Conductivity Meter Setup<br />
1. Install automatic dump valve prior to feed water storage tank<br />
2. Place conductivity probe in condensate line prior to the dump<br />
valve<br />
1. False sugar positives will occur during stop and go<br />
production as ammonia will buildup and set-off the alarm<br />
3. Set the conductivity valve set-point just above the background<br />
reading<br />
4. When the conductivity meter sets off the alarm, the dump valve<br />
should open automatically<br />
5. Factory personnel should test the water with Alpha-Naphthol<br />
Test<br />
1. Find the point of contamination or if it was a false positive,<br />
close the automatic valve.<br />