6. Administrative Services Building<br />
Building Impact on <strong>Chilled</strong> <strong>Water</strong> System<br />
• The two-way valves on the AHUs are performing properly and are not<br />
having a negative impact on the chilled water distribution system.<br />
• The return water temperature control valve is intended to restrict<br />
return water flow to the chilled water plant until it reaches a<br />
predetermined temperature. There is no cross-connect to the supply<br />
water line and no booster pump to move the water if there were. This<br />
valve is redundant to and, in some cases, overrides the performance<br />
of the individual AHU control valves.<br />
Recommendations<br />
• Command open the return water temperature control valve and remove its control parameters.<br />
• Properly tune individual AHU control valves.<br />
• Install BTU chilled water meter in ground floor mechanical room.<br />
• Balance water flow to AHUs.<br />
• Document new performance data.<br />
28