19. <strong>St</strong>udent Recreation Center<br />

GRAPH 4<br />

CHW Temperature (°F)<br />

70<br />

65<br />

60<br />

55<br />

50<br />

45<br />

<strong>St</strong>udent Rec Center<br />

September 1, 2011<br />

CHW Supply and Return Temperatures<br />

Supply Temp, °F<br />

Return Temp, °F<br />

40<br />

7:12 PM<br />

12:00 AM<br />

4:48 AM<br />

9:36 AM<br />

2:24 PM<br />

7:12 PM<br />

12:00 AM<br />

Cooling System Performance<br />

Graphs 2, 3, and 4 above indicate that the building load commences around 7:00 AM and maintains the<br />

desired setpoint until 10:00 PM every day of the week.<br />

Building Impact on <strong>Chilled</strong> <strong>Water</strong> System<br />

The two-way valves on the AHUs are performing properly and are not having a negative impact on the chilled<br />

water distribution system.<br />

Recommendations<br />

• Investigate and resolve issues with scheduling and system performance.<br />

• Properly tune individual AHU control valves.<br />

• Install BTU chilled water meter in the ground floor mechanical room.<br />

• Balance water flow to AHUs.<br />

• Document new performance data.<br />