Chapter 5 Test Bench for the Doubly-Fed Induction Generator based ...
Chapter 5 Test Bench for the Doubly-Fed Induction Generator based ...
Chapter 5 Test Bench for the Doubly-Fed Induction Generator based ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Chapter</strong> 5<br />
<strong>Test</strong> <strong>Bench</strong> <strong>for</strong> <strong>the</strong> <strong>Doubly</strong>-<strong>Fed</strong> <strong>Induction</strong> <strong>Generator</strong><br />
<strong>based</strong> Wind Turbine <strong>Generator</strong> System<br />
This chapter describes in detail <strong>the</strong> realized test bench. The dimensioning of<br />
major components is also discussed. It is organized such that Section-5.1<br />
provides <strong>the</strong> test bench layout while Section-5.2 and Section-5.3 describe <strong>the</strong><br />
power handling and <strong>the</strong> control system components respectively.<br />
The developed setup is <strong>for</strong> a 10 kW DFIG <strong>based</strong> WTGS, controlled by Digital<br />
Signal Processing (DSP) cards from <strong>the</strong> manufacturer dSPACE [dSPACE 2011].<br />
The Semiteach converter is from <strong>the</strong> manufacturer Semikron [SEMIKRON 2005].<br />
The necessary transducers and hardware protection against short-circuit, overvoltage<br />
at <strong>the</strong> DC-link and over-temperature have been included inside chariots<br />
especially made <strong>for</strong> <strong>the</strong> test bench. The user’s manual attached as Appendix-D<br />
provides detailed in<strong>for</strong>mation on <strong>the</strong> chariots. Special ef<strong>for</strong>t has been placed to<br />
ensure safe operation of <strong>the</strong> equipment and safety of <strong>the</strong> user. Apart from <strong>the</strong><br />
functions provided by <strong>the</strong> IGBT drivers, <strong>the</strong> additional fault protection features<br />
designed are<br />
• The measurement signals (low power) are accessible at <strong>the</strong> front while<br />
<strong>the</strong> high power currents and voltages are connected at <strong>the</strong> back of <strong>the</strong><br />
chariot.<br />
• Phase indicator lamps: to show <strong>the</strong> availability of each of <strong>the</strong> grid phases.<br />
• Status LEDs: to indicate which of <strong>the</strong> contactors are currently operating.<br />
• DC-link voltage panel meter: to indicate capacitor voltage at all times.<br />
• DC-link over-voltage circuit: to avoid damage to <strong>the</strong> capacitors.<br />
• Thermal over-load circuit: to avoid damage to <strong>the</strong> semiconductors.<br />
• Audible alarm generator and latch function: to prevent fur<strong>the</strong>r operation<br />
unless <strong>the</strong> cause of <strong>the</strong> fault has been removed.<br />
• Desktop emergency push-button: to isolate <strong>the</strong> system quickly and from a<br />
safe distance, to avoid fault propagation.<br />
5.1 <strong>Test</strong> <strong>Bench</strong> Layout<br />
The layout of <strong>the</strong> test bench is presented in Figure-5.1. The components, marked<br />
with numbers, are listed in Table-5.1. The arrow, to <strong>the</strong> left of <strong>the</strong> figure, signifies<br />
<strong>the</strong> fact that <strong>the</strong> wind turbine drive train i.e. <strong>the</strong> blades, <strong>the</strong> low-speed shaft and<br />
<strong>the</strong> gear-box are to be emulated by a motor controlled by a drive. This drive<br />
takes its reference from a DSP card that runs <strong>the</strong> model of <strong>the</strong> drive-train. The<br />
o<strong>the</strong>r DSP cards control <strong>the</strong> electrical part of <strong>the</strong> generator. They send proper<br />
switching signals to <strong>the</strong> IGBT drivers and <strong>the</strong> measured currents and voltages are<br />
fed-back to <strong>the</strong> cards, after signal-conditioning and filtering. Several of <strong>the</strong><br />
components have been recuperated from existing material in <strong>the</strong> laboratory due<br />
to large time delays, up to 4 months, in delivery.<br />
5-1
Figure 5.1 – The DFIG <strong>based</strong> WTGS test bench.<br />
Table 5.1 – List of components <strong>for</strong> <strong>the</strong> DFIG <strong>based</strong> WTGS test bench.<br />
Component<br />
No.<br />
1<br />
3<br />
5<br />
8<br />
10<br />
12<br />
14<br />
Description<br />
Drive-Train<br />
Emulator-Motor<br />
Drive<br />
(30 kVA)<br />
Speed Encoder<br />
(360 pulses/rev)<br />
<strong>Doubly</strong>-<strong>Fed</strong><br />
<strong>Induction</strong> <strong>Generator</strong><br />
(15 kW)<br />
DC-link Capacitor<br />
(1100 μF, 750 V)<br />
Machine Contactors, Circuit<br />
Breakers, Over-load Relays<br />
(<strong>for</strong> a 15 kW machine)<br />
Digital Signal<br />
Processing Card<br />
(DS1104)<br />
Signal Conditioning +<br />
Filtering<br />
(±10 V, ≤ 500 Hz)<br />
Component<br />
No.<br />
2<br />
4<br />
6 & 7<br />
9<br />
11<br />
13<br />
15<br />
16 Desktop Computer (PC) 17<br />
Miscellaneous<br />
Description<br />
Drive-Train<br />
Emulator-Motor<br />
(15 kW)<br />
Torque Meter<br />
(100 Nm)<br />
IGBT <strong>based</strong><br />
Converter<br />
(20 kVA)<br />
Inductance Filter<br />
(6 mH, 30 A)<br />
Digital Signal<br />
Processing Card<br />
(DS1104)<br />
Current and Voltage<br />
Transducers<br />
(50 A, 860 V)<br />
DC Power Supply<br />
(± 15V, 5 V, 24 V)<br />
Charging Resistors<br />
(330 Ω, 300 W)<br />
Cables, Connectors, Panel Meters, Indicator Lamps etc.<br />
(5 % added to <strong>the</strong> total component costs)<br />
5-2
5.2 Power Handling Components<br />
Proper dimensioning is required especially <strong>for</strong> components which handle power,<br />
such that <strong>the</strong>y do not fail <strong>for</strong> routine operation.<br />
5.2.1 Back-to-Back Converter<br />
The 20 kVA back-to-back converter is <strong>for</strong>med using two commercially available<br />
Semiteach converters [SEMIKRON 2005]. Each converter has a diode bridge<br />
rectifier, a three-phase IGBT inverter, an IGBT chopper leg and DC-link<br />
capacitors. The drivers <strong>for</strong> <strong>the</strong> IGBTs, <strong>the</strong> heat-sink temperature measurement<br />
sensor, a protective <strong>the</strong>rmal switch and a cooling fan are integrated in <strong>the</strong><br />
converter module. The converter schematic is given in Figure-5.2.<br />
Figure 5.2 – The schematic of <strong>the</strong> Semiteach converter [SEMIKRON 2005].<br />
5.2.1.1 Component Description<br />
5.2.1.1.1 IGBT Modules<br />
The individual IGBT modules SKM 50 GB 123 D are rated at 1200 V, 50 A but <strong>the</strong><br />
maximum current recommended by <strong>the</strong> manufacturer <strong>for</strong> <strong>the</strong> Semiteach unit is<br />
30 A [Sargos 2008] [SEMIKRON 2005]. The input voltage signal level required to<br />
turn <strong>the</strong> IGBT on and off is +15 V and -15 V respectively. The typical turn-on<br />
threshold voltage is 5.5 V. The maximum saturation collector to emitter voltage is<br />
3 V (3.7 V), <strong>for</strong> junction temperature of 25 ˚C (125 ˚C), at <strong>the</strong> rated current of 50 A<br />
[SEMIKRON 2006]. The peak collector current can be 80 A but with a maximum<br />
pulse duration of 1 ms. The IGBTs have a high short-circuit current capability of<br />
500 A, at full DC voltage of 1200 V, but this short-circuit must be detected and<br />
removed within 10 μs o<strong>the</strong>rwise <strong>the</strong>re is a risk of <strong>the</strong>rmal breakdown [Sargos<br />
2008]. A maximum of 1000 short-circuit events are allowed, which must be at<br />
least 1 s apart. When <strong>the</strong> short-circuit current reaches 10 times <strong>the</strong> nominal, <strong>the</strong><br />
IGBT starts to de-saturate, <strong>the</strong> voltage between collector and emitter increases<br />
and <strong>the</strong> current is limited [Sargos 2008].<br />
5.2.1.1.2 IGBT Drivers<br />
The SKHI 22A drivers can provide an output peak current of 8 A with <strong>the</strong> +15 V<br />
and -15 V required to switch <strong>the</strong> IGBT. The gate resistor value is 30 Ω. The<br />
drivers require a supply voltage of 15 V and consume 16 mA per driver. The<br />
maximum switching frequency <strong>for</strong> <strong>the</strong> drivers is 50 kHz. There is interlocking to<br />
prevent simultaneous switch-on <strong>for</strong> <strong>the</strong> IGBTs in <strong>the</strong> same inverter leg. The<br />
driver inserts an interlock dead time of 3.3 – 4.3 µs by default.<br />
5-3
The drivers also provide an error output <strong>for</strong> protection at faults like short-circuit<br />
of <strong>the</strong> IGBT, by monitoring <strong>the</strong> collector to emitter voltage V CE, and <strong>the</strong> driver<br />
supply under-voltage 13 V. A short-circuit is detected within 5 μs [Sargos 2008].<br />
The error input to output propagation time is 0.6 μs. In fault case, <strong>the</strong> input firing<br />
pulses are ignored and <strong>the</strong> output error latch is set. In order to reset <strong>the</strong> latch,<br />
both <strong>the</strong> signal inputs should be put to zero <strong>for</strong> at least 9 μs. The absence of a<br />
fault condition is indicated by a +15 V level at <strong>the</strong> error outputs. This error<br />
output has to be included when designing an application. The driver also has an<br />
integrated short pulse suppression function, which suppresses switching pulses<br />
less than 500 ns, caused by high frequency interference at <strong>the</strong> driver input<br />
[SEMIKRON 2008].<br />
5.2.1.1.3 Snubber Capacitors<br />
The MKP type snubber capacitors, rated at 22 μF, 1600 V, are mounted directly<br />
between <strong>the</strong> collector and emitter terminals of <strong>the</strong> IGBT modules. They limit<br />
over-voltage, due to <strong>the</strong> parasitic inductances, and <strong>the</strong> high rate of change of<br />
IGBT currents. A snubber also reduces <strong>the</strong> switching losses but this function is<br />
less important <strong>for</strong> an IGBT, since it can be switched at full current with full rated<br />
voltage e.g. 1200 V [Sargos 2008].<br />
5.2.1.2 Component Dimensioning<br />
For a DFIG, <strong>the</strong> power flows through <strong>the</strong> stator ps and <strong>the</strong> rotor pr are given as<br />
[Santos-Martin et al. 2006]<br />
p<br />
s<br />
pe<br />
≈ (5.1)<br />
1 − s<br />
pr ≈ −s. p s<br />
(5.2)<br />
The selected rated slip s = – 0.12, <strong>for</strong> a rated power p e = 10 kW of <strong>the</strong> DFIG<br />
system, gives a rotor power p r equal to 1.1 kW. Now, <strong>the</strong> rotor voltage v r at a<br />
specific slip s is given as<br />
v<br />
= v .s<br />
(5.3)<br />
r s r s=<br />
1<br />
v<br />
v r =<br />
s=<br />
1<br />
r<br />
s<br />
t<br />
(5.4)<br />
r t is <strong>the</strong> turns ratio between <strong>the</strong> stator and <strong>the</strong> rotor while v s is <strong>the</strong> stator voltage.<br />
Turns ratio is an important factor <strong>for</strong> converter current dimensioning since a<br />
large ratio requires larger currents in <strong>the</strong> rotor, <strong>for</strong> <strong>the</strong> same slip power. It is<br />
<strong>the</strong>re<strong>for</strong>e recommended to select a small turns ratio, if possible [Rabelo &<br />
Hofmann 2005] [Petersson, Lundberg & Thiringer 2005] [Serban et al. 2006]<br />
[Lindholm 2003]. The turns ratio <strong>for</strong> <strong>the</strong> generator used in <strong>the</strong> test bench is 1.91,<br />
which is ra<strong>the</strong>r large. With a rated line (phase-phase) voltage of 380 V, this gives<br />
a rotor line voltage around 24 V at <strong>the</strong> rated slip and <strong>the</strong> resulting rotor phase<br />
current is 26.6 A, which is within <strong>the</strong> recommended limit.<br />
5-4
5.2.2 DC-link Capacitor<br />
Electrolytic capacitors are mostly used in automotive and industrial applications<br />
from 1 kW to 1 MW and DC voltages from 200 V to 1000 V [Sargos 2008]. The<br />
advantage, when compared to o<strong>the</strong>r capacitor technologies, is greater<br />
capacitance per unit volume while <strong>the</strong> disadvantages are <strong>the</strong> higher ESR and <strong>the</strong><br />
inability to withstand reverse voltages of a significant value. The heating losses,<br />
incurred due to current flow through <strong>the</strong> ESR, put a limit on <strong>the</strong> RMS value of <strong>the</strong><br />
ripple current that <strong>the</strong> capacitor can withstand [Anwar & Teimor 2002].<br />
5.2.2.1 Component Description<br />
Two electrolytic DC-link capacitors, each rated at 2200 μF, 400 V, are connected<br />
in series to provide an equivalent 1100 μF, 800 V rating. The capacitor voltage<br />
balancing resistors are 22 kΩ each. The DC-link capacitor will discharge through<br />
<strong>the</strong> voltage balancing resistor across it with a time constant of about 48 s.<br />
5.2.2.2 Component Dimensioning<br />
The maximum DC-link voltage specified in <strong>the</strong> datasheet of <strong>the</strong> Semiteach<br />
converter is 750 V. The peak DC-link voltage ripple ∆vDC <strong>for</strong> <strong>the</strong> converter at<br />
rated conditions, Sconv = 20 kVA, CDC = 1100 μF, vDC = 750 V and ω1 = 314.16 rad/s,<br />
is calculated to be 38.6 V or 5 % of <strong>the</strong> average DC-link voltage using Equation<br />
(5.5) [Lindholm 2003] [Bojrup 1999].<br />
Sconv<br />
1<br />
∆ vDC<br />
= .<br />
(5.5)<br />
v .C 2. ω<br />
DC<br />
DC<br />
sync<br />
For <strong>the</strong> rated slip power S conv = 1.1 kVA with C DC = 1100 μF, v DC = 380 V and ω sync =<br />
314.16 rad/s, it gives a 2.0 % peak-peak voltage ripple on <strong>the</strong> DC-link.<br />
Apart from ensuring equal voltage drop on <strong>the</strong> series connected capacitors, <strong>the</strong><br />
voltage sharing resistors provide a discharge path to <strong>the</strong> capacitors. This is<br />
important from a safety point of view. This Equation (5.6) gives <strong>the</strong> expression to<br />
calculate <strong>the</strong> voltage sharing resistance Rvsr1 <strong>for</strong> a capacitance value C1 [Evox Rifa<br />
n.d.]. For C1 = 2200 μF capacitance value this gives 30 kΩ which is close to <strong>the</strong><br />
available 22 kΩ resistances on <strong>the</strong> Semiteach.<br />
R<br />
vsr1<br />
1000<br />
= (5.6)<br />
0.015 × C<br />
1<br />
[ ] [ k Ω ] µ F<br />
For high reliability, <strong>the</strong> power loss in <strong>the</strong> resistor should be less than 50 % of its<br />
rated value while <strong>the</strong> tolerance should be better than 5 %. The consequence of<br />
omitting <strong>the</strong> voltage sharing resistor is that <strong>the</strong> DC-link voltage is limited, due to<br />
tolerance in capacitance value. This is found using Equation (5.7) [Evox Rifa n.d.].<br />
For an electrolytic capacitor of <strong>the</strong> type used in this converter, a tolerance of 20<br />
% normally exists. For a v DC = 700 V, maximum tolerance T max = 1.2, minimum<br />
tolerance T min = 0.8 and number of capacitors in series n c = 2, <strong>the</strong> voltage v cap on<br />
<strong>the</strong> minimum value capacitor would be 420 V which exceeds its rating.<br />
5-5
v<br />
cap<br />
= vDC<br />
.T max<br />
T + ( n − 1).T<br />
(5.7)<br />
max<br />
c<br />
min<br />
The determination of <strong>the</strong> capacitor combination, series or parallel, is dependent<br />
on voltage rating and <strong>the</strong> calculation of power losses. The power losses depend<br />
on <strong>the</strong> ESR value and <strong>the</strong> RMS ripple current through <strong>the</strong> capacitor, which are<br />
application dependent <strong>the</strong>mselves. The current through <strong>the</strong> capacitor consists of<br />
different frequencies, which depend on <strong>the</strong> converter switching frequency and<br />
<strong>the</strong> duty cycle of <strong>the</strong> output [Anwar & Teimor 2002]. The power loss should be<br />
determined at each frequency, with <strong>the</strong> RMS value of current and <strong>the</strong><br />
corresponding ESR, and added up [Evox Rifa n.d.]. The hot spot temperature, and<br />
thus <strong>the</strong> operational life time, can <strong>the</strong>n be determined using <strong>the</strong> <strong>the</strong>rmal<br />
resistance table usually available on request from <strong>the</strong> manufacturer. The ripple<br />
current limit, <strong>for</strong> <strong>the</strong> capacitor used in this converter, is 8.2 Arms at 100 Hz, 85 ˚C<br />
[Sargos 2008].<br />
5.2.3 Inductance Filter<br />
The idea of <strong>the</strong> inductance filter or <strong>the</strong> L filter is to put adequate impedance at<br />
<strong>the</strong> output of <strong>the</strong> converter to limit <strong>the</strong> flow of currents around <strong>the</strong> switching<br />
frequency. Although additional inductance is contributed by <strong>the</strong> grid interface<br />
trans<strong>for</strong>mer, but if <strong>the</strong> trans<strong>for</strong>mer leakage inductance is significant i.e. <strong>the</strong> grid<br />
is weak, <strong>the</strong> harmonic currents can cause voltage harmonic distortion at <strong>the</strong> lowvoltage<br />
side of <strong>the</strong> trans<strong>for</strong>mer [Chen 2005]. This can disturb <strong>the</strong> PLL on which<br />
<strong>the</strong> complete control loop relies. There<strong>for</strong>e, <strong>the</strong> major impedance contribution to<br />
<strong>the</strong> harmonic current flow should come from <strong>the</strong> inductance of <strong>the</strong> filter.<br />
The advantage of using an L filter as opposed to an LCL filter is <strong>the</strong> simple design<br />
concept. The disadvantage is that, <strong>for</strong> a specific amount of attenuation required<br />
at a switching frequency, a larger overall value of inductance is needed. The<br />
larger <strong>the</strong> inductance, <strong>the</strong> greater is <strong>the</strong> voltage drop across it <strong>the</strong>reby requiring<br />
a larger converter output voltage and <strong>the</strong> required minimum DC-link voltage<br />
[Lindholm 2003]. For good dynamic current control per<strong>for</strong>mance an additional<br />
increase in DC-link voltage is often required [Lindgren & Svensson 1995]. The<br />
larger DC-link voltage leads to a higher ripple in <strong>the</strong> current component<br />
associated with active power and <strong>the</strong>re<strong>for</strong>e a higher ripple in <strong>the</strong> active power<br />
[Lindgren & Svensson 1995]. Fur<strong>the</strong>rmore, <strong>the</strong> converter output has a higher<br />
dv/dt, when <strong>the</strong> voltage switches alternately between 0 and vDC, which can cause<br />
EMI problems <strong>for</strong> nearby equipment and insulation stress. Also <strong>the</strong> amplitude of<br />
<strong>the</strong> harmonics in <strong>the</strong> converter output voltage depends on <strong>the</strong> ratio of <strong>the</strong> DClink<br />
voltage and fundamental output voltage. It is <strong>the</strong>re<strong>for</strong>e recommended to use<br />
<strong>the</strong> PWM strategy that gives a higher converter output voltage <strong>the</strong>reby limiting<br />
<strong>the</strong> DC-link voltage required. The DC-link voltage is usually not set more than<br />
two times <strong>the</strong> phase-phase voltage [Lindgren & Svensson 1995].<br />
To reduce <strong>the</strong> inductor size, a higher switching frequency can be used but <strong>the</strong><br />
overall switching losses increase since <strong>the</strong>re will be more switching events. It<br />
might also lead to sub-harmonic output currents due to non-ideal switching, if<br />
<strong>the</strong> time to turn an IGBT on and off becomes larger than a critical percentage of<br />
5-6
<strong>the</strong> overall switching time period [Lindgren & Svensson 1995]. One solution to<br />
reduce EMI is also to turn an IGBT on and off more slowly but <strong>the</strong> sub-harmonic<br />
problem may appear, as explained above. To realize an inductance value <strong>for</strong><br />
higher power ratings, <strong>the</strong> cost of <strong>the</strong> material and weight of <strong>the</strong> product also<br />
become a concern.<br />
5.2.3.1 Component Description<br />
The three L filter units are three-phase single-core 2 mH, 30 A, 50 – 60 Hz each,<br />
provided by <strong>the</strong> manufacturer Gestufir. These filter inductances are shown in<br />
Figure-5.3.<br />
Figure 5.3 – The L filter units.<br />
5.2.3.2 Component Dimensioning<br />
The converter can be modelled as a superposition of two voltage sources, one<br />
with a frequency equal to that of <strong>the</strong> grid and <strong>the</strong> o<strong>the</strong>r with <strong>the</strong> switching<br />
frequency. On <strong>the</strong> o<strong>the</strong>r hand, <strong>the</strong> grid itself can ideally be modelled as a single<br />
voltage source at <strong>the</strong> fundamental frequency, while being a short circuit <strong>for</strong> o<strong>the</strong>r<br />
frequencies [Liserre, Blaabjerg & Hansen 2005]. Thus, <strong>the</strong> harmonic frequency<br />
circuit is just a voltage source with frequency dependent impedance at its output.<br />
The transfer characteristics from converter voltage to phase current are given by<br />
Equation (5.8). i h, v h are <strong>the</strong> h order harmonic current and voltage of <strong>the</strong><br />
fundamental frequency f sync respectively.<br />
i<br />
v<br />
h<br />
h<br />
1<br />
= (5.8)<br />
2. π .( h. f ).L<br />
sync<br />
f<br />
The frequency response is shown in Figure-5.4 <strong>for</strong> different values of L f. As a 1 st<br />
order filter it has an attenuation of -20 dB/decade [Serban et al. 2006] [Lindgren<br />
5-7
& Svensson 1995] [Peltoniemi et al. 2006]. The standards related to harmonic<br />
quality of currents exchanged with <strong>the</strong> grid are IEEE 519-1992 and IEC 1000-3-4<br />
[Liserre, Blaabjerg & Hansen 2005] [Roufi & Lamchich 2004]. A criterion of a<br />
maximum THD of 5 % is usually set <strong>for</strong> <strong>the</strong> current exchanged with <strong>the</strong> grid<br />
[Liserre, Blaabjerg & Hansen 2005] [Peltoniemi et al. 2006]. This is met at a<br />
minimum fundamental-frequency RMS current of 10 A, with simulations carried<br />
out using an inductance of 6 mH and switching frequency of 1.95 kHz. The<br />
voltage drop over <strong>the</strong> filter, in this case, is 2.0 % of <strong>the</strong> grid line voltage 220 V.<br />
From simulations, <strong>for</strong> a fundamental-frequency RMS current of 2.9 A equivalent<br />
to 1.1 kW slip power, <strong>the</strong> THD of <strong>the</strong> currents is 11 % but this current is only a<br />
fraction of <strong>the</strong> total current of <strong>the</strong> generator. The THD is calculated using<br />
Equation (4.24).<br />
Figure 5.4 – Frequency response of <strong>the</strong> inductance filter transfer characteristics.<br />
5.2.4 Emulator Motor<br />
As mentioned in Section-5.1, <strong>the</strong> drive train of <strong>the</strong> WTGS is emulated through an<br />
induction motor coupled to <strong>the</strong> DFIG, as shown in Figure-5.5.<br />
Figure 5.5 – The emulator motor (left) and <strong>the</strong> DFIG (right).<br />
5-8
5.2.4.1 Component Description<br />
The squirrel-cage induction motor selected <strong>for</strong> <strong>the</strong> emulator function is an IEC 34<br />
15 kW, 400 V, 50 Hz, 1460 rpm machine from <strong>the</strong> manufacturer 2EC. The name<br />
plate is shown in Figure-5.6.<br />
Figure 5.6 – Name plate of <strong>the</strong> induction motor <strong>for</strong> <strong>the</strong> wind turbine emulator.<br />
5.2.4.2 Component Dimensioning<br />
The catalogue data of <strong>the</strong> 15 kW slip ring induction machine, used as a DFIG, is<br />
given in Table-5.2 [VEM n.d.]. It is necessary to determine <strong>the</strong> rating of <strong>the</strong><br />
emulator motor, which allows one to generate 10 kW from this machine. With a<br />
rated efficiency of 85 %, <strong>the</strong> input power required at <strong>the</strong> shaft is 10 kW/0.85 =<br />
11.76 kW.<br />
Table 5.2 – Catalogue data of <strong>the</strong> 15 kW, 400 V, 50 Hz, 4-pole slip ring induction<br />
machine SPH 160 M4 from VEM [VEM n.d.].<br />
Stator<br />
Voltage<br />
[ V ]<br />
Stator<br />
Current<br />
[ A ]<br />
Speed<br />
[rpm]<br />
Rotor<br />
Voltage<br />
[V]<br />
Rotor<br />
Current<br />
[A]<br />
Eff.<br />
[%]<br />
Power<br />
Factor<br />
Inertia<br />
[kg.m 2 ]<br />
Y 380<br />
∆ 220<br />
Y 31.5<br />
∆ 54.5<br />
1440 205 45 85 0.85 0.128<br />
The rated slip s <strong>for</strong> <strong>the</strong> DFIG is -0.12. This is equivalent to 176 rad/s or 1680 rpm.<br />
The torque required at <strong>the</strong> shaft is <strong>the</strong>re<strong>for</strong>e 11760/176 = 66.84 Nm.<br />
To run <strong>the</strong> emulator motor at n m = 1680 rpm <strong>the</strong> output frequency f d of <strong>the</strong> drive,<br />
<strong>for</strong> a machine with poles p = 4, is 56 Hz determined using<br />
p<br />
f d = nm<br />
.<br />
120<br />
(5.9)<br />
The load capacity curves of IEC 34 motors are given in Figure-5.7 [ABB n.d.].<br />
Curve 1 is <strong>the</strong> typical continuous load capacity curve of a self-ventilated motor.<br />
The motor rated frequency and <strong>the</strong> flux weakening point are at 50 Hz.<br />
5-9
The shape of <strong>the</strong> curve is defined by <strong>the</strong> required cooling and flux weakening.<br />
Below 50 Hz, <strong>the</strong> cooling capacity of <strong>the</strong> self-ventilated motor is reduced while at<br />
frequencies above, <strong>the</strong> flux weakening region, <strong>the</strong> voltage cannot be increased<br />
fur<strong>the</strong>r. Thus in both cases, <strong>the</strong> load capacity is reduced.<br />
At 56 Hz, <strong>the</strong> specified load capacity is 90 %. Thus <strong>the</strong> nominal torque of <strong>the</strong><br />
emulator motor is 66.84/0.90 = 74.27 Nm. Finally, <strong>the</strong> rated power of <strong>the</strong><br />
required emulator motor is 74.27*1500*(2*π/60) = 11.67 kW.<br />
The higher standard offering after 11 kW is 15 kW. Thus a 15 kW squirrel-cage<br />
induction machine is selected <strong>for</strong> <strong>the</strong> emulator function.<br />
Figure 5.7 – Load Capacity Curves <strong>for</strong> IEC 34 motors [ABB n.d.].<br />
5.2.5 <strong>Generator</strong><br />
The name plate data of <strong>the</strong> DFIG is given in Table-5.2. The stator of <strong>the</strong> generator<br />
has been rewound to study winding short-circuit faults. The construction details<br />
of <strong>the</strong> machine are given in Table-5.3. All dimensions are in mm. Figure-5.8<br />
shows <strong>the</strong> rotor.<br />
Figure 5.8 – The DFIG rotor.<br />
5-10
Table 5.3 – Construction details of <strong>the</strong> DFIG with dimensions in mm.<br />
Stator<br />
No. Property Value<br />
1 Stack length 170<br />
2 Stack diameter 176<br />
3 End turns length (terminals side) 60<br />
4 End turns length (opposite side) 50<br />
5 Winding diameter (internal) 185<br />
6 Winding diameter (external) 230<br />
7 Slots 48<br />
8 Slot opening 2.65<br />
9 Slot width 7<br />
10 Slot depth 21<br />
11 Conductors in parallel 2<br />
12 Conductor diameter 1.6<br />
13 Poles 4<br />
14 Cable terminals 6<br />
15 Coil pitch 11 th slot<br />
16 Turn length 700 approx.<br />
17 Sensor PT 100<br />
Rotor<br />
No. Property Value<br />
1 Stack length 169<br />
2 Stack diameter 175<br />
3 Slots 36<br />
4 Slot opening 2.65<br />
5 Slot width 8<br />
6 Slot depth 34<br />
7 Conductors in parallel 4<br />
8 Conductor diameter 0.95<br />
9 Coil pitch (concentric) 8 th and 6 th slot<br />
10 Turns 15 approx.<br />
11 Turn length 770 approx.<br />
12 Skew angle 5˚<br />
The stator winding scheme is presented in Figure-5.9. Figure-5.10 shows <strong>the</strong><br />
rewound stator.<br />
5-11
Figure 5.9 – Scheme of <strong>the</strong> rewound DFIG stator.<br />
5-12
(a)<br />
(b)<br />
Figure 5.10 – The rewound DFIG stator. (a) Stator core. (b) Winding terminals.<br />
5.2.6 The Encoder<br />
The speed measurement is provided by an encoder integrated within an inline<br />
torque meter DR-2112 from Lorenz Messtechnik [Lorenz n.d.]. The torque output<br />
is ±5 V <strong>for</strong> 100 Nm with a sample rate 10 kSamples/s. Two TTL channels, A and B,<br />
provide 360 pulses per revolution, which are 90˚ phase shifted to allow <strong>the</strong><br />
determination of <strong>the</strong> direction of rotation. The torque meter is shown in Figure-<br />
5.11.<br />
5-13
Figure 5.11 – The torque meter.<br />
5.3 Control Hardware<br />
The control hardware consists of data acquisition and data processing devices.<br />
5.3.1 Current Transducers<br />
Five current transducers are provided <strong>for</strong> each converter. The instantaneous<br />
value transducers, LT-100S from LEM, have a bandwidth DC…150 kHz and an<br />
output of ±9.8 V <strong>for</strong> a ±50 A current input (DC/AC/pulsed). The response time at<br />
90 % of <strong>the</strong> nominal current is less than 1 μs while <strong>the</strong> accuracy and linearity are<br />
±0.5 % and less than 0.1 % respectively [LEM n.d.].<br />
5.3.2 Voltage Transducers<br />
Five voltage transducers are provided <strong>for</strong> each converter. The instantaneous<br />
value transducers, LV100 from LEM, provide ±7.5 V output <strong>for</strong> an input of ±860 V<br />
(DC/AC/pulsed). The response time at 90 % of <strong>the</strong> nominal voltage is 20 μs to<br />
100 μs while <strong>the</strong> accuracy and linearity are ±0.7 % and less than 0.1 %<br />
respectively [LEM n.d.].<br />
5.3.3 DS1104 Rapid Prototyping System<br />
The dSPACE DS1104 R&D Controller Board is <strong>based</strong> on MPC8240 processor with<br />
PPC603e core and on-chip peripherals. It is a 64 bit floating-point processor with<br />
a 250 MHz CPU. The slave DSP responsible <strong>for</strong> PWM generation is <strong>based</strong> on<br />
TMS320F240 from Texas Instruments. It is a 16 bit fixed-point processor with a<br />
20 MHz clock frequency. The hardware interface panel is shown in Figure-5.12.<br />
Figure 5.12 – Connector panel <strong>for</strong> <strong>the</strong> DS1104 R&D Controller Board.<br />
5-14
O<strong>the</strong>r features of <strong>the</strong> rapid prototyping system, related to <strong>the</strong> control system of<br />
<strong>the</strong> DFIG, are described below.<br />
5.3.3.1 Analogue to Digital Converters (ADC)<br />
The ADC inputs are present to interface with <strong>the</strong> transducers. They consist of 8<br />
channels. ADCH1 to ADCH4 are multiplexed, 16 bit resolution, to a single ADC<br />
while ADCH5 to ADCH8 are four independent ADC, each with 12 bit resolution.<br />
The input voltage limit is ±10 V. The conversion time <strong>for</strong> <strong>the</strong> multiplexed<br />
channels is 2 μs while <strong>for</strong> <strong>the</strong> parallel channels it is 800 ns.<br />
5.3.3.2 Digital to Analogue Converters (DAC)<br />
The DAC outputs are present to interface with actuators. There are 8<br />
independent DAC channels. DACH1 through DACH8 have a 16 bit resolution and<br />
voltage output limits of ±10 V. The output current limit is ±5 mA.<br />
5.3.3.3 Master PPC Digital Input/Output<br />
The 20 parallel Input/Output (I/O) provided by <strong>the</strong> master processor are<br />
indicated as Digital I/O on <strong>the</strong> connector panel. They have a TTL level and a<br />
current limit of ±5 mA.<br />
5.3.3.4 Slave PWM Digital Input/Output<br />
The digital I/O controlled by <strong>the</strong> slave DSP and marked as Slave I/O PWM on <strong>the</strong><br />
connector panel are reserved <strong>for</strong> functions related to <strong>the</strong> generation of PWM<br />
signals. They also have a TTL level but a higher current limit of ±13 mA.<br />
5.3.3.5 Incremental Encoder Interface<br />
The 24 bit digital incremental encoder interfaces, 2 in number, are present <strong>for</strong><br />
speed and position measurement. They are single-ended TTL or differential<br />
RS422, input selectable, with a maximum input frequency of 1.65 MHz.<br />
5.3.3.6 Serial Interface<br />
Two serial Universal Asynchronous Receiver and Transmitter (UART), one with<br />
RS232 and <strong>the</strong> o<strong>the</strong>r, selectable, RS422/RS485 transceiver mode are also<br />
present.<br />
5.3.4 Measurement Filter<br />
The prototype of <strong>the</strong> 2 nd order low-pass Butterworth measurement filter,<br />
discussed in Section-3.4.8, is shown in Figure-5.13. The electronic circuit<br />
equivalent to <strong>the</strong> transfer function H f of <strong>the</strong> 2 nd order filter, given in Equation<br />
(5.10), is shown in Figure-5.14. OP07 is <strong>the</strong> operational amplifier used.<br />
H<br />
f<br />
( s )<br />
1<br />
= (5.10)<br />
⎛ C f 1C<br />
f 2<br />
⎞ ⎛ 1 1 ⎞<br />
⎜ ⎟ 2<br />
s + C ⎜<br />
f 2 + ⎟s<br />
+ 1<br />
G f 1G<br />
f 2 G f 2 G<br />
⎝ ⎠ ⎝<br />
f 1 ⎠<br />
Gf1 and Gf2 are <strong>the</strong> respective conductance of resistors Rf1 and Rf2 while Cf1 and Cf2<br />
are <strong>the</strong> capacitance values. This transfer function <strong>for</strong>m implies that as long as <strong>the</strong><br />
5-15
atio between <strong>the</strong> reactance and <strong>the</strong> resistance is maintained, <strong>the</strong> frequency<br />
response will remain <strong>the</strong> same [Maxim 2003]. This will help in adjusting <strong>the</strong><br />
values of components.<br />
Figure 5.13 – The measurement filter.<br />
Figure 5.14 – Circuit of <strong>the</strong> 2 nd order low-pass filter.<br />
Equation (3.11) can be rearranged to <strong>the</strong> <strong>for</strong>m of Equation (5.10). A comparison<br />
of <strong>the</strong> corresponding coefficients of s, in <strong>the</strong> denominator of <strong>the</strong> two functions,<br />
yields <strong>the</strong> components values. With <strong>the</strong> resistor values chosen to be R f1 = R f2 = 1<br />
kΩ, <strong>the</strong> capacitance values are found to be C f1 = 450 nF and C f2 = 225 nF. Using<br />
standard values of capacitors C f1 = 470 nF and C f2 = 220 nF, <strong>the</strong> cut-off frequency<br />
is recalculated to be 494.95 Hz which is close enough to <strong>the</strong> design value of 500<br />
Hz.<br />
The delay and <strong>the</strong> attenuation introduced by <strong>the</strong> realized filter are given in<br />
Table-5.4 measured using <strong>the</strong> HAMEG 8030-5 function generator. For rotor<br />
electrical frequencies, maximum 6 Hz at s = -0.12, <strong>the</strong> delay is not noticeable even<br />
when observed with an oscilloscope.<br />
Table 5.4 – Per<strong>for</strong>mance of <strong>the</strong> realized measurement filter with a sinusoidal<br />
input signal of 10 V peak value using HAMEG 8030-5 function generator.<br />
<strong>Test</strong> No.<br />
Input Frequency Time Delay Output Voltage<br />
[ Hz ]<br />
[ ms ]<br />
[ V ]<br />
1 5 0 10<br />
2 50 0.4 10<br />
3 500 0.5 7<br />
5-16
5.4 Conclusions<br />
This chapter has introduced <strong>the</strong> components related to <strong>the</strong> developed DFIG<br />
<strong>based</strong> WTGS test bench. Component dimensioning has also been discussed.<br />
Complete details of <strong>the</strong> fabricated chariots such as <strong>the</strong> protection circuits and<br />
wiring schematics can be found in <strong>the</strong> user’s manual attached as Appendix-D.<br />
5-17
<strong>Chapter</strong> 6<br />
Experimental Results<br />
This chapter describes <strong>the</strong> tests to determine parameter values of components<br />
and <strong>the</strong> experiments carried out on <strong>the</strong> test bench. It is organized such that<br />
Section-6.1 discusses <strong>the</strong> estimation of grid impedance, DFIG electrical circuit<br />
parameters and <strong>the</strong> delay of <strong>the</strong> converter. The experiments reported in Section-<br />
6.2 and Section-6.3 are in <strong>the</strong> context of DFIG start-up, discussed in Section-3.7.<br />
Section-6.2 demonstrates <strong>the</strong> operation of <strong>the</strong> GSC, with <strong>the</strong> charging of <strong>the</strong> DClink<br />
capacitor and controller per<strong>for</strong>mance <strong>for</strong> reference tracking, disturbance<br />
rejection and reactive power generation. Section-6.3 follows <strong>the</strong> start-up steps of<br />
stator voltage generation, phase difference minimization and grid<br />
synchronization. A grid line voltage of 220 V is used. The simplified phase<br />
difference minimization technique, developed in Section-3.7.2.1, and <strong>the</strong><br />
harmonic suppression property of <strong>the</strong> control system, highlighted in Section-<br />
4.2.3, are shown to work in reality. The stand-alone operation of <strong>the</strong> generator is<br />
also tested to determine <strong>the</strong> per<strong>for</strong>mance of <strong>the</strong> voltage controller. An<br />
investigation into <strong>the</strong> erroneous oscillations observed in <strong>the</strong> RSC operation is<br />
carried out in Section-6.4. Section-6.5 is a brief treatment of <strong>the</strong> stator current<br />
frequency harmonics, <strong>for</strong> <strong>the</strong> rewound machine in <strong>the</strong> motor mode, to<br />
demonstrate <strong>the</strong> ones most affected by <strong>the</strong> winding asymmetry. Finally, some<br />
conclusions are drawn in Section-6.6.<br />
6.1 Parameter Estimation <strong>Test</strong>s<br />
The parameter values of interest need to be determined <strong>for</strong> simulations, to<br />
decide <strong>the</strong> controller gains and to account <strong>for</strong> non-ideal factors such as <strong>the</strong><br />
converter delay.<br />
6.1.1 Grid Impedance Estimation<br />
In order to make simulations representative of <strong>the</strong> test bench, measurements to<br />
ascertain <strong>the</strong> grid impedance have been carried out. The three-phase Dy11<br />
distribution trans<strong>for</strong>mer in <strong>the</strong> laboratory is rated at 100 kVA, 380 V/500 V and<br />
50 Hz. The test circuit layout is presented in Figure-6.1. The voltage at <strong>the</strong><br />
secondary side of <strong>the</strong> trans<strong>for</strong>mer can be changed in steps of 20 V. The<br />
measurements have been carried out at a line voltage of 100 V and maximum 86<br />
A, to avoid exceeding <strong>the</strong> rated voltage limits of <strong>the</strong> devices used to load <strong>the</strong><br />
trans<strong>for</strong>mer and to respect <strong>the</strong> trans<strong>for</strong>mer fuse limit of 100 A. V o, Z T and Z L<br />
represent <strong>the</strong> open-circuit voltage, <strong>the</strong> trans<strong>for</strong>mer impedance and <strong>the</strong><br />
impedance of <strong>the</strong> load respectively.<br />
Figure-6.2 plots <strong>the</strong> measurements carried out on <strong>the</strong> secondary side of <strong>the</strong><br />
trans<strong>for</strong>mer. Two types of load were used <strong>for</strong> <strong>the</strong> test. R L represents <strong>the</strong> lighting<br />
load, which is predominantly resistive. It consists of 110 V, 115 W lamps, a<br />
maximum of 60 in each phase. X L is predominantly inductive and consists of<br />
three banks. Each bank is made up of three 25.68 mH inductances, which are<br />
delta-connected. Each bank is rated at 4500 VA, 50 Hz, Y 190 V / ∆ 110 V, Y 13.6 A<br />
6-1
∆ 23.6 A, cosΦ = 0.05. There<strong>for</strong>e, <strong>the</strong> calculated impedance per phase of a bank<br />
is 0.401 + i8.056 Ω.<br />
Figure 6.1 – Circuit layout to measure <strong>the</strong> grid impedance.<br />
Figure 6.2 – Voltage regulation of <strong>the</strong> grid trans<strong>for</strong>mer.<br />
An almost linear voltage reduction with a similar slope is observed <strong>for</strong> <strong>the</strong> two<br />
cases. The trans<strong>for</strong>mer per-phase impedance is calculated to be 0.018 Ω and <strong>the</strong><br />
total three-phase short-circuit power S kg at 100 V is <strong>the</strong>re<strong>for</strong>e 586.8 kVA.<br />
6.1.2 Machine Parameter Estimation<br />
The equivalent circuit parameters of <strong>the</strong> rewound DFIG have been determined<br />
by <strong>the</strong> classical no-load, blocked-rotor and DC resistance tests [Chapman 1999].<br />
The name plate data of <strong>the</strong> DFIG are given in Table-5.2. For <strong>the</strong> no-load test, <strong>the</strong><br />
emulator motor could not be decoupled from <strong>the</strong> DFIG since <strong>the</strong> speed<br />
measurement is given by <strong>the</strong> inline torque meter. For this reason <strong>the</strong> slip is<br />
larger. The rotor is short-circuited via a liquid rheostat and <strong>the</strong> stator is fed from<br />
<strong>the</strong> grid. The no-load measurements have been recorded in plots of Figure-6.3,<br />
where <strong>the</strong> measurement corresponding to <strong>the</strong> rated phase-neutral voltage of 220<br />
V is marked. Figure-6.3(a) to Figure-6.3(f) present <strong>the</strong> stator current, <strong>the</strong> slip, <strong>the</strong><br />
rotor current, <strong>the</strong> per-phase active power, <strong>the</strong> per-phase reactive power and <strong>the</strong><br />
6-2
estimated rotational losses respectively. Below 100 V, <strong>the</strong> slip is already quite<br />
large to assume <strong>the</strong> rotor as an open-circuit.<br />
(a)<br />
(b)<br />
(c)<br />
(d)<br />
(e)<br />
(f)<br />
Figure 6.3 – No-load test on <strong>the</strong> rewound DFIG to determine equivalent circuit<br />
parameters. (a) Stator current. (b) Slip. (c) Rotor current. (d) Active power perphase.<br />
(e) Reactive power per-phase. (f) Estimated rotational losses.<br />
Table 6.1 – Blocked-rotor test on <strong>the</strong> rewound DFIG to determine equivalent<br />
circuit parameters.<br />
Stator<br />
Voltage<br />
[ V ]<br />
Stator<br />
Current<br />
[ A ]<br />
Active<br />
Power<br />
[ W ]<br />
Reactive<br />
Power<br />
[ VAr ]<br />
Rotor<br />
Current<br />
[ A ]<br />
Rotor<br />
Speed<br />
[ rpm ]<br />
22.1 16.35 185.8 315 28.85 0.0<br />
6-3
Figure 6.4 – The calculated magnetizing inductance of <strong>the</strong> rewound DFIG.<br />
Table 6.2 – The estimated electrical parameter values of <strong>the</strong> rewound DFIG<br />
determined with classical tests (referred to <strong>the</strong> stator).<br />
Stator<br />
Resistance<br />
R s [Ω]<br />
Stator<br />
Leakage<br />
Inductance<br />
Lls [mH]<br />
Magnetizing<br />
Inductance<br />
L m [mH]<br />
Rotor<br />
Leakage<br />
Inductance<br />
Llr [mH]<br />
Rotor<br />
Resistance<br />
R r [Ω]<br />
0.37 1.90 62.03 1.90 0.28<br />
The blocked-rotor test, Table-6.1, has been per<strong>for</strong>med <strong>for</strong> a stator current lower<br />
than rated, since <strong>the</strong> applied line voltage could only be increased in steps of 20 V.<br />
The magnetizing inductance curve, determined from <strong>the</strong> tests, is shown in<br />
Figure-6.4. Finally, <strong>the</strong> determined parameter values, referred to <strong>the</strong> stator, of<br />
<strong>the</strong> electrical equivalent circuit are given in Table-6.2.<br />
6.1.3 Converter Delay<br />
The consequences of converter and control system delay are readily apparent<br />
when synchronization has to be carried out with <strong>the</strong> grid. This delay causes a<br />
current flow, as soon as <strong>the</strong> converter function is enabled, which activates ei<strong>the</strong>r<br />
<strong>the</strong> DC-link over-voltage protection or <strong>the</strong> over-current protection. Figure-6.5<br />
shows <strong>the</strong> typical delays of components in <strong>the</strong> test bench obtained from <strong>the</strong><br />
datasheets. It includes <strong>the</strong> delay to generate <strong>the</strong> voltage, <strong>the</strong> delay of <strong>the</strong><br />
measurement transducer and <strong>the</strong> delay of <strong>the</strong> ADC. The components are: <strong>the</strong><br />
buffer GD74LS07, <strong>the</strong> driver SKHI 22 A, <strong>the</strong> IGBT module SKM50GB123D, <strong>the</strong><br />
voltage transducer LEM LV-100 and <strong>the</strong> ADC of DS1104 [Datasheet4U n.d.]<br />
[SEMIKRON 2008] [SEMIKRON 2006] [LEM n.d.] [dSPACE 2011]. t PLH, t PHL, t r, t f<br />
and T dt represent <strong>the</strong> propagation time <strong>for</strong> low to high logic, high to low logic,<br />
rise time, fall time and <strong>the</strong> dead time respectively.<br />
Two types of tests have been carried out to determine <strong>the</strong> source and <strong>the</strong><br />
dependence of <strong>the</strong> system delay. In one type, <strong>the</strong> sampling and <strong>the</strong> switching<br />
frequency are changed while a 50 Hz reference signal is given to <strong>the</strong> converter.<br />
6-4
For <strong>the</strong> o<strong>the</strong>r type, <strong>the</strong> frequency of <strong>the</strong> reference signal is changed while <strong>the</strong><br />
sampling and <strong>the</strong> switching frequency are kept <strong>the</strong> same. These tests determine<br />
<strong>the</strong> total system delay, starting from reference generation by <strong>the</strong> control system.<br />
Figure 6.5 – System delay <strong>for</strong> generation of voltage through <strong>the</strong> converter.<br />
The total system delay T sd is determined experimentally in <strong>the</strong> <strong>for</strong>m of phase<br />
difference θ diff, by recording both <strong>the</strong> reference voltage and <strong>the</strong> measured<br />
converter voltage in steady-state and doing an FFT on both. The equivalent time<br />
to <strong>the</strong> phase difference, <strong>for</strong> <strong>the</strong> reference voltage frequency f ref, is found using<br />
Equation (6.1a). The results of <strong>the</strong> tests are given in Table-6.3 and Table-6.4. It<br />
can be seen that <strong>the</strong> major contributor to <strong>the</strong> total system delay is <strong>the</strong> selected<br />
switching frequency. When <strong>the</strong> switching frequency is doubled, keeping <strong>the</strong> same<br />
sampling frequency, <strong>the</strong> phase difference reduces almost by half. The net system<br />
delay, apart from <strong>the</strong> converter, is approximated by subtracting <strong>the</strong> switching<br />
time period T sw from T sd. It can also be seen that <strong>the</strong> net system delay is affected<br />
by <strong>the</strong> sampling frequency.<br />
Table 6.3 – System delay with different sampling and switching frequencies<br />
at <strong>the</strong> reference voltage frequency fref = 50 Hz.<br />
<strong>Test</strong> No.<br />
Sampling<br />
Frequency<br />
[ Hz ]<br />
Switching<br />
Frequency<br />
[ Hz ]<br />
Switching<br />
Time<br />
Period<br />
Tsw<br />
Phase<br />
Difference<br />
θ diff<br />
[ ° ]<br />
Equivalent<br />
Time<br />
Delay<br />
Tsd<br />
Net<br />
System<br />
Delay<br />
[ ms ]<br />
[ ms ]<br />
[ ms ]<br />
1 7500 750 1.33 26.3 1.46 0.13<br />
2 7500 1500 0.67 14.3 0.79 0.13<br />
3 15000 1500 0.67 13.6 0.76 0.09<br />
4 15000 750 1.33 25.6 1.42 0.09<br />
Table 6.4 – System delay at different frequencies f ref <strong>for</strong> reference voltage<br />
with 1.25 kHz switching and 10 kHz sampling frequency.<br />
<strong>Test</strong> No.<br />
Frequency of<br />
<strong>the</strong> Reference<br />
Signal fref<br />
[ Hz ]<br />
Phase<br />
Difference<br />
θdiff<br />
Equivalent<br />
Time Delay T sd<br />
[ ms ]<br />
Net<br />
System Delay<br />
[ ms ]<br />
[ ° ]<br />
1 6 1.98 0.92 0.12<br />
2 12 4.01 0.93 0.13<br />
3 24 7.88 0.91 0.11<br />
4 50 16.33 0.91 0.11<br />
6-5
T<br />
sd<br />
θdiff<br />
1<br />
= .<br />
(6.1a)<br />
360 f<br />
ref<br />
T<br />
sd<br />
Ts<br />
+ 2Tsw<br />
= (6.1b)<br />
2<br />
The average total system delay can also be approximated by Equation (6.1b),<br />
provided <strong>the</strong> delay introduced by <strong>the</strong> components apart from <strong>the</strong> converter is<br />
small. Consider Figure-6.6, which has been adapted from [le Roux & van Wyk<br />
2000]. The reference voltage amplitude and <strong>the</strong> step-wise output, fundamentalfrequency<br />
voltage amplitude, from <strong>the</strong> converter can be seen. The instants when<br />
<strong>the</strong> reference voltage is sampled are marked, on <strong>the</strong> time axis, with solid vertical<br />
lines while <strong>the</strong> instants when <strong>the</strong> converter generates <strong>the</strong> corresponding output<br />
are marked with dashed vertical lines.<br />
Figure 6.6 – Approximation of total system delay Tsd [le Roux & van Wyk 2000].<br />
The converter delay is compensated by adding an equivalent angle to <strong>the</strong> angle<br />
used <strong>for</strong> <strong>the</strong> dq-abc conversion of <strong>the</strong> control voltage output [Park & Kwon 2004]<br />
[Kuperman, Rabinovici & Zhong 2004]. This way <strong>the</strong> initial large current<br />
transient is avoided. Thus <strong>the</strong> converter can be connected to <strong>the</strong> grid.<br />
Afterwards, <strong>the</strong> current control implicitly nullifies this angle by modifying <strong>the</strong><br />
reference voltages in response to <strong>the</strong> current observed.<br />
The switching wave<strong>for</strong>ms are presented in Figure-6.7(a). The first two plots are<br />
<strong>the</strong> switching signals, <strong>for</strong> <strong>the</strong> top and bottom IGBTs of a branch, sent to <strong>the</strong><br />
drivers. The last plot is <strong>the</strong> corresponding phase voltage at <strong>the</strong> output of <strong>the</strong><br />
converter, measured w.r.t. <strong>the</strong> negative terminal of <strong>the</strong> DC-link. This figure is<br />
redrawn from <strong>the</strong> observation made using an oscilloscope, at a switching<br />
frequency of 1.25 kHz with 325 V at <strong>the</strong> DC-link. Figure-6.7(b) shows a typical<br />
6-6
charging of <strong>the</strong> gate-emitter circuit of an IGBT [Sargos 2008]. This is <strong>the</strong> output<br />
of <strong>the</strong> driver. The gate resistor along with <strong>the</strong>, IGBT characteristic, gate<br />
capacitance can be approximated as an RC circuit. The gate resistor is used to<br />
improve <strong>the</strong> Electro-Magnetic Compatibility (EMC) per<strong>for</strong>mance and limit <strong>the</strong><br />
rate of gate current and consequently <strong>the</strong> over-voltage due to parasitic<br />
inductance but causes switching losses.<br />
(a)<br />
(b)<br />
Figure 6.7 – Converter switching.<br />
(a) Input switching signal and <strong>the</strong> converter output.<br />
(b) A typical driver output wave<strong>for</strong>m [Sargos 2008].<br />
The CMOS compatible IGBT drivers have <strong>the</strong> following characteristics, related to<br />
<strong>the</strong> switching per<strong>for</strong>mance [SEMIKRON 2008]:<br />
6-7
• The maximum and minimum input thresholds are 12.5 V and 4.7 V <strong>for</strong> <strong>the</strong><br />
high and low logic respectively.<br />
• The maximum input to output turn-on and turn-off propagation time<br />
delay is 1.15 μs.<br />
• An IGBT interlock dead-time of 3.3 – 4.3 μs is inserted by default and<br />
cannot be changed.<br />
• The maximum frequency <strong>for</strong> <strong>the</strong> input switching signal is 50 kHz.<br />
6.2 Grid-Side Converter Operation<br />
This section discusses <strong>the</strong> per<strong>for</strong>mance of <strong>the</strong> GSC control. <strong>Test</strong>s <strong>for</strong> reference<br />
tracking, disturbance rejection and reactive power generation are carried out. A<br />
comparison between simulation and experimental results is also provided,<br />
where some difference is observed between <strong>the</strong> two despite ef<strong>for</strong>ts to model <strong>the</strong><br />
system as accurately as possible. These differences can be due to <strong>the</strong> values<br />
assumed <strong>for</strong> components in simulations. For example, <strong>the</strong> actual value of ESR<br />
and <strong>the</strong> impedance of cables used to connect different components are not<br />
known. Never<strong>the</strong>less, <strong>the</strong> system model is close enough to <strong>the</strong> real setup to allow<br />
<strong>the</strong> use of same controller gains. The schematic of <strong>the</strong> GSC control part, from <strong>the</strong><br />
overall DFIG system, is shown in Figure-6.8. Figure-6.8(a) shows <strong>the</strong> layout of<br />
<strong>the</strong> test setup components while Figure-6.8(b) shows <strong>the</strong> control system layout.<br />
The switching frequency is 1950 Hz or 39 p.u., while <strong>the</strong> sampling frequency is<br />
3900 Hz or 78 p.u. The compensation angle <strong>for</strong> converter delay is 13˚, determined<br />
experimentally <strong>for</strong> <strong>the</strong> sampling and switching frequency used. The gains of <strong>the</strong><br />
PI controllers are found in Table-3.3.<br />
The component values used in simulations are repeated here: Lf = 6 mH, Rf = 0.1<br />
Ω, C 1 = C 2 = 2C DC = 2200 μF, R DC = 0.03 Ω, R vsr1 = R vsr2 = 22 kΩ, S kg = 586.8 kVA and<br />
<strong>the</strong> DC-link charging resistors R ch = 330 Ω. The actual X/R ratio of <strong>the</strong> grid is not<br />
known, thus <strong>for</strong> simulations a value of 2, 5, 7 and 9 was taken. The measurement<br />
noise has not been considered to observe <strong>the</strong> differences clearly. In general, <strong>the</strong><br />
X/R ratio of trans<strong>for</strong>mers increases with <strong>the</strong>ir power rating. An X/R value of 7 is<br />
<strong>the</strong> default value suggested by SimPowerSystems while an X/R value of 2 was<br />
taken from <strong>the</strong> ANSI Standard C37.010 <strong>for</strong> a 100 kVA power trans<strong>for</strong>mer<br />
[Arcadvisor n.d.].<br />
Currrent<br />
Source<br />
+<br />
s<br />
-<br />
i<br />
+ -<br />
C1<br />
C2<br />
Switch<br />
+<br />
-<br />
IdcRSC<br />
v<br />
Rvsr<br />
1<br />
Rvsr<br />
2<br />
Vdc<br />
pulses<br />
g<br />
+<br />
A<br />
B<br />
-<br />
C<br />
GSC<br />
Current<br />
Measurement<br />
A<br />
Vabc<br />
Iabc<br />
B a<br />
b<br />
C<br />
c<br />
A<br />
B<br />
C<br />
If<br />
A<br />
B<br />
C<br />
Filter Inductance<br />
Lf = 6 mH<br />
Grid Voltage<br />
Measurement<br />
Va Van<br />
Vb<br />
Vc<br />
Vbn<br />
n<br />
Vcn<br />
Contactor<br />
A<br />
B<br />
C<br />
A<br />
B<br />
C<br />
a<br />
b<br />
c<br />
A<br />
B<br />
C<br />
Charging<br />
Resistance<br />
Rch = 330 Ohm<br />
A<br />
B<br />
C<br />
Vgrid<br />
N<br />
Grid<br />
220 V, 50 Hz<br />
Skg = 586.8 kVA<br />
Idc<br />
RSC1<br />
Step<br />
Idc<br />
RSC2<br />
(a)<br />
6-8
Step<br />
1<br />
Vdc*<br />
2<br />
Vdc*<br />
1<br />
PLL<br />
Enable<br />
Vgrid_ac<br />
Vgrid_bc<br />
Grid<br />
Voltage<br />
Measurement<br />
Switch<br />
1<br />
Vac<br />
Vbc<br />
Ifa<br />
Ifb<br />
Ifc<br />
Step<br />
2<br />
Current<br />
Measurement<br />
PLL<br />
Ifd*<br />
2<br />
Ifd*<br />
1<br />
Switch<br />
2<br />
ifa<br />
Ifd<br />
ifb<br />
ifc<br />
<strong>the</strong>taPLL<br />
Ifq<br />
(a,b,c)--> (d,q)<br />
Power Invariant<br />
Vd,grid<br />
Vq,grid<br />
<strong>the</strong>taPLL<br />
fPLL<br />
Ifd*<br />
Vdc*<br />
Ifd<br />
Ifq<br />
Vd,grid<br />
Vq,grid<br />
<strong>the</strong>taPLL<br />
Vfa<br />
Vfb<br />
Vfc<br />
Control<br />
On/Off<br />
SVM_PWM<br />
Vfa<br />
Vfb<br />
Vfc<br />
Vdc<br />
PWM<br />
On/Off<br />
DC_a<br />
DC_b<br />
DC_c<br />
DC_a<br />
DC_b<br />
DC_c<br />
PWM Stop<br />
Pulses<br />
DS1104SL_DSP_PWM<br />
pulses<br />
Vdc<br />
Vdc<br />
Vector Control<br />
(b)<br />
Figure 6.8 – Schematic of <strong>the</strong> GSC system. (a) <strong>Test</strong> setup. (b) Control system.<br />
Figure 6.9 – GUI <strong>for</strong> <strong>the</strong> GSC control in dSPACE Control Desk software.<br />
Figure-6.9 shows <strong>the</strong> Graphic User Interface (GUI) developed in dSPACE Control<br />
Desk software. The experiment can be controlled in steps using <strong>the</strong> On/Off<br />
buttons. The status of I/O can be seen and <strong>the</strong> captured variables displayed. The<br />
6-9
layout is divided into different sections, like <strong>the</strong> ‘start-up’ to charge <strong>the</strong> DC-link<br />
capacitors via <strong>the</strong> anti-parallel diodes of <strong>the</strong> GSC, <strong>the</strong> ‘vector control’ to boost <strong>the</strong><br />
DC-link voltage to <strong>the</strong> operational level and <strong>the</strong> ‘acquisition’ section to control<br />
how <strong>the</strong> data is acquired.<br />
6.2.1 Reference Tracking<br />
The reference tracking per<strong>for</strong>mance is tested through charging of <strong>the</strong> DC-link<br />
capacitors up to <strong>the</strong> operational DC voltage of 380 V. Figure-6.10 presents <strong>the</strong><br />
experimental results of <strong>the</strong> charging process and <strong>the</strong> per<strong>for</strong>mance of <strong>the</strong> PLL. At<br />
time t = 1 s, capacitor charging begins via <strong>the</strong> charging resistors. The resistors are<br />
shorted out at t = 12 s and <strong>the</strong> DC-link voltage achieves <strong>the</strong> nominal value of<br />
about 320 V <strong>for</strong> <strong>the</strong> grid voltage of 225 V, see Figure-6.10(a). The PLL is enabled<br />
at t = 13 s and its recorded output is shown in Figure-6.10(c). At t = 15 s, <strong>the</strong><br />
control system is enabled with a reference voltage of 320 V <strong>for</strong> <strong>the</strong> DC-link. A<br />
transient is observed in <strong>the</strong> DC-link voltage when this is done. This is due to<br />
small error between <strong>the</strong> reference and <strong>the</strong> measured value resulting from <strong>the</strong><br />
measurement noise, <strong>for</strong> example. After t = 18 s, <strong>the</strong> reference voltage is stepped<br />
up to 380 V and at around t = 23 s it is stepped down to 320 V again. The currents<br />
measured on <strong>the</strong> grid side are shown in Figure-6.10(b) and Figure-6.10(d). It is<br />
seen in <strong>the</strong> close-up provided that although <strong>the</strong> currents are periodic <strong>the</strong>y are<br />
dominated by harmonics. The current harmonic content is presented in Figure-<br />
6.10(e), where <strong>the</strong> harmonic magnitudes Ih are reported with respect to <strong>the</strong><br />
magnitude I1, of <strong>the</strong> 50 Hz fundamental frequency component, and <strong>the</strong> numbers<br />
indicate <strong>the</strong> harmonic order.<br />
(a)<br />
(b)<br />
(c)<br />
(d)<br />
6-10
(e)<br />
Figure 6.10 – DC-link capacitor charging. (a) Capacitor voltage. (b) Filter<br />
currents. (c) PLL output. (d) Filter currents – close-up. (e) FFT i fb.<br />
A comparison between experiments and simulations is presented in Figure-6.11.<br />
The experimental results are in <strong>the</strong> left-hand column while <strong>the</strong> simulations are in<br />
<strong>the</strong> right-hand column. Figure-6.11(a) is a close-up of Figure-6.10(a) and focuses<br />
on <strong>the</strong> time during which <strong>the</strong> control is ON. In Figure-6.11(b), two cases are<br />
presented. For X/R = 2, <strong>the</strong> controller is already ON when a step change, at t = 1 s<br />
from 320 V to 380 V, in voltage reference is made. For all o<strong>the</strong>rs, <strong>the</strong> controller is<br />
turned ON with 380 V as reference. It can be seen that <strong>the</strong> overshoot is larger in<br />
<strong>the</strong> latter case. It is due to <strong>the</strong> fact that it takes some time <strong>for</strong> <strong>the</strong> controller to<br />
establish <strong>the</strong> right voltages as reference to <strong>the</strong> converter since <strong>the</strong> initial<br />
condition <strong>for</strong> <strong>the</strong> integrators of <strong>the</strong> PIs is zero. A similar observation, <strong>for</strong> <strong>the</strong><br />
same application, has been reported in literature with 1.5 p.u. current flow due to<br />
<strong>the</strong> control system delay [Teodorescu et al. 2003]. This is easily understood,<br />
since <strong>the</strong> grid can readily source current while <strong>the</strong> response time of <strong>the</strong> control<br />
system to achieve <strong>the</strong> proper converter voltage, to limit this current, is larger.<br />
The reference is achieved in about 200 ms.<br />
Figure-6.11(c), (d) and Figure-6.11(e), (f) provide <strong>the</strong> comparison <strong>for</strong> ifq and ifd<br />
current components respectively. For <strong>the</strong> experiments, <strong>the</strong> increased oscillations<br />
in <strong>the</strong> dq component currents in steady state are due to offset errors of <strong>the</strong><br />
transducers and measurement noise. For <strong>the</strong> simulations, <strong>the</strong>re is only a slight<br />
difference in <strong>the</strong> reference tracking per<strong>for</strong>mance <strong>for</strong> different X/R ratios where a<br />
larger overshoot is seen <strong>for</strong> a higher value of <strong>the</strong> ratio, see Figure-6.11(b).<br />
(a)<br />
(b)<br />
6-11
(c)<br />
(d)<br />
(e)<br />
(f)<br />
Figure 6.11 – Comparison between experiment (left-hand column) and<br />
simulation (right-hand column) <strong>for</strong> reference tracking per<strong>for</strong>mance of <strong>the</strong> GSC<br />
control.<br />
(a) and (b) DC-link voltage. (c) and (d) ifq. (e) and (f) ifd.<br />
6.2.2 Disturbance Rejection<br />
The disturbance rejection per<strong>for</strong>mance is tested by connecting a load at <strong>the</strong> DClink.<br />
For <strong>the</strong> experiments, a resistive load consisting of lamps while <strong>for</strong> <strong>the</strong><br />
simulations a controlled current source, shown in Figure-6.8(a), is used. A<br />
current of 3.15 A is drawn at <strong>the</strong> operational DC-link voltage of 380 V. The<br />
disconnection of this load is equivalent to <strong>the</strong> injection of current in <strong>the</strong> DC-link,<br />
from <strong>the</strong> RSC. It corresponds to a power injection of 1197 W. Figure-6.12<br />
presents <strong>the</strong> disturbance rejection test. The experimental results are in <strong>the</strong> lefthand<br />
column while <strong>the</strong> simulations are in <strong>the</strong> right-hand column.<br />
(a)<br />
6-12
(b)<br />
(c)<br />
(d)<br />
(e)<br />
(f)<br />
(g)<br />
(h)<br />
6-13
(i)<br />
Figure 6.12 – Comparison between experiment (left-hand column) and<br />
simulation (right-hand column) <strong>for</strong> disturbance rejection per<strong>for</strong>mance of <strong>the</strong> GSC<br />
control.<br />
(a) Lamp load current. (b) and (c) DC-link voltage. (d) and (e) i fq. (f) and (g) i fd.<br />
(h) Filter currents. (i) FFT i fb.<br />
Figure-6.12(a) shows <strong>the</strong> lamp load current. A circuit breaker is used as a switch<br />
to manually connect and disconnect <strong>the</strong> load. There<strong>for</strong>e, <strong>the</strong> connection is not<br />
instantaneous due to <strong>the</strong> spring loaded mechanism. The simulations are started<br />
with a DC-link voltage of 380 V. At t = 0.1 s, <strong>the</strong> control is enabled and a transient<br />
can be seen. The load is connected at t = 1.3 s and disconnected at t = 4 s. For <strong>the</strong><br />
experiments, <strong>the</strong> load was connected and disconnected at t = 3 s and t = 8.5 s<br />
respectively. A comparison of Figure-6.12(b) and Figure-6.12(c) indicates a<br />
notable difference in <strong>the</strong> DC-link voltage wave<strong>for</strong>ms. The X/R ratio does not<br />
seem to make much difference in <strong>the</strong>se simulations. The filter currents are<br />
shown in Figure-6.12(h) and <strong>the</strong> harmonic content is presented in Figure-6.12(i).<br />
6.2.3 Reactive Power Generation<br />
The current control loop per<strong>for</strong>mance has been tested by injecting reactive<br />
power into <strong>the</strong> grid. A step change in i fd from 0 A to 9 A is made at <strong>the</strong> DC-link<br />
voltage of 380 V. This is equivalent to an injection of about 2 kVAr. Figure-6.13<br />
presents <strong>the</strong> comparison <strong>for</strong> reactive power injection into <strong>the</strong> grid. Here a<br />
significant difference is observed <strong>for</strong> <strong>the</strong> DC-link voltage comparison shown in<br />
Figure-6.13(c) and Figure-6.13(d). Figure-6.13(g) shows <strong>the</strong> filter currents while<br />
Figure-6.13(h) shows <strong>the</strong> current harmonic content.<br />
(a)<br />
(b)<br />
6-14
(c)<br />
(d)<br />
(e)<br />
(f)<br />
(g)<br />
(h)<br />
Figure 6.13 – Comparison between experiment (left-hand column) and<br />
simulation (right-hand column) <strong>for</strong> reactive power generation per<strong>for</strong>mance of<br />
<strong>the</strong> GSC control. (a) and (b) ifd. (c) and (d) DC-link voltage. (e) and (f) ifq.<br />
(g) Filter currents. (h) FFT ifb.<br />
6-15
6.3 Rotor-Side Converter Operation<br />
The schematic of <strong>the</strong> RSC control part, from <strong>the</strong> overall DFIG system, is shown in<br />
Figure-6.14. Figure-6.14(a) shows <strong>the</strong> layout of <strong>the</strong> test setup components while<br />
Figure-6.14(b) shows <strong>the</strong> control system layout. The voltage source shown on<br />
<strong>the</strong> DC-link in Figure-6.14(a) signifies that <strong>the</strong> voltage is maintained constant<br />
ei<strong>the</strong>r through <strong>the</strong> GSC or <strong>the</strong> diode bridge rectifier supplied from <strong>the</strong> grid.<br />
Figure-6.15 shows <strong>the</strong> GUI developed in dSPACE Control Desk software. The<br />
experiment can be controlled in steps using <strong>the</strong> On/Off buttons. The status of I/O<br />
can be seen and <strong>the</strong> captured variables displayed. The layout is divided into<br />
different sections, like <strong>the</strong> ‘start-up’ to measure <strong>the</strong> grid voltages and activate <strong>the</strong><br />
PLL, <strong>the</strong> ‘vector control’ section <strong>for</strong> stator voltage generation and<br />
synchronization with <strong>the</strong> grid etc.<br />
A<br />
N B<br />
C<br />
Grid<br />
220 V,<br />
50 Hz<br />
Grid Voltage<br />
Measurement<br />
A<br />
B<br />
C<br />
Vabc<br />
a<br />
b<br />
c<br />
A<br />
B<br />
C<br />
Vgrid<br />
Contactor<br />
Is<br />
Vs<br />
A<br />
Vabc<br />
a Iabc<br />
b<br />
c<br />
B<br />
C<br />
a<br />
b<br />
c<br />
Stator Output<br />
Measurement<br />
Speed<br />
Speed<br />
w<br />
A<br />
B<br />
C<br />
DFIG<br />
m<br />
a<br />
b<br />
c<br />
Ir<br />
A<br />
Vabc<br />
Iabc<br />
B a<br />
b<br />
C<br />
c<br />
Rotor Current<br />
Measurement<br />
pulses<br />
g<br />
+<br />
A<br />
B<br />
-<br />
C<br />
RSC<br />
Vdc<br />
v + -<br />
C1<br />
C2<br />
Rvsr<br />
1<br />
Rvsr<br />
2<br />
(a)<br />
Ps*<br />
2<br />
Ps*<br />
Qs*<br />
Measurements<br />
Step<br />
1<br />
Ps*<br />
1<br />
Qs*<br />
2<br />
Switch<br />
1<br />
Control<br />
On/Off<br />
Ir<br />
Vs<br />
Is<br />
Ir<br />
Vs<br />
Is<br />
Current Control Enable<br />
Var<br />
SVM_PWM<br />
pulses<br />
Step<br />
2<br />
PLL<br />
Enable<br />
Qs*<br />
1<br />
Vac,grid<br />
Vbc,grid<br />
Grid<br />
Voltage<br />
Measurement<br />
Switch<br />
2<br />
Vac<br />
Vbc<br />
Control<br />
On/Off2<br />
Control<br />
On/Off1<br />
PLL<br />
Vd,grid<br />
Vq,grid<br />
<strong>the</strong>taPLL<br />
fPLL<br />
Control<br />
On/Off3<br />
Speed<br />
poz_error_enable<br />
Voltage Control Enable<br />
Power Control enable<br />
Vd,grid<br />
Vq,grid<br />
<strong>the</strong>taPLL<br />
fPLL<br />
Speed<br />
Vbr<br />
Vcr<br />
Var<br />
Vbr<br />
Vcr<br />
Vdc<br />
PWM<br />
On/Off<br />
DC_a<br />
DC_b<br />
DC_c<br />
DC_a<br />
DC_b<br />
DC_c<br />
PWM Stop<br />
Pulses<br />
DS1104SL_DSP_PWM<br />
Vdc<br />
Vdc<br />
Control System<br />
(b)<br />
Figure 6.14 – Schematic of <strong>the</strong> RSC system. (a) <strong>Test</strong> setup. (b) Control system.<br />
6-16
Figure 6.15 – GUI <strong>for</strong> <strong>the</strong> RSC control in dSPACE Control Desk software.<br />
As mentioned at <strong>the</strong> beginning of this chapter, <strong>the</strong> RSC operation has some<br />
problems. Erroneous periodic oscillations are observed as shown in <strong>the</strong> next<br />
section. Never<strong>the</strong>less, <strong>the</strong> tests done show that <strong>the</strong> steps defined in Section-3.7.2<br />
<strong>for</strong> DFIG start-up are indeed valid. Fur<strong>the</strong>rmore, same parameter and gain values<br />
are applicable here. The results of <strong>the</strong> investigation carried out to isolate <strong>the</strong><br />
cause or determine <strong>the</strong> conditions under which this oscillation problem occurs<br />
are reported in Section-6.4. The sample-and-hold technique presented in<br />
Section-3.7.2.1, to minimize <strong>the</strong> phase difference between <strong>the</strong> stator and <strong>the</strong> grid<br />
voltage due to <strong>the</strong> unknown position of <strong>the</strong> rotor when <strong>the</strong> control is activated, is<br />
tested here experimentally. It has not been found in <strong>the</strong> consulted literature and<br />
is a contribution of this <strong>the</strong>sis.<br />
6.3.1 Generation of Stator Voltage and Synchronization with <strong>the</strong> Grid<br />
This section corresponds to <strong>the</strong> discussion in Section-3.7.2 regarding <strong>the</strong><br />
generation of stator voltages, correction of <strong>the</strong> initial rotor position error and <strong>the</strong><br />
synchronization of stator voltage to <strong>the</strong> grid be<strong>for</strong>e connection. The results of <strong>the</strong><br />
same experiment have been divided into Figure-6.16 and Figure-6.17 to make<br />
<strong>the</strong> commentary easier. The sampling and switching frequency are both 1950 Hz<br />
while <strong>the</strong> bandwidth of <strong>the</strong> current and voltage control loop is 0.07 p.u. and 0.007<br />
p.u. respectively on a 50 Hz basis, as used <strong>for</strong> simulations in Section-3.7.<br />
6-17
(a)<br />
(b)<br />
(c)<br />
(d)<br />
(e)<br />
(f)<br />
(g)<br />
Figure 6.16 – Stator voltage generation and rotor position error correction.<br />
(a) Rotor dq currents close-up. (b) Stator and grid dq voltages close-up.<br />
(c) Speed. (d) Stator and grid dq voltages. (e) Rotor dq currents.<br />
(f) Correction angle. (g) Synchronized stator and grid voltages.<br />
6-18
6.3.1.1 Generation of Stator Voltages and Angle Correction<br />
This section focuses on <strong>the</strong> generation of stator voltages through closed-loop<br />
rotor current control and <strong>the</strong> correction of initial error due to <strong>the</strong> unknown rotor<br />
position at <strong>the</strong> start of <strong>the</strong> experiment. The experiment starts with <strong>the</strong> DFIG<br />
being rotated by <strong>the</strong> grid-fed emulator motor near synchronous speed as seen in<br />
Figure-6.16(c). The rotor current control is enabled at t = 3.45 s and <strong>the</strong> speed<br />
drops due to an opposing torque exerted by <strong>the</strong> DFIG. Although <strong>the</strong> stator<br />
terminals are open, <strong>the</strong> rotor flux causes currents in <strong>the</strong> stator core.<br />
The reference <strong>for</strong> irq is zero while <strong>the</strong> reference <strong>for</strong> ird is -10.3 A or 0.15 p.u. on a<br />
15 kW, 220 V basis. The per<strong>for</strong>mance of <strong>the</strong> current control loop is shown in<br />
Figure-6.16(a) where <strong>the</strong> reference is achieved within 350 ms. The generated<br />
stator voltages in <strong>the</strong> dq <strong>for</strong>m are seen in Figure-6.16(b) and (d). It is seen that<br />
<strong>the</strong>re is a difference between <strong>the</strong> stator and <strong>the</strong> reference grid voltages, in <strong>the</strong> dq<br />
<strong>for</strong>m. This is due to phase error caused by <strong>the</strong> initial unknown rotor position.<br />
These figures can be compared to Figure-3.27(b) in terms of <strong>the</strong> settling time <strong>for</strong><br />
<strong>the</strong> generated stator voltages. The phase angle error θ corr, shown in Figure-<br />
6.16(f), is corrected at around t = 28 s. A transient is seen in <strong>the</strong> dq rotor currents<br />
shown in Figure-6.16(e). The result of this corrective action is seen in Figure-<br />
6.16(g) where <strong>the</strong> stator voltage becomes almost in phase with that of <strong>the</strong> grid.<br />
6.3.1.2 Stator Voltage Control<br />
In order to ensure perfect synchronization be<strong>for</strong>e <strong>the</strong> stator is connected to <strong>the</strong><br />
grid, <strong>the</strong> control is handed over to <strong>the</strong> voltage control loop around t = 38 s. This is<br />
evident from Figure-6.16(e) where <strong>the</strong> current reference starts varying under<br />
<strong>the</strong> control of <strong>the</strong> external voltage loop. The nature of <strong>the</strong> erroneous periodic<br />
oscillation changes and it becomes bidirectional. This can be seen in Figure-<br />
6.16(d), (e) and (f). In principle, <strong>the</strong> stator is now ready to be connected to <strong>the</strong><br />
grid provided <strong>the</strong>se oscillations are not present.<br />
6.3.1.3 Harmonic Suppression<br />
One contribution of this work is to lay emphasis on <strong>the</strong> fact that <strong>the</strong> control<br />
system tends to suppress harmonics in <strong>the</strong> current. This is <strong>the</strong> argument in<br />
<strong>Chapter</strong>-4 where fault detection <strong>based</strong> on negative-sequence current is favoured<br />
as a result of <strong>the</strong> frequency harmonic and symmetrical component analysis<br />
carried out on <strong>the</strong> currents <strong>for</strong> stator winding short-circuit faults. The<br />
suppression of harmonics could be due to <strong>the</strong> use of Park’s trans<strong>for</strong>mation which<br />
is <strong>based</strong> on <strong>the</strong> assumption of perfect symmetry in <strong>the</strong> phases and a principal<br />
frequency on <strong>the</strong> respective stator and rotor side which converts <strong>the</strong> alternating<br />
three-phase quantities to DC values on <strong>the</strong> rotating dq reference frame. Any<br />
deviation from <strong>the</strong> DC reference values amounts to a deviation from <strong>the</strong> pure<br />
sinusoid and thus leads to control action, <strong>the</strong>reby suppressing <strong>the</strong> harmonics.<br />
The suppression of harmonics is illustrated in Figure-6.17, which is part of <strong>the</strong><br />
same experiment as Figure-6.16. It can be seen in Figure-6.17(a) that <strong>the</strong> rotor<br />
currents are sinusoidal, as compared to those seen in Figure-6.21(c) <strong>for</strong> <strong>the</strong><br />
open-loop operation, see Section-6.4.2. The references to <strong>the</strong> converter are<br />
modified by <strong>the</strong> control system to achieve this. This is evident when <strong>the</strong> duty<br />
cycles in <strong>the</strong> two cases are compared; see Figure-6.17(b) and Figure-6.21(b). The<br />
6-19
control voltages are shown in Figure-6.17(c) and (d), which should normally be<br />
sinusoidal and constant DC values respectively.<br />
(a)<br />
(b)<br />
(c)<br />
(d)<br />
Figure 6.17 – Suppression of current harmonics by <strong>the</strong> control system.<br />
(a) Rotor currents. (b) Duty cycles. (c) Control voltages in abc.<br />
(d) Control voltages in dq.<br />
6.3.2 Stand-alone <strong>Generator</strong> Operation<br />
<strong>Test</strong>s are done <strong>for</strong> <strong>the</strong> stand-alone operation to check <strong>the</strong> per<strong>for</strong>mance of <strong>the</strong><br />
control system <strong>for</strong> <strong>the</strong> stator voltage control objective. Since <strong>the</strong> stator can not be<br />
connected to <strong>the</strong> grid due to <strong>the</strong> oscillation problem, this test was done instead to<br />
create a disturbance at <strong>the</strong> stator terminals in terms of current flow. In standalone<br />
operation, <strong>the</strong> generator has to maintain voltage and frequency <strong>for</strong> <strong>the</strong> load<br />
connected to its terminals. In steady-state, <strong>the</strong> derivative terms in Equation<br />
(3.1a) and Equation (3.1b) are zero since <strong>the</strong> fluxes are constant. Expressing<br />
<strong>the</strong>se equations in terms of currents gives<br />
v<br />
sd<br />
= −R<br />
i + ω L i − ω L i<br />
(6.2a)<br />
s sd<br />
d<br />
s sq<br />
d<br />
m rq<br />
v<br />
sq<br />
= −R<br />
i − ω L i + ω L i<br />
(6.2b)<br />
s sq<br />
d<br />
s sd<br />
d<br />
m rd<br />
With <strong>the</strong> stator voltage vector aligned with <strong>the</strong> q axis, vsd = 0, and Rs ≈ 0 as be<strong>for</strong>e,<br />
<strong>the</strong> same relation <strong>for</strong> stator isq current and active power is obtained as given in<br />
Equation (3.45a) and Equation (3.46a) respectively. irq is related to isq by a<br />
6-20
constant factor L m/L s. Thus i rq will cater to <strong>the</strong> active power demand of <strong>the</strong> load.<br />
The current i rd will fulfil <strong>the</strong> reactive power demand of <strong>the</strong> DFIG and <strong>the</strong> load. If<br />
<strong>the</strong>re is no reactive power exchange at <strong>the</strong> stator terminals <strong>the</strong>n <strong>the</strong> same<br />
relation is obtained as Equation (3.40) with v sq maintained by i rd. Thus <strong>the</strong> value<br />
of i rd will remain <strong>the</strong> same in steady-state, as be<strong>for</strong>e <strong>the</strong> connection of load.<br />
Figure-6.18 presents <strong>the</strong> results of this test. In this experiment, a higher<br />
bandwidth 0.25 p.u. <strong>for</strong> <strong>the</strong> current control loop is used since <strong>the</strong> stator is not<br />
going to be connected to <strong>the</strong> grid. The test starts with <strong>the</strong> DFIG being rotated by<br />
<strong>the</strong> grid-fed emulator motor as shown in Figure-6.18(c). The rotor current<br />
control is enabled around t = 1 s. The rotor dq currents and <strong>the</strong> generated stator<br />
dq voltages are given in Figure-6.18(a) and Figure-6.18(b) respectively. The<br />
three-phase rotor currents, stator line voltages and phase currents are presented<br />
in Figure-6.18(d), (e) and (f) respectively.<br />
At t = 8 s, <strong>the</strong> initial rotor position angle is corrected. This is actually not required<br />
here since <strong>the</strong> generator is working in <strong>the</strong> stand-alone mode without requiring<br />
any synchronization with <strong>the</strong> grid. The correction angle and <strong>the</strong> corrected slip<br />
angle are shown in Figure-6.18(k) and Figure-6.18(l) respectively. It confirms<br />
again that <strong>the</strong> sample-and-hold technique is working satisfactorily.<br />
The stator voltage control is enabled at t = 16 s and <strong>the</strong>re<strong>for</strong>e <strong>the</strong> stator voltage,<br />
Figure-6.18(b), comes in phase with <strong>the</strong> reference. The reference is given as a<br />
constant voltage with 50 Hz frequency ra<strong>the</strong>r than through a PLL working on <strong>the</strong><br />
grid.<br />
(a)<br />
(b)<br />
(c)<br />
(d)<br />
6-21
(e)<br />
(f)<br />
(g)<br />
(h)<br />
(i)<br />
(j)<br />
(k)<br />
(l)<br />
6-22
(m)<br />
(n)<br />
Figure 6.18 – Stand-alone operation of <strong>the</strong> DFIG.<br />
(a) Rotor dq currents. (b) Stator dq voltages. (c) Speed. (d) Rotor abc<br />
currents. (e) Stator abc voltages (f) Stator abc currents. (g) Stator active and<br />
reactive power (h) Rotor dq voltages. (i) Rotor abc voltages. (j) Duty cycles.<br />
(k) Correction angle. (l) Slip angle. (m) Stator abc voltages close-up.<br />
(n) Stator abc currents close-up.<br />
At t = 22 s, a resistive load consisting of lamps is connected to <strong>the</strong> stator<br />
terminals of <strong>the</strong> DFIG. The DFIG works as a generator supplying a total power of<br />
2500 W to <strong>the</strong> load as shown in Figure-6.18(g). The slip of <strong>the</strong> DFIG increases<br />
which leads to an increased frequency <strong>for</strong> rotor related quantities shown in<br />
Figure-6.18(d), (h), (i), (j) and (l). Finally, a close-up of <strong>the</strong> stator voltages and<br />
currents is provided in Figure-6.18(m) and Figure-6.18(n) respectively when <strong>the</strong><br />
load is connected.<br />
6.3.2.1 Frequency Harmonic Analysis<br />
A close-up of <strong>the</strong> steady-state stator voltages and currents is presented in Figure-<br />
6.19(a) and Figure-6.19(b) respectively. Since <strong>the</strong>y have been low-pass filtered<br />
with a cut-off frequency of 500 Hz, <strong>the</strong> harmonics with a lower frequency are not<br />
affected. The harmonic analysis of <strong>the</strong> stator currents i as and i bs, given in Figure-<br />
6.19(c) and (d) respectively, shows that <strong>the</strong> harmonic content is very low. The<br />
same can be observed <strong>for</strong> <strong>the</strong> stator voltage harmonics in Figure-6.19(e) and (f).<br />
Harmonic analysis on <strong>the</strong> generated stator voltage and currents shows that <strong>the</strong><br />
fundamental frequency is indeed 50 Hz. It can be concluded that <strong>the</strong> developed<br />
control system works well.<br />
(a)<br />
(b)<br />
6-23
(c)<br />
(d)<br />
(e)<br />
(f)<br />
Figure 6.19 – Harmonic analysis of stator currents and voltages in stand-alone<br />
generator mode.<br />
(a) Stator line voltages close-up. (b) Stator phase currents close-up.<br />
(c) FFT ias. (d) FFT ibs. (e) FFT vac,stator. (f) FFT vbc,stator.<br />
6.4 <strong>Test</strong>s to Determine <strong>the</strong> Cause of <strong>the</strong> RSC Problem<br />
6.4.1 DFIG Rotor Balance<br />
First test is to determine if <strong>the</strong> DFIG rotor phases are balanced. For this, <strong>the</strong> rotor<br />
is fed from <strong>the</strong> grid with a line voltage at 60 V, 50 Hz.<br />
Figure 6.20 – Imposed grid voltage and <strong>the</strong> resulting currents measured in <strong>the</strong><br />
rotor.<br />
6-24
The DFIG is not rotating during this test and <strong>the</strong> stator terminals are opencircuited.<br />
The sampling frequency is 1950 Hz. The measured voltages and <strong>the</strong><br />
currents are shown in Figure-6.20. It is clear that <strong>the</strong> rotor phases are balanced.<br />
6.4.2 Open-Loop <strong>Test</strong><br />
The same test reported in Section-6.4.1 is repeated with <strong>the</strong> rotor now supplied<br />
through <strong>the</strong> converter in order to observe <strong>the</strong> currents. The stator terminals are<br />
open circuited, as be<strong>for</strong>e. Both <strong>the</strong> sampling and switching frequency are 1950<br />
Hz. A constant voltage reference is imposed on <strong>the</strong> converter, without activating<br />
<strong>the</strong> control. It is given in <strong>the</strong> dq <strong>for</strong>m and <strong>the</strong> slip angle is used <strong>for</strong> <strong>the</strong> dq to abc<br />
trans<strong>for</strong>mation, in order to obtain <strong>the</strong> three-phase reference voltages <strong>for</strong> <strong>the</strong><br />
converter. The speed is measured and <strong>the</strong> PLL is used to obtain <strong>the</strong> grid angle,<br />
<strong>for</strong> subsequent calculation of <strong>the</strong> slip angle. The DFIG is rotated by <strong>the</strong> emulator<br />
motor that is fed directly from <strong>the</strong> grid.<br />
(a)<br />
(b)<br />
(c)<br />
(d)<br />
(e)<br />
(f)<br />
6-25
(g)<br />
(h)<br />
Figure 6.21 – Open-loop test to observe rotor currents when supplied from <strong>the</strong><br />
converter. (a) Speed. (b) Duty-cycles. (c) Rotor phase currents.<br />
(d) Stator line voltages. (e) Slip angle. (f) Rotor dq currents.<br />
(g) Stator and grid dq voltages. (h) DC-link voltage.<br />
Figure-6.21 presents <strong>the</strong> measurements from this experiment. Figure-6.21(a)<br />
shows <strong>the</strong> speed of <strong>the</strong> coupled machines. The grid supplied emulator motor is<br />
turned ON around t = 18 s and OFF at t = 62 s. The <strong>for</strong>m of <strong>the</strong> imposed duty<br />
cycles, Figure-6.21(b), is ideal. The resulting rotor currents, however, are<br />
severely distorted; see Figure-6.21(c). The wave<strong>for</strong>m is <strong>the</strong> result of a 5 th<br />
harmonic superimposed with a phase shift of 180˚ on <strong>the</strong> fundamental frequency<br />
current. As a consequence, <strong>the</strong> generated stator voltage shown in Figure-6.21(d)<br />
is also distorted and has an envelope <strong>for</strong>m. The large oscillations observed in <strong>the</strong><br />
stator voltage be<strong>for</strong>e and after <strong>the</strong> machine is rotating could not be explained.<br />
The slip angle is shown in Figure-6.21(e), while <strong>the</strong> rotor currents and <strong>the</strong> stator<br />
voltages in dq <strong>for</strong>m are shown in Figure-6.21(f) and (g) respectively. Finally, <strong>the</strong><br />
DC-link voltage is shown in Figure-6.21(h), where a slight reduction is seen in<br />
<strong>the</strong> loaded condition.<br />
6.4.3 Closed-loop <strong>Test</strong><br />
The closed-loop test is done to observe <strong>the</strong> effect of control bandwidth.<br />
Increasing <strong>the</strong> bandwidth of current control gives an improvement but <strong>the</strong>n <strong>the</strong><br />
system becomes unstable when connection to <strong>the</strong> grid is effected. Figure-6.22<br />
compares two cases with bandwidths of 0.04 p.u. and 0.25 p.u. on left-hand and<br />
right-hand columns respectively. The bandwidth of <strong>the</strong> outer voltage control<br />
loop is 10 times less <strong>for</strong> both <strong>the</strong> cases. It is seen that with a higher bandwidth<br />
<strong>the</strong> situation is improved. The magnitude of oscillations in <strong>the</strong> rotor dq currents<br />
and stator dq voltages is less as can be seen in Figure-6.22(b) and Figure-6.22(d)<br />
respectively. The rotor three-phase currents shown in Figure-6.22(f) are also<br />
more sinusoidal.<br />
The good per<strong>for</strong>mance of <strong>the</strong> developed sample-and-hold technique, <strong>for</strong> initial<br />
rotor position error correction, is evident from Figure-6.22(c) and (d) where <strong>the</strong><br />
phase error with <strong>the</strong> grid voltage is minimized no matter what <strong>the</strong> initial position<br />
of <strong>the</strong> rotor.<br />
6-26
(a)<br />
(b)<br />
(c)<br />
(d)<br />
(e)<br />
(f)<br />
Figure 6.22 – Effect of increasing <strong>the</strong> current control bandwidth on <strong>the</strong><br />
problematic oscillations.<br />
Bandwidth: 0.04 p.u. (left-hand column), 0.25 p.u. (right-hand column)<br />
(a) and (b) Rotor dq currents. (c) and (d) Stator dq voltages.<br />
(e) and (f) Rotor three-phase currents.<br />
6.4.4 Conclusion of <strong>the</strong> Investigation<br />
Investigation into <strong>the</strong> cause of <strong>the</strong> problem reveals that <strong>the</strong> oscillations occur<br />
when <strong>the</strong> rate of change of <strong>the</strong> duty cycle is large as can be seen in Figure-6.23.<br />
6-27
Figure 6.23 – Duty cycles and <strong>the</strong> periodic oscillations.<br />
This figure is <strong>for</strong> <strong>the</strong> test reported in Section-6.3.1. At higher slips <strong>the</strong> oscillations<br />
occur more frequently as can be deduced from <strong>the</strong> figure. This has also been<br />
verified by operating <strong>the</strong> emulator motor with a drive at different speeds. O<strong>the</strong>r<br />
steps taken to identify <strong>the</strong> source of <strong>the</strong> problem are listed below:<br />
1) Interchanging <strong>the</strong> chariots to observe if <strong>the</strong> problem is due to a<br />
component installed in <strong>the</strong> chariot.<br />
2) Measuring all three rotor currents instead of two.<br />
3) <strong>Test</strong>ing various switching and sampling frequencies.<br />
4) Changing <strong>the</strong> SVM modulation technique to sinusoidal PWM.<br />
5) Using both <strong>the</strong> absolute encoder angle and <strong>the</strong> angle difference between<br />
successive samples (both given by <strong>the</strong> speed sensor). Also testing<br />
different filters on <strong>the</strong> measured speed.<br />
6) Changing <strong>the</strong> solver.<br />
7) Imposing ideal constant magnitude and frequency grid voltages as input<br />
to <strong>the</strong> PLL.<br />
8) Correcting <strong>the</strong> offset errors of <strong>the</strong> current and voltage transducers.<br />
9) Using a diode rectifier to maintain voltage at <strong>the</strong> DC-link and boosting it<br />
with <strong>the</strong> GSC.<br />
From <strong>the</strong> steps mentioned above it has be concluded that <strong>the</strong> source of <strong>the</strong><br />
oscillation problem is not <strong>the</strong> hardware installed inside <strong>the</strong> chariot or <strong>the</strong><br />
software <strong>based</strong> control algorithm. It could not be traced to a single component.<br />
However, <strong>the</strong> speed measurement and/or <strong>the</strong> switching circuit have to be <strong>the</strong><br />
cause of <strong>the</strong> problem, as concluded from Section-6.4.2.<br />
6-28
6.5 Frequency Harmonic Analysis – Motor Mode<br />
Figure-6.24 presents <strong>the</strong> recorded data during <strong>the</strong> uncontrolled motoring mode<br />
of <strong>the</strong> DFIG. The grid line voltage is 380 V, 50 Hz while <strong>the</strong> sampling frequency is<br />
1 kHz. Un<strong>for</strong>tunately, <strong>the</strong> squirrel-cage induction machine could not be loaded,<br />
thus no-load stator current measurements are analysed. The stator is connected<br />
to <strong>the</strong> grid around t = 1 s where a large stator current transient is observed as<br />
shown in Figure-6.24(b). When this is done <strong>the</strong> machine starts rotating due to<br />
currents in <strong>the</strong> rotor core although <strong>the</strong> rotor terminals are open-circuited; see<br />
Figure-6.24(a).<br />
(a)<br />
(b)<br />
(c)<br />
Figure 6.24 – Measurements on <strong>the</strong> DFIG in <strong>the</strong> motoring mode.<br />
(a) Speed. (b) Stator phase currents. (c) Rotor phase currents.<br />
(a)<br />
(b)<br />
6-29
(c)<br />
(d)<br />
(e)<br />
(f)<br />
Figure 6.25 – Harmonic analysis of stator voltages and currents <strong>for</strong> <strong>the</strong><br />
uncontrolled DFIG with a shorted rotor in <strong>the</strong> motor mode.<br />
(a) Stator line voltages close-up. (b) Stator phase currents close-up. (c) FFT i as.<br />
(d) FFT i bs. (e) FFT v ac,stator. (f) FFT v bc,stator.<br />
At t = 5 s, <strong>the</strong> rotor phases are short-circuited slowly via a liquid rheostat and <strong>the</strong><br />
machine starts to accelerate rapidly. The rotor currents are given in Figure-<br />
6.24(c). At t = 12.5 s, <strong>the</strong> rotor is completely short circuited and <strong>the</strong> machine<br />
achieves near synchronous speed.<br />
The steady-state stator line voltages and phase currents are shown in Figure-<br />
6.25(a) and Figure-6.25(b) respectively. The harmonics in <strong>the</strong> stator voltage and<br />
current are analysed by FFT. Figure-6.25(c) and Figure-6.25(d) present <strong>the</strong><br />
harmonic content of <strong>the</strong> stator currents ias and ibs respectively while Figure-<br />
6.25(e) and Figure-6.25(f) show <strong>the</strong> harmonic content of <strong>the</strong> stator line voltages<br />
vac,stator and vbc,stator respectively. The harmonic magnitudes are reported as<br />
compared to <strong>the</strong> 50 Hz fundamental frequency magnitude. Since one pole in each<br />
of <strong>the</strong> two phases of <strong>the</strong> DFIG stator has been rewound, Section-5.2.5, <strong>the</strong><br />
winding asymmetry is exacerbated. It is seen that <strong>the</strong> 3 rd and <strong>the</strong> 5 th harmonic in<br />
<strong>the</strong> stator current are <strong>the</strong> most affected and have a different magnitude in <strong>the</strong><br />
two phases while <strong>the</strong> stator line voltage harmonics are <strong>the</strong> same. A similar<br />
observation is reported in Section-4.2.2 <strong>for</strong> <strong>the</strong> no-load singly-fed induction<br />
generator, although <strong>the</strong> modelled machine is different.<br />
6-30
6.6 Conclusions<br />
This chapter has presented parameter estimation tests <strong>for</strong> <strong>the</strong> test bench<br />
components and <strong>the</strong> experiments on <strong>the</strong> GSC and RSC in <strong>the</strong> context of DFIG<br />
start-up. The designed controllers have been validated <strong>for</strong> reference tracking and<br />
disturbance rejection per<strong>for</strong>mance. The method developed in Section-3.7.2.1 <strong>for</strong><br />
initial rotor position correction has been demonstrated to work in reality. The<br />
harmonic suppression property of <strong>the</strong> control system has been demonstrated.<br />
The oscillation problem in RSC operation has been extensively investigated and<br />
possible causes have been identified. A test with stand-alone operation of <strong>the</strong><br />
DFIG has also been conducted on <strong>the</strong> side to observe <strong>the</strong> per<strong>for</strong>mance of <strong>the</strong><br />
system, although it is not <strong>the</strong> main objective. Finally, <strong>the</strong> harmonic content of <strong>the</strong><br />
stator currents in <strong>the</strong> motoring mode is analyzed and it is observed that <strong>the</strong> 3 rd<br />
and <strong>the</strong> 5 th harmonic are affected by <strong>the</strong> winding unbalance, which exists due to<br />
<strong>the</strong> rewound stator. The same observation was made in Section-4.2.2 when <strong>the</strong><br />
developed machine model, to simulate stator winding unbalance due to shortcircuits,<br />
was validated.<br />
6-31