Tmax<br />

MCCBs<br />

Technical data<br />

Shunt trips, Undervoltages<br />

T1 - T7<br />

Standard shunt trip<br />

Inrush Power Consumption<br />

Voltage<br />

T1,T2,T3 Ts3 T4,T5,T6 T7<br />

AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)<br />

12 VDC - 50 - 120 - 150 - -<br />

24 VAC/DC - - 100 100 or 4 1 - - 300 300<br />

24…30 VAC/DC 50 50 - - 150 150 - -<br />

30 VAC/DC - - - - - - 300 300<br />

48 VAC/DC - - - 120 - - 300 300<br />

48…60 VAC/DC 60 60 - - 150 150 - -<br />

60 VAC/DC - - - - - - 300 300<br />

100…120 VAC/DC - - 100 or 4 1 - - - 300 300<br />

120…127 VAC/DC - - - - - - 300 300<br />

110…127 VAC 110…125 VDC 50 50 - 120 150 150 - -<br />

220…240 VAC/DC - - - - - - 300 300<br />

220…240 VAC 220…250 VDC 50 50 100 120 150 150 - -<br />

240…250 VAC/DC - - - - - - 300 300<br />

380…400 VAC - - - - - - 300 -<br />

380…440 VAC 55 - - - 150 - - -<br />

415…440 VAC - - - - - - 300 -<br />

480 VAC - - 100 - - - - -<br />

480…525 VAC 55 - - - 150 - - -<br />

Opening Time (ms) 15 15 ≤15 ≤15 15 15 20 20<br />

Permanent supply shunt trip<br />

T4,T5,T6<br />

Voltage<br />

AC (VA) DC (W)<br />

24 VAC/DC 4 4<br />

100…120 VAC 4 -<br />

17<br />

Undervoltage<br />

Power consumption during permanent operation<br />

Voltage<br />

T1,T2,T3 Ts3 T4, T5, T6 T7<br />

AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)<br />

24 VAC/DC - - 6 3 - - 3.5 3.5<br />

24…30 VAC/DC 1.5 1.5 - - 6 3 - -<br />

30 VAC/DC - - - - - - 3.5 3.5<br />

48 VAC/DC 1 1 6 3 6 3 - -<br />

60 VAV/DC 1 1 - - 6 3 - -<br />

110…120 VAC/DC - - 6 - - - 3.5 3.5<br />

120…127 VAC/DC - - - - - - 3.5 3.5<br />

110…127 VAC 110…125 VDC 2 2 - - 6 3 - -<br />

220…240 VAC/DC - - - - - - 3.5 3.5<br />

220…240 VAC 220…250 VDC 2.5 2.5 - 3 6 3 - -<br />

220…250 VAC - - 6 - - - - -<br />

240…250 VAC/DC - - - - - - 3.5 3.5<br />

380…400 VAC - - - - - - 3.5 -<br />

380…440 VAC 3 - - - 6 - - -<br />

415 - 440 VAC - - - - - - 3.5 -<br />

480…525 VAC 4 - - - 6 - - -<br />

480 VAC - - 6 - - - - -<br />

Opening Time (ms) 15 15 ≤18 ≤18 ≤25 ≤25 ≤25 ≤25<br />