Troubleshooting: Burner starts and fires, but lock out on safety.<br />

Source Procedure Causes Correction<br />

Poor Fire<br />

Flame Detector<br />

Primary Control<br />

After burner<br />

fires, immediately<br />

jumper<br />

across flame<br />

detector terminals<br />

at the primary<br />

control.<br />

If burner continues<br />

to run,<br />

this may be<br />

due to poor<br />

fire. Inspect<br />

fire.<br />

If fire is good,<br />

fault is in the<br />

flame detector.<br />

Check detector<br />

circuit.<br />

If burner locks<br />

out on safety,<br />

fault is in the<br />

primary control.<br />

Unbalanced fire<br />

Too much air − −lean short fire<br />

Too little air − − long dirty fire<br />

Excessive draft<br />

Too little draft or restriction<br />

Faulty cad cell (open circuit)<br />

Loose connections or broken<br />

cad cell wires<br />

Cad cell cannot sense flame<br />

Primary control circuit failed<br />

Replace nozzle<br />

Reduce combustion air − check<br />

combustion.<br />

Increase combustion air − check<br />

combustion.<br />

Adjust barometric draft control<br />

for correct draft.<br />

Correct draft or remove restriction.<br />

Replace cad cell.<br />

Secure connections or replace<br />

cad cell holder and wire leads.<br />

Check cad cell for proper alignment.<br />

Check cad cell face and<br />

clean, if necessary.<br />

Replace primary control.<br />

Troubleshooting: Burner Starts and Fires, but Loses Flame and Lock Out on Safety<br />

Source Procedure Causes Correction<br />

Poor Fire<br />

Flame Detector<br />

<strong>Oil</strong> Supply<br />

After burner<br />

fires, immediately<br />

jumper<br />

across flame<br />

detector terminals<br />

at the primary<br />

control.<br />

If burner continues<br />

to run<br />

(does not lock<br />

out of safety),<br />

fault may be<br />

due to poor<br />

fire. Inspect<br />

fire.<br />

If fire is good,<br />

fault is in the<br />

flame detector.<br />

Check detector<br />

circuit.<br />

If burner loses<br />

flame (does<br />

not lock out on<br />

safety), fault is<br />

in the fuel system.<br />

Listen for pump whine<br />

Unbalanced fire<br />

Too much air − − lean short fire<br />

Too little air − − long dirty fire<br />

Excessive draft<br />

Too little draft or restriction<br />

Faulty cad cell (open circuit)<br />

Loose connections or broken<br />

cad cell wires<br />

Cad cell cannot sense flame<br />

Pump loses prime − air slug<br />

Pump loses prime − air leak in<br />

supply line<br />

Replace nozzle<br />

Reduce combustion air − check<br />

combustion.<br />

Increase combustion air − check<br />

combustion.<br />

Adjust barometric draft control<br />

for correct draft.<br />

Correct draft or remove restriction.<br />

Replace cad cell.<br />

Secure connections or replace<br />

cad cell holder and wire leads.<br />

Check cad cell for proper alignment.<br />

Check cad cell face and<br />

clean, if necessary.<br />

Prime pump at bleed port<br />

Check supply line for loose connections<br />

and tighten fittings.<br />

Water slug in line Check oil tank for water (over 1<br />

inch) pump or drain out water.<br />

Partially plugged nozzle or Replace nozzle.<br />

nozzle strainer<br />

Restriction in oil line<br />

Plugged fuel pump strainer<br />

Cold oil − outdoor tank<br />

Clear restriction.<br />

Clean strainer or replace pump.<br />

Change to number 1 oil.<br />

Page 22