01.10.2014 Views

Our Products

Our Products

Our Products

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Air Circuit Breakers ...........................................<br />

Very fast interruption by<br />

DoubleBreak system<br />

The unique "Double Break"<br />

main contact system<br />

ensures extremely fast<br />

interruption of short circuit<br />

currents and substantially<br />

reduces main contact wear.<br />

The internally symmetrical<br />

"DoubleBreak" structure<br />

allows reverse power<br />

connection. The only ACB<br />

with this facility in India<br />

No extra arc space required,<br />

vertical stacking permitted<br />

No extra arc space<br />

The TemPower2 ACB dissipates<br />

all arc energy within its unique<br />

"DoubleBreak" arc chamber. The<br />

internal energy dissipation<br />

within the ACB allows the<br />

clearance distance of the ACB<br />

to nearby earthed metal to be<br />

zero. This will assist in<br />

minimizing switchboard height<br />

and costs.<br />

Releases<br />

TemPower2 provides positive protection for electric<br />

power systems.<br />

Standard OCR with<br />

adjustment<br />

dial Type AGR-11.<br />

For General Feeder circuits<br />

L Characteristics<br />

For General Feeder circuits<br />

R Characteristics<br />

For Gererator protection<br />

Protection features<br />

Standard<br />

Long time delay<br />

Short time delay<br />

Instantaneous<br />

Optional<br />

Ground fault<br />

Reverse Power trip<br />

Enhanced OCR<br />

with adjustment<br />

dial Type AGR-21.<br />

Enhanced OCR with<br />

L.C.D.<br />

display Type AGR-22.<br />

N-phase protection<br />

Earth leakage<br />

Two channel pre trip<br />

Advance LCD display<br />

Contact temperature<br />

monitoring<br />

Communication protocol<br />

TemPower 2 Air Circuit Breakers<br />

Double Breaker : Two Steps ahead<br />

3 Pole ACBs<br />

Type Rated<br />

Current (A) Poles Breaking Capacity<br />

MRP Rs.<br />

OCR<br />

Ics=Icu at 440VAC<br />

MDO EDO<br />

AR208S 800 3 65 KA AGR-11 BL-AL 160545 188379<br />

AR212S 1250 3 65 KA AGR-11 BL-AL 176120 212170<br />

AR216S 1600 3 65 KA AGR-11 BL-AL 201983 238033<br />

AR220S 2000 3 65 KA AGR-11 BL-AL 247118 283168<br />

AR325S 2500 3 85 KA AGR-11 BL-AL 311276 347326<br />

AR332S 3200 3 85 KA AGR-11 BL-AL 364785 400835<br />

AR440S 4000 3 100 KA AGR-11 BL-AL 441762 479094<br />

4 Pole ACBs<br />

Type Rated<br />

Current (A) Poles Breaking Capacity<br />

MRP Rs.<br />

OCR<br />

Ics=Icu at 440VAC<br />

MDO EDO<br />

AR208S 800 4 65 KA AGR-11 BL-AL 191868 227918<br />

AR212S 1250 4 65 KA AGR-11 BL-AL 225282 261332<br />

AR216S 1600 4 65 KA AGR-11 BL-AL 249538 285588<br />

AR220S 2000 4 65 KA AGR-11 BL-AL 304221 340271<br />

AR325S 2500 4 85 KA AGR-11 BL-AL 395541 431591<br />

AR332S 3200 4 85 KA AGR-11 BL-AL 460760 496810<br />

AR440S 4000 4 100 KA AGR-11 BL-AL 528870 572424<br />

Prices for 5000A and 6300A on request<br />

MDO : Manual Draw out, EDO : Electrical Draw out<br />

Note : Above price is with over current release (OCR) Type AGR-11BL-AL with standard Functions LSI<br />

Long Time (L), Short Time (S) and Instanteneous (I)<br />

In Motorised Version the following are included in the above price<br />

Electrical Charging Device<br />

Closing Release<br />

Main Safety Shutter, Shunt Release and Auxiliary Switches (4C) are available as STANDARD in all the above versions<br />

Options<br />

Other Over Current Releases Functions Additional Price (Rs.)<br />

AGR-11BL-GL LSIG* 1615<br />

AGR-21BL-PS LSI with LCD display 9125<br />

AGR-21BL-PG LSIG with LCD & Communication on req.<br />

* When using a 3 Pole ACB in a 3 phase 4 wire system, additional Neutral CT is required for<br />

OCR type AGR-11BL-GL<br />

Accessories<br />

MRP Rs.<br />

Shunt Release 2680<br />

UVT - Instantaneous type 11790<br />

UVT - Delay type 11790<br />

Closing Release 2680<br />

Auxiliary Switch 778<br />

Neutral CT 800A & 1200AF 4460<br />

Neutral CT 1600A & 2000 AF 4180<br />

Neutral CT 2500A & 3200 AF 8033<br />

Neutral CT 4000AF 11261<br />

Mechanical Interlock Horizontol<br />

on req.<br />

Mechanical Interlock-Vertical<br />

on req.<br />

Key Lock (In ON)<br />

on req.<br />

Key Lock (In OFF)<br />

on req.<br />

For prices contact our nearest sales office.<br />

2<br />

Effective from 29.09.2012

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!