Information<br />

Table of characteristics<br />

Locked-rotor protection<br />

General remarks:<br />

All EC motors are protected against improper<br />

use (locked-rotor protection) in accordance<br />

with relevant regulations.<br />

Sizes 045, 055, 074 <strong>and</strong> 084:<br />

The motor windings are de-energised with<br />

locked-rotor condition. The motor tries to<br />

restart every 5 seconds. Once the rotor is no<br />

longer locked, the motor will restart.<br />

Sizes 084 <strong>and</strong> 112 with external electronics:<br />

A thermal switch is built into the motor. The<br />

external electronics will de-energise the motor<br />

windings once the rotor is locked. Either the<br />

enable input or the power supply have to be<br />

disconnected for a moment to restart the<br />

motor. If an RS485 interface is used, restart via<br />

software is possible.<br />

Start-up, overload, current limitation<br />

Sizes 045, 055, 074 <strong>and</strong> 084:<br />

In general, there is soft start. In case of overload,<br />

the current is limited <strong>and</strong> the motor will<br />

eventually be shut off.<br />

Sizes 084 <strong>and</strong> 112 with external electronics:<br />

Soft start is included in the external electronics<br />

as st<strong>and</strong>ard.<br />

Closed loop / open loop speed control<br />

EC motors are controlled via PWM or linear<br />

(0-10 VDC) input signal. There is an open loop<br />

speed control so that the speed changes<br />

depending on the load. (St<strong>and</strong>ard interfaces,<br />

see page 21). Closed loop speed control is possible<br />

for sizes 084 <strong>and</strong> 112 with external electronics,<br />

in size 150 with integrated electronics.<br />

There are inputs for potentiometers, 0-10 VDC<br />

or PWM signals.<br />

PWM (pulse width modulation)<br />

A PWM signal is a square wave signal with a<br />

variable pulse-pause ratio.<br />

n<br />

n min<br />

n max<br />

Linear closed loop /open loop speed control<br />

At 0 VDC, the motor is de-energised <strong>and</strong> does<br />

not rotate. From 1 VDC onwards, the motor<br />

starts to run. Maximum speed is reached at<br />

10 VDC.<br />

n<br />

n min<br />

1 V<br />

PWM<br />

100 %<br />

10 V<br />

H-level<br />

19<br />

Accessories EC-SYSTEMS<br />

EC axial<br />

EC centrifugal<br />

AC axial<br />

AC centrifugal