UNITOR FIRE SUPPRESSION SYSTEMS<br />
<strong>Unitor</strong> 1230 Clean Agent Fire<br />
Extinguishing System<br />
• Machinery Spaces<br />
• Pump Room<br />
• Compressors Room<br />
• Other Spaces<br />
Trust us to protect you, your people and<br />
the environment
<strong>Unitor</strong> 1230 Clean Agent Fire<br />
Extinguishing System<br />
Machinery Spaces, Pump Room,<br />
Compressors Room and Other Spaces<br />
<strong>Unitor</strong> 1230 Clean Agent Fire Extinguishing System is designed as a total fl ooding<br />
system for Machinery Spaces of Category A, Cargo Pump Rooms on tankers,<br />
Cargo Compressors Rooms and Other Spaces needing fi re protection.<br />
It fulfils requirements of IMO MSC/Circ. 848 and MSC.1/Circ.1267, and is equivalent<br />
to Fire Extinguishing Systems required by SOLAS 1974 as amended, Chapter II-2.<br />
The system can be applied on merchant marine and offshore structures as design<br />
is in accordance to SOLAS and IMO MODU Code.<br />
Features and benefi ts<br />
• <strong>Unitor</strong> 1230 system using Novec 1230 Fluid*<br />
Stored as a liquid and discharged as a gas. It<br />
suppresses fire by a combination of heat absorption<br />
and chemical interference with the fl ame.<br />
• Environment<br />
No measurable impact on climate change because:<br />
• Ozone Depletion Potential (ODP) equal to zero<br />
• Global Warming Potential (GWP) is 1<br />
• Atmospheric life time of only fi ve days<br />
• Safety<br />
A low design concentration of 4 to 6% in combination<br />
with a high No Observable Adverse Effect Level<br />
(NOAEL) of 10% gives as a result a safety margin<br />
of up to 100%. The US EPA Significant New<br />
Alternatives Program (SNAP) classifies Novec 1230<br />
fl uid as acceptable for use as a total fl ooding agent<br />
in occupied spaces. In addition there is no risk of<br />
human asphyxiation since Novec 1230 is not<br />
depleting oxygen in the hazard zone.<br />
• Space saving installation<br />
• Unique discharge pattern through nozzle<br />
• Largest nozzle coverage designed specifi cally for the<br />
offshore and marine industry<br />
• A true Halon replacement alternative<br />
• Small pipe dimensions delivering:<br />
• Lower cost<br />
• Easier installation<br />
• Sea, land and air transport of liquid for service purpose<br />
*) The liquid is developed and manufactured by 3M, USA.
Technical Design<br />
The <strong>Unitor</strong> 1230 Clean Agent Fire Extinguishing System comprises Novec 1230 liquid,<br />
stored in steel cylinders, pressured with nitrogen to 34.5 bar at 21 o C, connected via<br />
cylinder valves, fl exible hoses or pipes to distribution pipelines with discharge nozzles.<br />
The cylinder valve assembly is equipped with a supervisory pressure switch connection<br />
for monitoring cylinder pressure, a pressure gauge and a safety bursting disc. Valves are<br />
actuated by electric solenoid, pneumatically or manually by handle.<br />
Depending on the application storage place accessibility – following types of installation<br />
can be used:<br />
• Modular system – when cylinders are stored directly in protected compartments or<br />
adjacently outside;<br />
• Centralised system, when requested amount of extinguishing fl uid is stored in central<br />
bank of cylinders out of protected spaces and distributed as need via distribution vales;<br />
• Combination of above.<br />
All components are designed for optimum system performance, allowing weight and<br />
installation costs to be lowered. Time delay and pre-discharge alarm is provided as per<br />
Rules requirement.<br />
Technical Data<br />
Cylinders<br />
Volume: 14 to 345 litres<br />
Storage pressure: 34.5 bar @ 21 o C<br />
Material: steel<br />
Standards: EN or US DOT<br />
Certifi cates: All major Classifi cation Societies<br />
Nozzles<br />
Material: brass, suitable for applications up to 925 o C.<br />
Sizes: ½” to 3”
Wilhelmsen Ships Equipment<br />
Mail: P.O. Box 33, No- 1324 Lysaker, Norway<br />
Tel: +47 67 584550, Fax: +47 22 134507<br />
Internet: www.wilhelmsen.com/shipsequipment<br />
For Service and Spares contact: Wilhelmsen Ships Service<br />
Mail: PO Box 33, NO-1324 Lysaker, Norway<br />
Tel: +47 67 584000, Fax: +47 67 584319<br />
Internet: www.wilhelmsen.com/shipsservice<br />
What is Wilhelmsen Ships Equipment<br />
Wilhelmsen Ships Equipment delivers safety and environmental systems for New-builds<br />
and Retrofi ts in the Marine and Offshore markets. It is present in all major shipbuilding<br />
countries and delivers after sales service through its sister company Wilhelmsen Ships<br />
Service with local expertise from 390 sites serving 2200 ports in 116 countries.<br />
Wilhelmsen Ships Equipment delivers over 1500 systems per annum from sales locations<br />
in South Korea, Japan, China, Singapore, Vietnam, Norway, Finland, The Netherlands,<br />
Sweden, Denmark, Argentina, Great Britain, Germany, Poland, Russia, France, Italy,<br />
Spain, Croatia, Greece, Turkey, Romania, Portugal, Ukraine, UAE, Iran, India, US, Canada and<br />
Brazil.<br />
Products<br />
<strong>Unitor</strong> Fire Suppression Systems<br />
CO2 Fire Extinguishing System<br />
High Expansion Foam Fire Extinguishing<br />
System<br />
Deck Foam Fire Extinguishing System<br />
Dry Chemical Powder Fire Extinguishing<br />
System<br />
Local Application Fire Fighting System<br />
Deep-Fat Cooker Fire Extinguishing System<br />
Water Based Fire Extinguishing System<br />
<strong>Unitor</strong> 1230 Clean Agent Fire Extinguishing<br />
System<br />
Sample Extraction Smoke Detection System<br />
Fire Detection and Fire Alarm System<br />
Environmental Systems<br />
<strong>Unitor</strong> Ballast Water Treatment System<br />
<strong>Unitor</strong> SOx Exhaust Gas Scrubber System<br />
Yarwil NOxcare Systems<br />
<strong>Unitor</strong> Fuel Homogeniser Systems<br />
<strong>Unitor</strong> Multi-chamber Compactor<br />
<strong>Unitor</strong> Oily Water Pod<br />
Insulation<br />
LNG Tank / LPG Tank / LNG Pipe<br />
Navy<br />
Others<br />
Oxygen/Acetylene Fixed System<br />
Fire and Safety Equipment<br />
<strong>Unitor</strong>-Generon Nitrogen Systems<br />
Nitrogen Membrane Inert Gas System<br />
Nitrogen Membrane Controlled and Modified<br />
Atmosphere System<br />
Nitrogen Cylinder System<br />
(All systems conform to the relevant SOLAS and IMO requirements and hold approvals required by class)<br />
Trust us to protect you, your people and<br />
the environment<br />
Part of Wilhelmsen Martime Services,<br />
a Wilh. Wilhelmsen group company<br />
ID. No xxxxxx