <strong>of</strong> DG a <strong>fault</strong> in transmission network<br />

may lead to disconnection <strong>of</strong> DG over large geographic<br />

areas. In this paper the <strong>fault</strong> <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong><br />

wind turbines as well as CHP-plants are investigated based<br />

on transient stability analysis (calculation <strong>of</strong> critical clearing<br />

times (CCT) curves). Different types <strong>of</strong> DG have different<br />

<strong>fault</strong> <strong>ride</strong>-<strong>through</strong> capabilities. It is shown that adjustment<br />

<strong>of</strong> the protection settings according to these capabilities<br />

can lead to significant improvement <strong>of</strong> DG-units availability<br />

without loosing stability <strong>of</strong> generators.<br />

Keywords: distributed generation, <strong>fault</strong> <strong>ride</strong><strong>through</strong>,<br />

power system dynamics, protection<br />

1 INTRODUCTION<br />

The nature <strong>of</strong> today's distribution grids is changing<br />

from passive to active. The penetration level <strong>of</strong> distributed<br />

generation units (DG-units) is still increasing and it<br />

is expected that this growth will continue the next few<br />

years. At the moment not only the amount <strong>of</strong> DG-units is<br />

increasing, but in specific area also the sizes <strong>of</strong> the DGunits.<br />

In this way in the near future DG may generate a<br />

substantial part <strong>of</strong> the electricity consumption.<br />

Currently wind turbines have a large share in the generation<br />

<strong>of</strong> electricity by DG-units. Originally, the small<br />

wind turbines were connected to low voltage networks.<br />

The increase in wind turbine size have lead to large<br />

groups <strong>of</strong> wind turbines, which are connected to the<br />

medium voltage grid (MV-grid) and high voltage grid<br />

(HV-grid). In [1, 2, 3] it is stated that large wind farms<br />

must be treated like conventional power plants. This<br />

consideration has lead to the fact that grid operators<br />

have established requirements <strong>for</strong> the connection <strong>of</strong><br />

large wind farms.<br />

In the Netherlands local authorities have designated areas<br />

where greenhouse activities can be developed. Each<br />

greenhouse contains a CHP-plant in the range <strong>of</strong> 1-3<br />

MVA and the size <strong>of</strong> these units needs connection to the<br />

Anton Ishchenko<br />

Eindhoven University <strong>of</strong> Technology,<br />

Eindhoven, The Netherlands<br />

a.ishchenko@tue.nl<br />

Wil Kling<br />

Eindhoven University <strong>of</strong> Technology,<br />

Eindhoven, The Netherlands<br />

w.l.kling@tue.nl<br />

local MV-grid. Due to the high density <strong>of</strong> greenhouses in<br />

such areas, the penetration level <strong>of</strong> CHP-plants in the<br />

MV-grid is high which in these areas can lead to a total<br />

generated power <strong>of</strong> 100 MW or more. The load in these<br />

areas is less than the total amount <strong>of</strong> generated power.<br />

Due to the small size <strong>of</strong> the CHP-plants, grid operators<br />

do not have any requirements <strong>for</strong> connecting such<br />

units to the grid. The current practice is to disconnect<br />

the CHP-plants when the voltage drops to 80% <strong>of</strong> the<br />

nominal voltage. With the increasing penetration level<br />

<strong>of</strong> CHP-plants it can become important to keep, besides<br />

the wind farms, the CHP-plants connected to the grid as<br />

well [2]. To do so the <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> the<br />

DG-units have to be known. The Critical Clearing Time<br />

(CCT) is related to the <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> the<br />

DG-units since DG-units cannot be kept connected when<br />

the generators become unstable. In this paper the CCT is<br />

taken as an indicator to assess the <strong>ride</strong>-<strong>through</strong> capabilities<br />

<strong>of</strong> DG-units.<br />

Besides the stability indicator, CCT, there might be<br />

other limitations on <strong>ride</strong>-<strong>through</strong> capabilities, such as<br />

limits <strong>of</strong> power electronic converters, mechanical stress<br />

on wind turbine axes as well as turbine blades. These<br />

limitations are not considered in this paper. The objective<br />

<strong>of</strong> this paper is to set up a <strong>comparison</strong> between the<br />

<strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> a wind turbine having a<br />

Doubly Fed Induction Generator (DFIG) and a CHPplant<br />

having a synchronous generator.<br />

The paper is organized as follows: First the dynamic<br />

models <strong>of</strong> the CHP-plant and the DFIG are described<br />

briefly. Then, with the aid <strong>of</strong> a test grid and the dynamic<br />

models, <strong>for</strong> several voltage sags the CCT <strong>of</strong> both DGunits<br />

are determined. The paper ends with a case study<br />

<strong>of</strong> an existing power system including large penetration<br />

<strong>of</strong> DG-units.<br />

2 MODELING OF DG-UNITS<br />

The <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> DG-units are determined<br />

with the aid <strong>of</strong> dynamic models. These dynamic<br />

models are implemented in simulation s<strong>of</strong>tware such as<br />

Matlab/Simulink and DIgSILENT's PowerFactory. In<br />

this section the models <strong>of</strong> the CHP-plant and the DFIG<br />

wind turbine are discussed briefly.<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 1


2.1 Dynamic Model <strong>of</strong> a CHP-plant<br />

Modern CHP-plants have a turbo charged gas engine<br />

as a prime mover. When studying the <strong>ride</strong>-<strong>through</strong> capabilities<br />

<strong>of</strong> such CHP-plants it is necessary to study the<br />

dynamics <strong>of</strong> the gas engine. Gas engine modeling is<br />

very complex due to the difficulties in describing the<br />

internal processes <strong>of</strong> the engine by equations. Most<br />

models which are available in the literature are too specific<br />

and not developed <strong>for</strong> power system dynamical<br />

studies. In [4] a model is developed, which is suitable to<br />

represent the gas engine dynamics. In Figure 1 a block<br />

scheme <strong>of</strong> the gas engine model is given. This block<br />

scheme is implemented in Matlab/Simulink and dynamic<br />

simulations are per<strong>for</strong>med. In [4] a detailed description<br />

<strong>of</strong> the applied model as well as the used figures can be<br />

found.<br />

Throttle<br />

α<br />

1-α<br />

Engine<br />

Turbo<br />

Charger<br />

Figure 1: Block scheme <strong>of</strong> a turbo charged gas engine<br />

Torque<br />

The dynamics <strong>of</strong> the gas engine is demonstrated with<br />

a simulation <strong>of</strong> a torque step. At t = 0 s the engine is<br />

started up and at t = 5 s a torque step from 0.8 p.u. to 0.3<br />

p.u. is applied. The result is depicted in Figure 2 and<br />

shows that the dynamics <strong>of</strong> the gas engine are mainly<br />

determined by the dynamics <strong>of</strong> the throttle.<br />

2.2 Dynamic Model <strong>of</strong> a DFIG<br />

The scheme <strong>of</strong> a DFIG used <strong>for</strong> the simulations is<br />

shown in Figure 3. This concept includes a wound rotor<br />

asynchronous generator with the stator directly connected<br />

to the grid, while the rotor is coupled with the<br />

network using an AC to AC power converter with a DClink.<br />

Wind<br />

Turbine DFIG<br />

1.5 MW 2 MVA<br />

575 V / 10 kV<br />

Pitch<br />

Control<br />

RSC<br />

~<br />

RSC<br />

Control<br />

GSC<br />

~<br />

GSC<br />

Control<br />

150 kvar<br />

Figure 3: Model <strong>of</strong> the DFIG <strong>for</strong> stability assessment<br />

The simulations <strong>of</strong> the DFIG dynamic behavior were<br />

per<strong>for</strong>med with the Matlab/SimPowerSystems toolbox<br />

using the DFIG model available there [5]. The model<br />

includes the following main features:<br />

• The wind turbine is modeled using steady-state<br />

aerodynamic relationship between wind speed<br />

and the mechanical power <strong>of</strong> the turbine.<br />

• The power electronic converters are represented<br />

by equivalent voltage sources generating the AC<br />

voltage averaged over one cycle <strong>of</strong> the switching<br />

frequency.<br />

• Pitch control, rotor-side converter (RSC) and<br />

grid-side converter (GSC) controls are modeled<br />

in full detail. During the simulation the RSC control<br />

operates in power factor regulation mode<br />

keeping the generator reactive power exchange<br />

equal to zero.<br />

Figure 2: Dynamic response <strong>of</strong> a gas engine<br />

In <strong>comparison</strong> with typical <strong>fault</strong> clearing times <strong>of</strong> the<br />

protection systems and critical clearing time <strong>of</strong> generators,<br />

the dynamics <strong>of</strong> the gas engine are slow. Due to<br />

these slow dynamics the gas engine is represented by its<br />

inertia only. This inertia is incorporated with the generator<br />

inertia.<br />

The generator model <strong>of</strong> the CHP-plant, used in the<br />

dynamic simulations, is a regular model <strong>of</strong> the synchronous<br />

machine which is available in PowerFactory.<br />

• The wound rotor asynchronous generator is represented<br />

by 5th order model in the dq-reference<br />

frame.<br />

• The model does not include crowbar protection.<br />

3 TRANSIENT STABILITY OF DG-UNITS<br />

The aim <strong>of</strong> <strong>ride</strong>-<strong>through</strong> criteria is to keep DG-units<br />

connected to the grid during the disturbance and recover<br />

the power balance after <strong>fault</strong> clearing. Keeping DG-units<br />

connected to the grid means that the units have to withstand<br />

certain voltage dips. The effect <strong>of</strong> voltage dips on<br />

stability <strong>of</strong> CHP-plants and wind turbines is studied by<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 2


means <strong>of</strong> a study grid having a variable voltage source.<br />

The voltage source is able to produce a voltage dip <strong>of</strong> a<br />

certain depth and duration. The defined dynamic models<br />

are implemented in the test grid and the stability <strong>of</strong> the<br />

DG-units as a function <strong>of</strong> the depth and duration <strong>of</strong> the<br />

voltage dip is determined.<br />

In Figure 4 the study grid is shown. It consist <strong>of</strong> two<br />

10 kV busbars, a swing-bus which represents the external<br />

grid, a 3 km XLPE 630 mm 2 Al cable connection<br />

and a generator. Parallel at the swing-bus the variable<br />

voltage source is connected.<br />

Variable<br />

Voltage<br />

Source<br />

Swing<br />

Bus<br />

V<br />

Bus 1<br />

Bus 2<br />

Figure 4: Study grid including a variable voltage source<br />

G<br />

3.1 Dynamic Behavior <strong>of</strong> CHP-plants<br />

With the aid <strong>of</strong> the defined test grid the dynamic behavior<br />

<strong>of</strong> the CHP-plant is studied. In the simulations<br />

the rotor angle is used as a stability index. To find the<br />

stability limit at a certain depth <strong>of</strong> the voltage dip the<br />

duration <strong>of</strong> the voltage dip is adjusted. In this way the<br />

CCT as a function <strong>of</strong> the voltage dip can be found. In<br />

Table 1 the figures <strong>for</strong> which the simulations are carried<br />

out are displayed. The results <strong>of</strong> the simulation are depicted<br />

in Figure 5.<br />

S nom [MVA] P [MW] p.f. H [s]<br />

3 2.4 1.0 2<br />

3 2.4 0.8 2<br />

3 2.4 1.0 4<br />

3 2.4 0.8 4<br />

Table 1: Simulation figures <strong>of</strong> the CHP-plant<br />

u [p.u.]<br />

0.5<br />

0.45<br />

0.4<br />

0.35<br />

0.3<br />

0.25<br />

0.2<br />

0.15<br />

0.1<br />

H = 2 s, p.f. = 1<br />

H = 2 s, p.f. = 0.8<br />

0.05<br />

H = 4 s, p.f. = 1<br />

H = 4 s, p.f. = 0.8<br />

0<br />

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2<br />

t [s]<br />

Figure 5: CCT <strong>of</strong> a CHP-plant as a function <strong>of</strong> the voltage<br />

dip (remains voltage)<br />

3.2 Dynamic Behavior <strong>of</strong> a DFIG<br />

Transient stability <strong>of</strong> a DFIG can be evaluated by<br />

monitoring the DC-link voltage. Its behavior <strong>for</strong> threephase<br />

<strong>fault</strong> durations <strong>of</strong> 100 and 300 ms at wind speed<br />

<strong>of</strong> 10 m/s (voltage dip to 0.6 p.u. <strong>of</strong> the nominal voltage)<br />

is illustrated on Figure 6.<br />

2800<br />

2600<br />

2400<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

Fault duration = 300 ms<br />

Fault duration = 100 ms<br />

DC-link voltage Vdc [V]<br />

1000<br />

0 0.1 0.2 0.3 0.4 0.5 0.6<br />

t [s]<br />

Figure 6: DC-link voltage <strong>of</strong> a DFIG <strong>for</strong> different <strong>fault</strong> durations<br />

In an unstable situation the DC-link voltage starts to<br />

increase significantly immediately after the <strong>fault</strong>. The<br />

other variables (active and reactive powers, mechanical<br />

speed <strong>of</strong> the machine, etc.) exhibit not so clear unstable<br />

behavior, although as it can be seen from Figure 7, active<br />

and reactive powers start to oscillate, and the mechanical<br />

speed begins to grow slowly.<br />

2<br />

0<br />

Active power [p.u.]<br />

-2<br />

0 0.1 0.2 0.3 0.4 0.5 0.6<br />

1<br />

0<br />

Reactive power [p.u.]<br />

-1<br />

0 0.1 0.2 0.3 0.4 0.5 0.6<br />

1.11<br />

1.1<br />

1.09<br />

Fault duration=300 ms<br />

Fault duration=100 ms<br />

Mechanical speed [p.u.]<br />

0 0.1 0.2 0.3 0.4 0.5 0.6<br />

t [s]<br />

Figure 7: Mechanical speed, active and reactive powers <strong>of</strong> a<br />

DFIG <strong>for</strong> different <strong>fault</strong> durations<br />

To determine the CCT <strong>of</strong> the DFIG the same approach<br />

as described in section 3.1 is used. The simulations<br />

are carried out <strong>for</strong> various wind speeds which lead<br />

to the results depicted in Figure 8.<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 3


u [p.u.]<br />

0.5<br />

0.45<br />

0.4<br />

0.35<br />

0.3<br />

0.25<br />

0.2<br />

0.15<br />

0.1<br />

Wind speed = 9 m/s<br />

Wind speed = 10 m/s<br />

0.05<br />

Wind speed = 11 m/s<br />

Wind speed = 12 m/s<br />

0<br />

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5<br />

t [s]<br />

Figure 8: CCT <strong>of</strong> a DFIG as a function <strong>of</strong> the voltage dips<br />

Addition <strong>of</strong> the crowbar allows to prevent the growth<br />

<strong>of</strong> the DC-link voltage during a short-circuit and significantly<br />

increase the CCT, which becomes related to the<br />

large extent only with the mechanical part <strong>of</strong> wind turbine<br />

having a very large inertia. Switching between<br />

different control strategies in case <strong>of</strong> normal operation<br />

and <strong>fault</strong> conditions improves the shape <strong>of</strong> the DFIG<br />

transient response and prevents transient stability problems<br />

as illustrated in [6].<br />

4 CASE STUDY<br />

The frequency <strong>of</strong> disconnections, initiated by the undervoltage<br />

protection can be estimated by means <strong>of</strong> a<br />

voltage dip pr<strong>of</strong>ile. The dip pr<strong>of</strong>ile describes, <strong>for</strong> a certain<br />

location in the grid, the magnitude, duration and<br />

frequency <strong>of</strong> the dips. In a case study, the developed<br />

CCT-curves in combination with the voltage dip pr<strong>of</strong>ile<br />

are used to study the stability <strong>of</strong> the DG-units when<br />

disconnection by the undervoltage protection is prevented.<br />

The dip magnitude is determined by the network<br />

impedances and the type <strong>of</strong> <strong>fault</strong> [7]. When considering<br />

voltage dips caused by <strong>fault</strong>s, the <strong>fault</strong> clearing time <strong>of</strong><br />

the protection specifies the dip duration. The <strong>fault</strong> frequency<br />

determines the number <strong>of</strong> voltage dips.<br />

For the power system <strong>of</strong> the province Zuid Holland,<br />

the Netherlands, the voltage dip pr<strong>of</strong>ile at the point <strong>of</strong><br />

connection <strong>of</strong> the DG-units is assessed.<br />

4.1 Examined Grid<br />

The province <strong>of</strong> Zuid Holland has a 150 kV transmission<br />

grid, which is connected to the 380 kV grid at 3<br />

locations. The layout is given in Figure 9. From the 150<br />

kV nodes (HV/MV substations) the MV-networks are<br />

fed. Large generators are connected to the transmission<br />

grid.<br />

In the province <strong>of</strong> Zuid Holland there are three large<br />

areas having a high penetration <strong>of</strong> DG-units. In Table 2<br />

an overview <strong>of</strong> the location, type and amount <strong>of</strong> DG is<br />

given.<br />

Substation Type <strong>of</strong> DG S tot [MVA]<br />

Sub 3 Wind Turbines 70<br />

Sub 4 Wind Turbines 40<br />

Sub 6 CHP-plants 200<br />

Sub 18 CHP-plants 400<br />

Sub 23 CHP-plants 300<br />

Table 2: Location, type and amount <strong>of</strong> DG<br />

In the case-study substation 6 is taken as an example<br />

to study the voltage dip propagation <strong>through</strong> the transmission<br />

and distribution grid as well as the effect <strong>of</strong> the<br />

voltage dips on the DG-units. There<strong>for</strong>e the MV-grid<br />

fed by substation 6 is modeled in detail including DGunits.<br />

The MV-grid is schematically shown in Figure 10.<br />

The generic <strong>fault</strong> clearing times <strong>of</strong> the MV-grid<br />

shown in Figure 10 are listed in Table 3.<br />

Figure 10: Overview <strong>of</strong> MV-grid having large penetration <strong>of</strong><br />

DG-units<br />

Figure 9: Transmission grid <strong>of</strong> the province <strong>of</strong> Zuid Holland,<br />

the Netherlands<br />

Voltage level Protection Fault clearing time<br />

380 kV distance 150 ms<br />

150 kV distance 150 ms<br />

25 kV overcurrent 600 ms<br />

23 kV overcurrent 300 ms<br />

10 kV overcurrent 0 ms<br />

Table 3: Generic <strong>fault</strong> clearing times<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 4


4.2 Voltage Dips Pr<strong>of</strong>ile<br />

As mentioned earlier the <strong>fault</strong> frequency is based on<br />

the failure rate <strong>of</strong> the components in the system. Based<br />

on [8] <strong>for</strong> HV-lines and MV-cables respectively λ =<br />

0.54 [times per annum/100 km] and λ = 1.02 [times per<br />

annum/100 km] is used. In Table 4 the <strong>fault</strong> type distribution<br />

is given.<br />

Component 3 ph 1 ph 2 ph 2 ph-ground<br />

HV OH-line 30% 60% 5% 5%<br />

MV cable 30% 70% – –<br />

Table 4: Failure rate and <strong>fault</strong> distribution<br />

In PowerFactory a tool is available to calculate voltage<br />

dip tables. With the aid <strong>of</strong> this tool, the failure rate<br />

and <strong>fault</strong> distribution voltage dip pr<strong>of</strong>iles are constructed<br />

<strong>for</strong> a generator connection in the 10 kV grid <strong>of</strong><br />

Figure 10. The results are reported in two distinct ways:<br />

1. Dip pr<strong>of</strong>ile including <strong>fault</strong> type distribution.<br />

2. Dip pr<strong>of</strong>ile including voltage level distribution.<br />

The first pr<strong>of</strong>ile is depicted in Figure 11 and shows<br />

on the x-axis the depth <strong>of</strong> the dip (remains voltage level)<br />

experienced by the generator and on the y-axis the frequency<br />

<strong>of</strong> occurrence. The undervoltage protection<br />

measures the voltage between the phases so the voltage<br />

dip pr<strong>of</strong>iles are based on the line-line voltage. According<br />

to [7, 9] in case <strong>of</strong> a single phase to ground <strong>fault</strong>s the<br />

zero sequence voltage does not propagate <strong>through</strong> a Dy<br />

and Yd trans<strong>for</strong>mer. When Z0 ≫ Z1<br />

the sagged voltage<br />

remains high. All voltage levels smaller than 0.8 p.u.<br />

are caused by three phase <strong>fault</strong>s.<br />

1.4<br />

single phase to ground <strong>fault</strong>s and the dips do not really<br />

propagate <strong>through</strong> the Dy and Yd trans<strong>for</strong>mers.<br />

Times per year<br />

1.4<br />

1.2<br />

1<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

0<br />

10 kV<br />

20 kV<br />

25.6 kV<br />

150 kV<br />

380 kV<br />

0.2 0.4 0.6 0.7 0.8 0.85 0.9 0.95<br />

U [p.u.]<br />

Figure 12: Voltage dip pr<strong>of</strong>ile based on different voltage<br />

levels at generator terminals<br />

5 RESULTS<br />

In this section the results <strong>of</strong> the case study are discussed.<br />

The aim <strong>of</strong> the case study is to demonstrate<br />

whether the DG-units can stay connected to the grid and<br />

maintain stable operation. There<strong>for</strong>e the worst case<br />

CCT-curve <strong>of</strong> the CHP-plant and the worst case CCTcurve<br />

<strong>of</strong> the wind turbine are depicted in Figure 13. To<br />

judge if the DG-units stay in stable operation, the duration<br />

<strong>of</strong> the dip has to be determined. This is done by<br />

combining the results <strong>of</strong> Figure 12 and the <strong>fault</strong> clearing<br />

time <strong>of</strong> the protection <strong>of</strong> the MV-grid (Table 3). It is<br />

assumed that all <strong>fault</strong>s are cleared by the primary protection.<br />

This leads to the red dots in Figure 13.<br />

1<br />

0.9<br />

Times per year<br />

1.2<br />

1<br />

0.8<br />

0.6<br />

3 phase<br />

2 phase<br />

2 phase-ground<br />

single phase-ground<br />

u [p.u.]<br />

0.8<br />

0.7<br />

0.6<br />

0.5<br />

0.4<br />

0.3<br />

0.4<br />

0.2<br />

0<br />

0.2 0.4 0.6 0.7 0.8 0.85 0.9 0.95<br />

U [p.u.]<br />

Figure 11: Voltage dip pr<strong>of</strong>ile based on <strong>fault</strong> distribution at<br />

generator terminals<br />

In Figure 12 the second dip pr<strong>of</strong>ile is depicted and<br />

shows the experienced voltage dip caused by disturbances<br />

at a different voltage level. In the figure it can be<br />

seen that voltage levels smaller than 0.8 p.u. are caused<br />

by <strong>fault</strong>s in the 25 and 20 kV grid. At the generator<br />

terminals dips caused by disturbances in the HV-grid are<br />

hardly noticed. As discussed above most <strong>of</strong> the <strong>fault</strong>s are<br />

0.2<br />

0.1<br />

CHP<br />

DFIG<br />

0<br />

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1<br />

t [s]<br />

Figure 13: Comparison <strong>of</strong> <strong>fault</strong> clearing times and CCTcurves<br />

<strong>of</strong> DFIG and CHP-plant<br />

Most dots are above both CCT-curves and those dips<br />

do not lead to unstable operation <strong>of</strong> either the wind<br />

turbine or the CHP-plants. The dots under the CCTcurves<br />

are <strong>fault</strong>s in the 20 kV grid that have a clearing<br />

time, which is larger than the CCT <strong>of</strong> the DG-units. In<br />

this situation, keeping the DG-units connected lead to<br />

unstable operation. Preventing instability <strong>of</strong> the DGunits<br />

can be done by reducing the <strong>fault</strong> clearing time.<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 5


Reduction in <strong>fault</strong> clearing time can be reached by reducing<br />

time grading <strong>of</strong> two successive relays or applying<br />

differential protection.<br />

The nowadays undervoltage protection settings in the<br />

Netherlands are such that at voltage levels below 0.8<br />

p.u. all DG-units are disconnected. Comparing the current<br />

settings with the CCT-curves displayed in Figure<br />

13, it can be concluded that the settings <strong>of</strong> the undervoltage<br />

protection can be altered without instability <strong>of</strong><br />

the DG-units.<br />

Based on the data in Figure 12 with the current settings,<br />

the frequency <strong>of</strong> disconnection is 0.37 times per<br />

annum or 9.3 % <strong>of</strong> all the voltage dips (calculated by<br />

summing up all the frequencies <strong>of</strong> the voltage dips below<br />

0.8 p.u.). By applying the developed CCT-curves in<br />

the undervoltage protection the frequency <strong>of</strong> disconnection<br />

can be reduced to 0.02 times per annum or 0.5 % <strong>of</strong><br />

all the voltage dips. This figure holds <strong>for</strong> the wind turbine,<br />

while <strong>for</strong> the CHP-plant there are no disconnections<br />

at all. Thus, the availability <strong>of</strong> the DG-units can be<br />

increased significantly by adjusting the under-voltage<br />

protection in accordance with the CCT-curves.<br />

The <strong>fault</strong> <strong>ride</strong>-<strong>through</strong> capabilities <strong>of</strong> the wind turbine<br />

can be improved by adding a crowbar to the DFIG. The<br />

crowbar separates the rotor side converter from the rotor<br />

circuit. In [10] the operation <strong>of</strong> the crowbar is simulated<br />

and it is demonstrated that <strong>fault</strong> <strong>ride</strong> <strong>through</strong> during and<br />

after a deep voltage dip (0 V remains, 150 ms) is possible.<br />

6 CONCLUSION<br />

In this paper the <strong>ride</strong>-<strong>through</strong> behavior <strong>of</strong> a CHPplant<br />

and a DFIG-based wind turbine is studied. Based<br />

on the data <strong>of</strong> an existing power system including reliability<br />

data a voltage dip pr<strong>of</strong>ile at the generator terminals<br />

is established. This pr<strong>of</strong>ile is combined with the<br />

<strong>fault</strong> clearing times <strong>of</strong> the test system which have led to<br />

a plot where the depth and duration <strong>of</strong> the voltage dips<br />

are indicated. Using the single machine infinite network<br />

scheme the CCT-curves <strong>of</strong> the DG-units are derived.<br />

From stability point <strong>of</strong> view these curves show that it is<br />

not necessary to disconnect the DG-units at a voltage<br />

level <strong>of</strong> 0.8 p.u. (the present setting <strong>of</strong> DG undervoltage<br />

protection in the Netherlands), but at lower levels, which<br />

are dependent on the critical clearing times. These CCTcurves<br />

can be implemented in the undervoltage relay<br />

and prevent switching <strong>of</strong>f during a voltage dip caused by<br />

a <strong>fault</strong> in a HV- or neighboring MV-grid. In some cases<br />

disturbances in the 20 kV grid lead to unstable operation.<br />

This can be prevented by adjusting the <strong>fault</strong> clearing<br />

time or applying differential protection. For DFIG<br />

wind turbines transient stability can be significantly<br />

improved by introduction <strong>of</strong> crowbar protection and<br />

switching between different control strategies <strong>for</strong> normal<br />

operation and <strong>fault</strong> conditions.<br />

The method presented in this paper can be followed<br />

in all locations <strong>of</strong> the grid and prevent ambitious disconnection<br />

<strong>of</strong> DG.<br />

REFERENCES<br />

[1] B.M. Buchholz, “Dynamic Simulation <strong>of</strong> Renewable<br />

Energy Sources and Requirements on Fault Ride<br />

Through Behaviour”, Power Engineering Society<br />

General Meeting, Montreal, Canada, June, 2006<br />

[2] F.M. Gatta, F. Ilicento, S. Lauria and P. Masato,<br />

“Behaviour <strong>of</strong> Dispersed Generation in Distribution<br />

Networks During System Disturbances. Measures to<br />

prevent disconnection”, CIRED 17th International<br />

Conference on Electricity Distribution, Barcelona,<br />

May 2003<br />

[3] I. Erlich and U. Bachmann, “Grid Code Requirements<br />

Concerning Connection and Operation <strong>of</strong><br />

Wind Turbines in Germany”, IEEE Power Engineering<br />

Society General Meeting, San Francisco, Cali<strong>for</strong>nie,<br />

USA, 2005<br />

[4] G. Daniëls, “Betrieb von Mittelspannungsnetzen mit<br />

hoher Blockheizkraftwerkeinspeisung”, Band 39,<br />

dissertation Rheinisch-Westfälischen Technische<br />

Hochschule Aachen, 1996 (in German)<br />

[5] “SimPowerSystems User's Guide”, The Mathworks,<br />

2007<br />

[6] A.D. Hansen and G. Michalke, “Voltage grid support<br />

<strong>of</strong> DFIG wind turbines during grid <strong>fault</strong>s”,<br />

European Wind Energy Conference & Exhibition,<br />

Milan, Italy, May 2007<br />

[7] J.F.G. Cobben, “Power Quality: Implications at the<br />

Point <strong>of</strong> Connection”, PhD Thesis, ISBN: 978-90-<br />

386-1030-6, Eindhoven University <strong>of</strong> Technology,<br />

June 2007<br />

[8] R. Luiten et al, “Reliability <strong>of</strong> Electricity Networks<br />

in the Netherlands <strong>for</strong> 2006”, KEMA, May 2007 (in<br />

Dutch)<br />

[9] M.H.J. Bollen, “Understanding Power Quality Problems,<br />

Voltage Sags and Interruptions”, Piscataway,<br />

NJ: IEEE press, 1999<br />

[10]I. Erlich, H. Wrede and C. Feltes, “Dynamic Behavior<br />

<strong>of</strong> DFIG-Based Wind Turbines during Grid<br />

Faults”, PCC Power Conversion Conference, Nagoya,<br />

Japan, April, 2007<br />

16th <strong>PSCC</strong>, Glasgow, Scotland, July 14-18, 2008 Page 6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!