5.49 nviInhibitHeat<br />

nviInhibitHeat contains the current heating inhibit setting.<br />

Inhibit Heating value state<br />

Inhibit Off 0 0<br />

Inhibit On >0 1<br />

5.50 nviInhibitHumid<br />

nviInhibitHumid contains the current humidification inhibit setting.<br />

Inhibit Humidification value state<br />

Inhibit Off 0 0<br />

Inhibit On >0 1<br />

5.51 nviInhibitDehum<br />

nviInhibitDehum contains the current dehumidification inhibit setting.<br />

Inhibit Dehumidification value state<br />

Inhibit Off 0 0<br />

Inhibit On >0 1<br />

5.52 nviInhibitFan<br />

nviInhibitFan contains the current blower inhibit setting.<br />

Inhibit Blower value state<br />

Inhibit Off 0 0<br />

Inhibit On >0 1<br />

5.53 nviStandby<br />

nviStandby contains the current unit standby inhibit setting. Use this nvi for unit on/off control.<br />

For instance, if the value of this nvi is changed to 2 and the state is changed to 1, the unit will be in<br />

standby mode (so called off mode)<br />

Mode value state<br />

On 0 0<br />

Standby >0 1<br />

5.54 nviFanSpeed<br />

nviFanSpeed contains the current blower fan speed. The valid range is 30%-100%.<br />

This point can be used to control fan speed. Lower than 60% fan speed is not recommended for<br />

DX cooling equipment.<br />

Document 600-000-685 14