29.08.2014 Views

Chiller Details - Salvex

Chiller Details - Salvex

Chiller Details - Salvex

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

~70°C<br />

Condenser<br />

~70 °C<br />

~95°C<br />

to~4°C "<br />

Flow Diagram<br />

tc~45°C<br />

Generator<br />

Evaporator<br />

Absorber<br />

ta~35°C<br />

~50°C<br />

Tower Water Out ~37°C<br />

Heat<br />

Medium Out<br />

Heat Medium In<br />

6 °C<br />

Chilled Water<br />

12 °C<br />

~32,5°C<br />

Steam or<br />

Hot Water<br />

Tower Water In ~27°C<br />

Refrigerant (Water)<br />

Steam or Hot Water<br />

Diluted Solution (LiBr)<br />

Concentrated Solution (LiBr)<br />

Tower Water<br />

Chilled Water<br />

Early Warning System<br />

The integrated early warning systems warns before a<br />

safety shutdown of the unit and limits heating input rate<br />

supply until correcting actions had been taken. This<br />

system guarantees a stable operation even in<br />

abnormal operating conditions.<br />

Automatic Decrystallization<br />

Each IsoFlow absorption chiller is delivered with a<br />

protection system that quickly eliminates any minor<br />

crystallization that may occur under extreme conditions.<br />

I the unlikely event of a problem, a control-center signal<br />

immediately opens the stabilizer valve, sending pure<br />

water to dilute the most concentrated solutions in the<br />

machine. Additionally the Automatic Decrystallization<br />

Pipe send hot solution to warm the solution heat<br />

exchanger. This redundancy helps to ensure safe<br />

operation of the unit.<br />

Cooling Capacities<br />

and Physical Data<br />

Hermetic Pumps<br />

The unique construction of YORK's hermetic pumps<br />

ensures low energy consumption and long trouble-free<br />

operation. Service inspections are usually carried out<br />

every 50000 hours. Maintenance of the pumps can be<br />

carried out quickly and easily due to built-in isolation<br />

valves ahead and behind each internal pump.<br />

Dimensions<br />

Cooling mm Operating<br />

Model Capacity 1 Weight kg*<br />

kW Length Width Height<br />

1A1 420 3720 1760 2320 4950<br />

1A2 550 4330 1420 2320 5500<br />

2A3 600 4940 1420 2320 6130<br />

2A4 720 5550 1420 2320 6590<br />

2B1 830 4940 1580 2640 7900<br />

3B2 960 5550 1580 2640 8540<br />

3B3 1090 6160 1580 2640 9490<br />

4B4 1170 6770 1580 2640 10490<br />

4C1 1280 5550 1770 3020 11400<br />

5C2 1440 6160 1770 3020 12260<br />

5C3 1570 6770 1770 3020 13620<br />

6C4 1820 7530 1770 3020 14760<br />

7D1 1990 6160 2110 3540 17890<br />

7D2 2170 6770 2110 3540 19840<br />

8D3 2480 7530 2110 3540 21800<br />

8E1 2790 6870 2290 3840 24110<br />

9E2 3190 7630 2290 3840 26830<br />

10E3 3380 8390 2290 3840 29790<br />

12F1 4040 7630 2480 4240 35550<br />

13F2 4340 8390 2480 4240 39050<br />

14F3 4840 9150 2480 4240 41140<br />

Proven Design<br />

YORK has been manufacturing<br />

single stage absorption chillers<br />

since the late 1950s. With over<br />

3,000 units installed worldwide,<br />

YORK has a level of<br />

experience with the design and<br />

application of single stage<br />

absorbers that is the best.<br />

The proven industrial-grade<br />

design with YORK's renowned<br />

Millennium controls combine<br />

to provide the customer with the<br />

highest level of performance<br />

and reliability available today.<br />

YIA<br />

1<br />

Those values are valid at following conditions<br />

Chilled Water Temperatures (in/out) 12.2/6.7°C<br />

Cooling Water Temperatures (in/out) 29.4/39.4°C<br />

Hot Water Temperatures (in/out) 115/109°C<br />

Saturated Steam Pressure 0.8 barg<br />

Please ask your local YORK-office for other conditions