5.33 nvoAnaIn1Value<br />

Bit<br />

Description<br />

20 High humidity warning<br />

21 Low humidity warning<br />

22 Fan motor overload: Check motor amperage - Optional<br />

23 Local alarm #1: See tag inside door – Optional<br />

24 Local alarm #2: See tag inside door - Optional<br />

25 Local alarm #3: See tag inside door - Optional<br />

26 Local alarm #4: See tag inside door - Optional<br />

27 Standby pump on: Check primary pump - Optional<br />

28 UPS power on: Check main power supply - Optional<br />

29 Custom alarm #1 - Optional<br />

30 Custom alarm #2 - Optional<br />

31 Custom alarm #3 -Optional<br />

32 Custom alarm #4 - Optional<br />

33 Humidification inhibited - Optional<br />

34 Reheat inhibited - Optional<br />

35 Reheat and humidification inhibited - Optional<br />

36 Low discharge air temperature alarm - Optional<br />

37 Manual override: Check bypass switches<br />

38 High condensate water level – Optional on Floor Model,<br />

standard only ceiling Model<br />

39 Unit in standby, all functions held off – Optional<br />

nvoAnaIn1Value contains the current value of the sensor connected to analog input 1.<br />

5.34 nvoAnaIn2Value<br />

nvoAnaIn2Value contains the current value of the sensor connected to analog input 2.<br />

5.35 nvoAnaIn3Value<br />

nvoAnaIn3Value contains the current value of the sensor connected to analog input 3.<br />

5.36 nvoAnaIn4Value<br />

nvoAnaIn4Value contains the current value of the sensor connected to analog input 4.<br />

5.37 nviFireLimit<br />

nviFireTempLimit contains the fire temperature limit. The valid range is 38-65 C (100-150 F).<br />

5.38 nviHiTempLimit<br />

nviHiTempLimit contains the high return air temperature limit. The valid range is 10-32 C (50-90<br />

F).<br />

Document 600-000-685 12