Chilled <strong>and</strong> Hot <strong>Water</strong> Temperature Reset Controls<br />

Rationale – Hot <strong>Water</strong><br />

CALIFORNIA STATEWIDE UTILITIES CODES AND STANDARDS PROGRAM<br />

30<br />

● HW temperature reset always reduces boiler energy<br />

<strong>and</strong> piping losses <strong>and</strong> always reduces total energy,<br />

especially for condensing boilers<br />

● HW temperature reset can increase HW pump<br />

energy if the pump has a VFD. (VFDs are not cost<br />

effective or required on hot water pumps). Even if<br />

the HW pump has a VFD, increasing HW pump<br />

energy decreases boiler energy (opposite of CHW<br />

pumps!) so HWST reset always makes sense<br />

● Temperature reset is low/no cost – it requres a<br />

minor amount of programming but no additional<br />

hardware<br />

CA 2011 Utilities Title 24 2011 CASE Title <strong>Process</strong> 24 Stakeholder Update Meeting for Proposed Code Changes<br />