<strong>TBV</strong>-C<br />

ROOM TEMPERATUR CONTROL<br />

Diagram <strong>TBV</strong>-C NF, DN 20<br />

Position<br />

kPa<br />

60<br />

50<br />

1 2 3 4 5 6 7 8 9 10<br />

40<br />

30<br />

20<br />

15<br />

10<br />

7.5<br />

5<br />

4<br />

3<br />

2<br />

1.5<br />

1<br />

20 30 40 50 75 100 150 200 300 500 750 1000<br />

2000<br />

4000<br />

l/h<br />

Position 1 2 3 4 5 6 7 8 9 10<br />

Kv 0,40 0,53 0,67 0,82 1,03 1,29 1,72 2,40 2,96 3,40<br />

Recommended area: Pos. 3-10<br />

Tour & Andersson retains the right to make changes to its products and specifications without prior notice.<br />