Main Menu<br />
ENERGY EFFICIENCY<br />
Spec J1.6 – 2.<br />
Deemed-to-Satisfy Provisions<br />
Figure 2 TYPICAL R-VALUES FOR FLOOR CONSTRUCTION (for a floor without a floor heating system)— continued<br />
Floor construction description Item Item description R-Value<br />
(c) Solid concrete suspended slab,<br />
ground floor<br />
Up<br />
Down<br />
1. Indoor air film (still air) 0.11 0.16<br />
2. Solid concrete (150 mm,<br />
2400 kg/m 3 )<br />
0.10 0.10<br />
3. Outdoor air film (7 m/s) 0.03 0.03<br />
Total R-Value 0.24 0.29<br />
(d) 150 mm hollow-core concrete planks,<br />
ground floor<br />
1. Indoor air film (still air) 0.11 0.16<br />
2. Concrete topping (60 mm,<br />
2,400 kg/m 3 )<br />
3. Hollow-core concrete planks<br />
(150 mm, 1,680 kg/m 3 , 30%<br />
cores)<br />
0.04 0.04<br />
0.14 0.14<br />
4. Outdoor air film (7 m/s) 0.03 0.03<br />
Total R-Value 0.32 0.37<br />
Notes:<br />
1. The R-Value of an item, other than an air space, air film or air cavity, may be increased in<br />
proportion to the increased thickness of the item.<br />
2. The Total R-Value of a form of construction may be increased by the amount that an individual item<br />
is increased.<br />
3. For floor types (c) and (d) that are located over an internal space, the Total R-Value can be<br />
calculated by replacing the value for outdoor air film (R0.03) on the underside of the floor with the<br />
value for indoor air film (R0.11).<br />
4. The addition of 10 mm of render to the ceiling of a suspended internal concrete floor will increase<br />
the Total R-Value by 0.02.<br />
5. Solid concrete slab includes concrete beam and infill floors and concrete precast permanent<br />
formwork panels.<br />
6. Where an airspace is filled, the R-Value listed for the airspace must be deducted from the Total<br />
R-Value of the floor construction.<br />