Network Variable Network Variable Type Description<br />

nviStandby SNVT_switch Standby Mode – Unit on/off control.<br />

See the nvistandby description below<br />

for details.<br />

nviFanSpeed SNVT_lev_cont Plug Fan Speed control 30-100%<br />

5 Network Variables Description<br />

5.1 nvoReturnTemp<br />

nvoReturnTemp contains the current return air temperature.<br />

5.2 NvoDiscTemp (optional)<br />

nvoDiscTemp contains the current discharge air temperature. This is an optional nvo, it requires a<br />

optional discharge air temperature sensor to be installed to the <strong>DAP</strong> <strong>III</strong> controller.<br />

5.3 NvoWaterTemp (Optional)<br />

nvoWaterTemp contains the current chilled water temperature. This is an optional nvo, it requires<br />

an optional chilled water temperature sensor to be installed to the <strong>DAP</strong> <strong>III</strong> controller.<br />

5.4 nvoHumidity<br />

nvoHumidity contains the current space humidity.<br />

5.5 nvoCoolStagesOn<br />

nvoCoolStagesOn contains the current number of cooling stages in use.<br />

5.6 nvoHeatStagesOn<br />

nvoHeatStagesOn contains the current number of heating stages in use.<br />

5.7 nvoHumidifying<br />

nvoHumidifying contains the current state of the humidifier.<br />

Humidifier value state<br />

Off 0 0<br />

On >0 1<br />

Document 600-000-685 8