Chilled <strong>and</strong> Hot <strong>Water</strong> Temperature Reset Controls<br />
Rationale – Hot <strong>Water</strong><br />
CALIFORNIA STATEWIDE UTILITIES CODES AND STANDARDS PROGRAM<br />
30<br />
● HW temperature reset always reduces boiler energy<br />
<strong>and</strong> piping losses <strong>and</strong> always reduces total energy,<br />
especially for condensing boilers<br />
● HW temperature reset can increase HW pump<br />
energy if the pump has a VFD. (VFDs are not cost<br />
effective or required on hot water pumps). Even if<br />
the HW pump has a VFD, increasing HW pump<br />
energy decreases boiler energy (opposite of CHW<br />
pumps!) so HWST reset always makes sense<br />
● Temperature reset is low/no cost – it requres a<br />
minor amount of programming but no additional<br />
hardware<br />
CA 2011 Utilities Title 24 2011 CASE Title <strong>Process</strong> 24 Stakeholder Update Meeting for Proposed Code Changes<br />
May 25, 2010