32<br />
D. Boxes at Ceilings - Suspended (Paddle) Fan Outlets. Outlet<br />
boxes or outlet box systems used as <strong>the</strong> sole support of a ceilingsuspended<br />
(paddle) fan shall be listed, shall be marked by <strong>the</strong>ir<br />
manufacturer as suitable for this purpose, and shall not support<br />
ceiling-suspended (paddle) fans that weight more than 32 kg (70<br />
lbs.), For outlet boxes or outlet box systems designed to support<br />
ceiling-suspended (paddle) fans that weigh more than 16 kg (35<br />
lbs.), <strong>the</strong> required marking shall include <strong>the</strong> maximum weight to be<br />
supported.<br />
E. Utilization Equipment. Boxes used for <strong>the</strong> support of utilization<br />
equipment o<strong>the</strong>r than ceiling-suspended (paddle) fans shall meet <strong>the</strong><br />
requirements of NEC Article 314.27(A) and (B) for <strong>the</strong> support of a<br />
luminaire that is <strong>the</strong> same size and weight.<br />
Exception: Utilization equipment weighing not more than 3 kg (6<br />
lbs.) shall me permitted to be supported on o<strong>the</strong>r boxes or plaster<br />
rings that are secured to o<strong>the</strong>r boxes, provided <strong>the</strong> luminaire or its<br />
supporting yoke is secured to <strong>the</strong> box with no fewer than two No. 6<br />
or larger screws.<br />
6.15 CONDUIT:<br />
reinforced <strong>the</strong>rmosetting resin conduit shall be permitted under all<br />
atmospheric conditions and occupancies subject to NEC 355.10 and<br />
NEC 300.6<br />
Liquidtight Flexible Nonmetallic Conduit: The use of liquidtight<br />
flexible nonmetallic conduit shall be permitted under all atmospheric<br />
conditions and occupancies subject to NEC 356.10 and NEC 300.6<br />
Electrical Metallic Tubing (EMT): The use of electrical metallic<br />
tubing shall be permitted for both exposed and concealed work<br />
subject to NEC 358.10 (A) through (C) and NEC 300-6.<br />
Flexible Metallic Tubing (FMT): The use of flexible metallic tubing<br />
shall be permitted under all atmospheric conditions and occupancies<br />
subject to NEC 360.10 and NEC 300.6.<br />
6.15.2 Bending Radius: NEC 342.24-26, 344.24-26, 348.24-26, 350.24-26,<br />
352.24-26, 353.24-26, 354.24-26, 355.24-26, 356.24-26, 358.24-26,<br />
360.24-26<br />
6.15.3 To determine <strong>the</strong> maximum number of conductors allowed in<br />
conduit refer to NEC Annex C Tables.<br />
33<br />
6.15.1 Conduit Uses:<br />
Intermediate Metal Conduit (IMC): The use of intermediate metal<br />
conduit shall be permitted under all atmospheric conditions and<br />
occupancies subject to NEC 342.10 (A) through (D) and NEC 300.6.<br />
Rigid Metal Conduit (RMC): The use of rigid metal conduit shall be<br />
permitted under all atmospheric conditions and occupancies subject to<br />
NEC 344 and NEC 300-6.<br />
7. LIGHT CIRCUIT WIRING<br />
7.1 LIGHTING OUTLETS REQUIRED:<br />
7.1.1 At least one wall switch controlled lighting outlet shall be installed<br />
in every habitable room; in bathrooms, hallways, stairways,<br />
attached garages, and detached garages with electric power; and at<br />
outdoor entrances or exits. NEC 210.70<br />
Flexible Metal conduit (FMC): Use of flexible metal conduit shall be<br />
permitted under all atmospheric conditions and occupancies subject to<br />
NEC 348.10 and NEC 300.6.<br />
Liquid-Tight Flexible Metal Conduit (LFMC): The use of liquid-tight<br />
flexible metal conduit shall be permitted under all atmospheric<br />
conditions and occupancies subject to NEC 350.10 and NEC 300.6.<br />
Rigid Polyvinyl Chloride Conduit (PVC): The use of PVC conduit<br />
and fittings shall be permitted under all atmospheric conditions and<br />
occupancies subject to NEC 352.10(A) through (H) and NEC 300-6.<br />
High Density Polyethylene Conduit (HDPE): The use of high density<br />
polyethylene conduit shall be permitted under all atmospheric<br />
conditions and occupancies subject to NEC 353.10 and NEC 300.6<br />
7.1.2 A vehicle door in an attached garage is not considered an outdoor<br />
entrance or exit. NEC 210.70(2)(B)<br />
7.1.3 At least one lighting outlet controlled by a light switch located at<br />
<strong>the</strong> point of entry to <strong>the</strong> attic, under floor space, utility room, and<br />
basement shall be installed only where <strong>the</strong>se spaces are used for<br />
storage or containing equipment requiring servicing. The lighting<br />
outlet shall be provided at or near <strong>the</strong> equipment requiring<br />
servicing. NEC 210.70<br />
7.2 SWITCHES:<br />
7.2.1 Switches or circuit breakers shall not disconnect <strong>the</strong> grounded<br />
conductor of a circuit. NEC 404.2(B)<br />
Nonmetallic Underground Conduit (NUCC): The use of nonmetallic<br />
underground conduit shall be permitted under all atmospheric<br />
conditions and occupancies subject to NEC 354.10 and NEC 300.6<br />
Reinforced Thermosetting Resin Conduit (RTRC): The use of<br />
7.2.2 General use switches and circuit breakers shall clearly indicate<br />
whe<strong>the</strong>r <strong>the</strong>y are in <strong>the</strong> open (off) or closed (on) position. Where<br />
<strong>the</strong>se switch or circuit breaker handles are operated vertically, <strong>the</strong><br />
up position of <strong>the</strong> handle shall be <strong>the</strong> “on” position.<br />
Exception: Vertically operated double-throw switches shall be