13.09.2014 Views

Centrifugal blowers and fans Axial fans

Centrifugal blowers and fans Axial fans

Centrifugal blowers and fans Axial fans

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Information<br />

Bearings<br />

As a st<strong>and</strong>ard, ball bearings are used unless<br />

other bearings are specified in the relevant<br />

chapters. They are completely maintenancefree<br />

<strong>and</strong> can be used in any mounting position.<br />

Unless otherwise indicated, the bearing lubricant<br />

is suitable for a minimal ambient temperature<br />

of minus 15 °C (even minus 30 °C for a<br />

short period of time <strong>and</strong> without reaching dew<br />

point). For applications at an ambient temperature<br />

of 40 °C, minimal life cycle L10 is 40,000<br />

hours. On request, we provide a life cycle calculation<br />

for your specific application.<br />

Sleeve bearings have a very low noise level.<br />

Lifetime lubrication is guaranteed by means of<br />

a special retention medium. However, for use<br />

with suspended motor <strong>and</strong> at high ambient<br />

temperatures, ball bearings should be used.<br />

Life cycle depends on the ambient temperatures<br />

<strong>and</strong> application conditions, <strong>and</strong> up to<br />

30,000 hours are typically attained. Favourable<br />

conditions, though, can result in a life cycle of<br />

40,000 hours.<br />

Safety approvals<br />

Depending on the product, ebm-papst <strong>fans</strong> <strong>and</strong><br />

<strong>blowers</strong> comply with EN 60335-1, EN 50178,<br />

EN 60950, <strong>and</strong> EN 60034-1.<br />

Special requests as to flammability rating have<br />

to be specified by the customer.<br />

The major part of the <strong>fans</strong> <strong>and</strong> <strong>blowers</strong> can<br />

also be supplied in CE, VDE, UL, GOST, CCC<br />

<strong>and</strong>/or CSA approved design.<br />

Ambient temperature<br />

The permissible ambient temperature refers to<br />

the operating points as specified. <strong>Axial</strong> <strong>fans</strong>,<br />

when running at free air, have the lowest power<br />

consumption <strong>and</strong> the lowest temperature rise<br />

in the motor. With rising back pressure, the<br />

motor temperature rises as well. With some<br />

<strong>fans</strong>, there is a limit as to maximum pressure.<br />

Forward curved centrifugal <strong>fans</strong> heat up most<br />

at free delivery. With some <strong>fans</strong>, a minimum<br />

pressure has to be observed. The motor temperature<br />

goes down as soon as back pressure<br />

increases.<br />

The ambient temperatures as given apply to<br />

the characteristic operating range of the <strong>fans</strong><br />

<strong>and</strong> <strong>blowers</strong>.<br />

VDE<br />

S<br />

Accessories EC-SYSTEMS<br />

EC axial<br />

EC centrifugal<br />

AC axial<br />

AC centrifugal<br />

9