Conductivity Meter Setup<br />

1. Install automatic dump valve prior to feed water storage tank<br />

2. Place conductivity probe in condensate line prior to the dump<br />

valve<br />

1. False sugar positives will occur during stop and go<br />

production as ammonia will buildup and set-off the alarm<br />

3. Set the conductivity valve set-point just above the background<br />

reading<br />

4. When the conductivity meter sets off the alarm, the dump valve<br />

should open automatically<br />

5. Factory personnel should test the water with Alpha-Naphthol<br />

Test<br />

1. Find the point of contamination or if it was a false positive,<br />

close the automatic valve.<br />