2<br />

<strong>Power</strong> <strong>supply</strong> for fire detection and fire alarm<br />

systems, smoke and heat control systems, and o<strong>the</strong>r fire<br />

protection systems, series ZSP135-DR<br />

The power <strong>supply</strong> is a guaranteed source <strong>of</strong> 24V voltage. The wall box is outfitted with a lock and has space for two batteries. The<br />

built-in breaker supervised by <strong>the</strong> controller protects <strong>the</strong> internal battery bank against too deep discharge.<br />

The power supplies are devoted to devices <strong>of</strong>:<br />

• fire detection and fire alarm systems according to EN 54-4/A2<br />

• smoke and heat control systems according to EN 12101-10<br />

• o<strong>the</strong>r fire protection systems, in particular as stipulated in section 12.2 <strong>of</strong> <strong>the</strong> Ordinance <strong>of</strong> <strong>the</strong> Polish Minister <strong>of</strong> Interior and<br />

Administration on 20.6.2007 (Dz.U. nr 143, poz. 1002, <strong>the</strong>reafter referred to as <strong>the</strong> Ordinance)<br />

The power supplies comply with EU directives: CPD (constructive products) 89/106/EEC, LVD (low voltage devices) 206/95/EC, EMC<br />

(electromagnetic compatibility) 204/108/EC.<br />

FUNCTIONS OF THE DEVICE<br />

• uninterruptible 24V power <strong>supply</strong><br />

• monitoring <strong>of</strong> <strong>the</strong> mains voltage – indication <strong>of</strong> a fault<br />

• battery test<br />

• monitoring <strong>of</strong> resistance (thus also continuity) <strong>of</strong> <strong>the</strong><br />

battery circuit<br />

• monitoring <strong>of</strong> <strong>the</strong> rectifier’s operation<br />

• full monitoring <strong>of</strong> <strong>the</strong> charging process and state <strong>of</strong><br />

charge <strong>of</strong> batteries<br />

The power <strong>supply</strong> monitors <strong>the</strong> resistance <strong>of</strong> <strong>the</strong> battery<br />

circuit – this feature is obligatory after August 31, 2009<br />

(<strong>the</strong> standard EN 54-4/A2).<br />

The power <strong>supply</strong> simultaneously complies with both<br />

EN 54-4 and EN 12101-10 (as well as with <strong>the</strong><br />

Ordinance), thus one model <strong>of</strong> <strong>the</strong> power <strong>supply</strong> can<br />

serve diverse fire protection systems.<br />

INDIVIDUAL PARAMETERS<br />

• floating mode with temperature compensation<br />

• fast charging <strong>of</strong> <strong>the</strong> battery with <strong>the</strong> charging current limitation<br />

• protection <strong>of</strong> <strong>the</strong> batteries against too deep discharge<br />

• monitoring <strong>of</strong> <strong>the</strong> battery fuse<br />

• monitoring <strong>of</strong> fuses <strong>of</strong> both outputs<br />

• monitoring <strong>of</strong> <strong>the</strong> internal temperature<br />

• visual and remote indication <strong>of</strong> alarms<br />

The power <strong>supply</strong> has <strong>the</strong><br />

certificate <strong>of</strong> compliance<br />

issued by CNBOP<br />

No. 1438/CPD/0163 and<br />

<strong>the</strong> certificate <strong>of</strong> approval<br />

No. 583/DC/CNBOP/2009<br />

Index<br />

Maximal output<br />

current Imax b<br />

Nominal output<br />

current Imax a<br />

Maximal battery<br />

capacity<br />

Dimensions<br />

(WxHxD), mm<br />

Weight with<br />

batteries<br />

ZSP135-DR-2A-1 2.0A 1.0A 18Ah 390x350x90 18kg<br />

ZSP135-DR-3A-1<br />

ZSP135-DR-3A-2<br />

3.0A<br />

2.0A<br />

1.5A<br />

18Ah<br />

28Ah<br />

390x350x90<br />

390x350x140<br />

18kg<br />

28kg<br />

ZSP135-DR-5A-1 4.0A 18Ah 390x350x90 18kg<br />

ZSP135-DR-5A-2 5.0A<br />

3.5A 28Ah 390x350x140 28kg<br />

ZSP135-DR-5A-3<br />

3.0A 40Ah 450x350x180 42kg<br />

ZSP135-DR-7A-1 6.0A 18Ah 390x350x90 18kg<br />

ZSP135-DR-7A-2 7.0A<br />

5.5A 28Ah 390x350x140 28kg<br />

ZSP135-DR-7A-3<br />

5.0A 40Ah 450x350x180 42kg


COMMON PARAMETERS<br />

Input<br />

Voltage<br />

Output<br />

Floating mode voltage (25ºC)<br />

Output voltage range<br />

Operational environment<br />

Working temperature range<br />

Resistance to corrosion<br />

Sinusoidal vibration 10…50Hz<br />

50…150Hz<br />

Ingress protection EN 60529<br />

Functional class EN 12101-10<br />

Environmental class EN 12101-10<br />

Environmental class, <strong>the</strong> Ordinance<br />

General<br />

Efficiency<br />

Temperature compensation coefficient<br />

Cooling<br />

Quiescent current<br />

Max. resistance <strong>of</strong> <strong>the</strong> battery circuit<br />

Max. battery charging current<br />

Standard compliance<br />

Electrical safety<br />

EMC immunity<br />

EMC interferences<br />

Tester <strong>of</strong> <strong>the</strong> power supplies ZSP135<br />

ZSP135-TST<br />

The tester ZSP135-TST is a portable device to carry out a fast check <strong>of</strong> all power supplies <strong>of</strong> series ZSP135-D and ZSP135-DR during <strong>the</strong>ir<br />

operation. The tester doesn’t need separate power <strong>supply</strong>. It is connected to <strong>the</strong> maintenance socket, available in each power <strong>supply</strong>.<br />

The tester is a tool for personnel responsible for set-up and maintenance. It helps to diagnose <strong>the</strong> power <strong>supply</strong> and to find a cause <strong>of</strong> a<br />

malfunction without dismounting <strong>the</strong> power <strong>supply</strong>.<br />

CHARACTERISTIC FEATURES<br />

• handy casing<br />

• powered by ZSP135-D or ZSP135-DR<br />

• direct connection to <strong>the</strong> tested power <strong>supply</strong><br />

• possibility to force <strong>the</strong> battery test<br />

• LCD to show measured values<br />

FUNCTIONS OF THE DEVICE<br />

• diagnostics and check <strong>of</strong> parameters <strong>of</strong> <strong>the</strong> power <strong>supply</strong> and<br />

<strong>the</strong> battery bank<br />

ul. Toruńska 8, 44-122 Gliwice, Poland, phone +48 32 23 99 400, fax +48 32 23 99 409 • www.merawex.com.pl<br />

184…230…253<br />

26.8V<br />

20…28V<br />

-25ºC...+55ºC, +75ºC over 2h<br />

25 ppm SO 2 at +25º and 93% humidity<br />

1g<br />

3g<br />

IP 43<br />

A<br />

2<br />

I<br />

min 77…82%<br />

-48mV/ ºC<br />

convection<br />

max 35mA<br />

250mΩ<br />

2A<br />

EN 60950-1 class I<br />

EN 50130-4/A2<br />

The Ordinance, section 12.2.2.2 a ÷ g<br />

Radio disturbance EN 55022/A1 level B<br />

harmonic EN 61000-3-2<br />

fluctuations EN 61000-3-3<br />

• indications:<br />

- battery voltage<br />

- output voltage<br />

- battery charging current<br />

- time to wait until <strong>the</strong> next battery test and <strong>the</strong> voltage <strong>of</strong> <strong>the</strong><br />

last performed test<br />

- value <strong>of</strong> <strong>the</strong> resistance <strong>of</strong> <strong>the</strong> battery circuit (ZSP135-DR only)<br />

- temperature inside <strong>the</strong> box<br />

• check <strong>of</strong> continuity <strong>of</strong> <strong>the</strong> battery circuit<br />

3


4<br />

<strong>Power</strong> supplies <strong>of</strong> voice alarming systems<br />

ZDSO400<br />

Voice alarming systems require a guaranteed source <strong>of</strong> voltage to ensure <strong>supply</strong> <strong>of</strong> power over a specified duration needed by<br />

efficient evacuation from endangered zones.<br />

MERAWEX has developed and manufactures power supplies <strong>of</strong> series ZDSO400 for voice alarming systems Praesideo and Plena by<br />

Bosch, and Sinaps by Ultrak and Honeywell. A standard 19” rack cabinet <strong>of</strong> height up to 50U forms <strong>the</strong> main frame <strong>of</strong> <strong>the</strong> system to<br />

host not only elements <strong>of</strong> <strong>the</strong> power <strong>supply</strong>, but also elements <strong>of</strong> <strong>the</strong> voice alarming system (amplifiers, controllers, etc.). The power<br />

system takes care about <strong>supply</strong>ing <strong>the</strong> mains (primary) power as well as <strong>the</strong> backup power <strong>of</strong> 24V or 48V from own battery banks.<br />

The battery banks are protected against too deep discharge. It is possible to apply a single rack or a set <strong>of</strong> a few racks – <strong>the</strong> system<br />

allows for operation in a distributed mode. Reliability <strong>of</strong> <strong>the</strong> system can be improved by adding a supplementary power <strong>supply</strong> unit<br />

which can be used also to increase charging current. The power supplies ZDSO400 comply with EU directives: CPD (constructive<br />

products) 89/106/EEC, LVD (low voltage devices) 206/95/EC, EMC (electromagnetic compatibility) 204/108/EC.<br />

FEATURES AND FUNCTIONS OF THE POWER SUPPLY<br />

ZDSO400<br />

• no limitation as for <strong>the</strong> number <strong>of</strong> rack cabinets in <strong>the</strong> system<br />

• distribution <strong>of</strong> <strong>the</strong> mains and backup power to <strong>the</strong> modules <strong>of</strong><br />

<strong>the</strong> voice alarming systems<br />

• alarming in case <strong>of</strong> detected malfunctions <strong>of</strong> <strong>the</strong> system<br />

• possibility to connect with a fire alarm control panel<br />

• precise regulation <strong>of</strong> floating mode voltage – temperature<br />

compensation<br />

• fast charging <strong>of</strong> <strong>the</strong> battery with <strong>the</strong> charging current limitation<br />

• monitoring <strong>of</strong> low and high battery voltage<br />

• monitoring <strong>of</strong> continuity <strong>of</strong> battery circuits and protection <strong>of</strong><br />

batteries against too deep discharge<br />

• surge protection <strong>of</strong> <strong>the</strong> mains line<br />

• visual, sound and remote indication <strong>of</strong> alarms<br />

• history <strong>of</strong> events recorded in non volatile memory<br />

• wheels as optional outfit <strong>of</strong> <strong>the</strong> cabinet<br />

indication <strong>of</strong> high resistance <strong>of</strong> <strong>the</strong> battery bank<br />

and circuits connected to it<br />

Having conducted supplementary tests against EN 54-4/A2, conformity and approval was<br />

recertified for <strong>the</strong> power supplies.<br />

certificate <strong>of</strong> conformity: certificate <strong>of</strong> approval: date:<br />

ZDSO400D-AK4 nr 2144/2006 0463/2008 19.10.2009<br />

ZDSO400E-AK3 nr 2157/2006 0343/2008 24.09.2009<br />

ZDSO400D-AK3 nr 1438/CPD/0129 0456/2008 24.09.2009<br />

According to <strong>the</strong> obligatory since September 1, 2009 amendment A2 to EN 54-4 <strong>the</strong> power supplies have<br />

been extended by a measuring set consisting <strong>of</strong> <strong>the</strong> battery resistance meter RMB-1 and DC meters<br />

CP-100 in each battery string. The requirement to monitor high resistance <strong>of</strong> <strong>the</strong> battery bank is included<br />

in <strong>the</strong> standard EN 54-16 for voice alarming systems too, because this standard refers to EN 54-4.<br />

Adjustment <strong>of</strong> <strong>the</strong> power supplies to <strong>the</strong> amendment A2 is <strong>the</strong> necessary and sufficient condition that<br />

complete voice alarming systems continue to comply with <strong>the</strong> technical approvals used in <strong>the</strong> process<br />

<strong>of</strong> <strong>the</strong>ir certification. The monitoring <strong>of</strong> resistance <strong>of</strong> <strong>the</strong> battery circuit (backup source <strong>of</strong> power)<br />

increases reliability <strong>of</strong> <strong>the</strong> power system, thus also reliability <strong>of</strong> <strong>the</strong> whole voice alarming system.


BASIC PARAMETERS<br />

Size <strong>of</strong> <strong>the</strong> system<br />

Type <strong>of</strong> <strong>the</strong> 19” rack cabinet<br />

Usable height <strong>of</strong> <strong>the</strong> rack<br />

Number <strong>of</strong> amplifiers <strong>of</strong> <strong>the</strong> voice alarming systems<br />

Primary power (mains)<br />

Input voltage<br />

Surge protection <strong>of</strong> <strong>the</strong> mains line<br />

General<br />

Working temperature range<br />

Cooling<br />

Ingress protection<br />

Weight after setup<br />

Standard compliance<br />

Electrical safety<br />

EMC immunity<br />

EMC interferences<br />

<strong>Power</strong> <strong>supply</strong> <strong>of</strong> <strong>the</strong> “fireman’s <strong>microphone”</strong><br />

<strong>ZSP25</strong>-E-<strong>MS</strong> / <strong>ZSP25</strong>-D-<strong>MS</strong><br />

The power <strong>supply</strong> is devoted to uninterruptible <strong>supply</strong> <strong>of</strong> power to a stand with <strong>the</strong> microphone operated by a fireman in distributed<br />

systems <strong>of</strong> voice alarming. It was designed in a wall box with a lock to protect against access by unauthorized persons. The box can<br />

be unlocked by a standard light fireman’s axe. Backup <strong>of</strong> output voltage after a mains failure: 24h <strong>of</strong> standby, 0.5h <strong>of</strong> alarm.<br />

ul. Toruńska 8, 44-122 Gliwice, Poland, phone +48 32 23 99 400, fax +48 32 23 99 409 • www.merawex.com.pl<br />

600x600 or 800x600<br />

min 24U max 50U<br />

depending on <strong>the</strong> rack<br />

1 phase 230V +10% -15% or 3 phases 3x230V/400V +10% -15%<br />

class III (D) 3kA<br />

-5…+40°C<br />

forced<br />

IP30<br />

depending on <strong>the</strong> rack and configuration<br />

EN 60950-1 class I<br />

EN 50130-4/A2<br />

The Ordinance, section 12.2.2.2 a ÷ g<br />

Radio disturbance EN 55022/A1 level B<br />

harmonic EN 61000-3-2<br />

fluctuations EN 61000-3-3<br />

The power supplies <strong>ZSP25</strong>-E-<strong>MS</strong> and<br />

<strong>ZSP25</strong>-D-<strong>MS</strong> are integrated parts <strong>of</strong> <strong>the</strong><br />

voice alarming systems Praesideo and<br />

Sinaps, respectively, certified by CNBOP.<br />

5


6<br />

Versatile modular power supplies <strong>of</strong> series Cameleon<br />

Versatile modular power supplies CAMELEON are a family <strong>of</strong> products <strong>of</strong> unified construction and power in <strong>the</strong> range between<br />

150 and 600W. The standard voltage converters are <strong>of</strong>fered independently as single output power supplies or are <strong>the</strong> basis for<br />

power supplies with supplementary functions. Basic voltage versions are: 12, 24 and 48V. O<strong>the</strong>r versions are available on request.<br />

The single output power supplies can be used to power fiber optic interfaces or o<strong>the</strong>r devices in voice alarming systems. For<br />

uninterruptible operation <strong>of</strong> <strong>the</strong> powered equipment <strong>the</strong> battery backup version <strong>of</strong> <strong>the</strong> CAMELEON power <strong>supply</strong> is recommended to<br />

use. The version <strong>of</strong> <strong>the</strong> battery backup devices with monitoring <strong>of</strong> <strong>the</strong> battery has functionality complying with <strong>the</strong> standard<br />

EN 54-4 applicable in systems <strong>of</strong> fire detection and alarming.<br />

AVAILABLE VOLTAGES AND CURRENTS<br />

Nominal<br />

output<br />

voltage<br />

BASIC PARAMETERS OF POWER SUPPLIES<br />

Input<br />

Voltage<br />

Frequency<br />

<strong>Power</strong> factor<br />

General<br />

Efficiency<br />

Working temperature range<br />

Ingress protection<br />

Nominal output current (power)<br />

12V 10A (125W) 12A (150W) 16A (200W) 24A (300W) 32A (400W)<br />

24V 6A (150W) 8A (200W) 12A (300W) 16A (400W) 24A (600W)<br />

48V 3A (150W) 4A (200W) 6A (300W) 8A (400W) 12A (600W)<br />

* - power supplies without PFC can operate in <strong>the</strong> range <strong>of</strong> 187... 297Vdc<br />

CREATION OF THE INDEX OF THE POWER SUPPLY<br />

ZM 24V 12A - 300 B - 00<br />

Nominal output voltage<br />

Attention:<br />

The floating mode voltage is preset in power<br />

supplies to cooperate with batteries<br />

Nominal output current<br />

Attention:<br />

The available output current <strong>of</strong> power supplies<br />

to cooperate with batteries is decreased<br />

by <strong>the</strong> charging current<br />

Construction discriminant<br />

151, 201, 301 – no PFC<br />

200, 300, 400, 600 – with PFC<br />

184..230..253V AC or 165 ..220..297VDC*<br />

47..53 Hz<br />

0.95<br />

up to 87%<br />

-33°C...+70°C<br />

IP20<br />

Installation version<br />

00 – screw terminals<br />

10 – sockets and plugs<br />

Built-in function<br />

none – single output power <strong>supply</strong><br />

R – parallel work<br />

B – cooperation with a battery bank<br />

P – cooperation with a battery bank and monitoring<br />

<strong>of</strong> its state (compliance with EN 54-4)<br />

A – cooperation with a battery bank and monitoring<br />

<strong>of</strong> its state, incl. high resistance<br />

(compliance with EN 54-4/A2)<br />

S – custom made power <strong>supply</strong>


Battery backup power supplies in wall boxes CAMELEON BOX<br />

The power supplies Cameleon Box are dedicated to <strong>supply</strong> guaranteed DC voltage 12V, 24V or 48V up to 300W <strong>of</strong> power. The wall<br />

box is outfitted with a lock and three cable transits, and has space to mount batteries.<br />

FUNCTIONS OF THE DEVICE<br />

• LEDs indicating <strong>the</strong> state <strong>of</strong> operation (POWER, BATTERY)<br />

• overload protection <strong>of</strong> outputs and battery<br />

• protection <strong>of</strong> <strong>the</strong> batteries against too deep discharge (LVDD)<br />

• floating mode with temperature compensation (internal temperature probe)<br />

• possibility to input an external alarm (option)<br />

optional indication <strong>of</strong> <strong>the</strong> state <strong>of</strong> primary and separately <strong>of</strong> secondary power – LEDs on <strong>the</strong> box door and relays<br />

BASIC PARAMETERS<br />

Input<br />

Voltage<br />

Frequency<br />

<strong>Power</strong> factor<br />

Backup power source<br />

Nominal voltage <strong>of</strong> VRLA batteries<br />

Maximal capacity <strong>of</strong> <strong>the</strong> battery bank<br />

General<br />

Output power<br />

Efficiency<br />

Working temperature range<br />

Ingress protection<br />

* - power supplies <strong>of</strong> power up to 150W operate at voltage within <strong>the</strong> range <strong>of</strong> 187 ... 297Vdc<br />

** - for power supplies <strong>of</strong> power <strong>of</strong> 200 : 300W<br />

CREATION OF THE INDEX OF THE POWER SUPPLY<br />

Box dimensions:<br />

1B – 390x350x90<br />

2B – 390x350x140<br />

3B – 450x350x180<br />

Z<strong>MS</strong> - 1B - 12V - 10A<br />

Nominal output current<br />

ul. Toruńska 8, 44-122 Gliwice, Poland, phone +48 32 23 99 400, fax +48 32 23 99 409 • www.merawex.com.pl<br />

184..230..253VAC, 165..220..297VDC*<br />

47..53Hz<br />

0.95**<br />

12V 24V 48V<br />

80Ah 40Ah 12Ah<br />

120÷300W<br />

up to 87%<br />

-33°C..+55°C<br />

IP43<br />

Attention:<br />

The output current is decreased by <strong>the</strong> charging<br />

current.<br />

Nominal output voltage<br />

(12V, 24V, 48V)<br />

Attention:<br />

The floating mode voltage is preset.<br />

7


8<br />

Multi-output power supplies for CCTV<br />

ZW<br />

The power supplies are dedicated to <strong>supply</strong> DC voltage <strong>of</strong> 12V to CCTV cameras. Depending on version a unit can power up to 16<br />

cameras independently. The power supplies are designed as wall boxes with mounted one or two power modules (MZ), and one<br />

or two output modules (MW).<br />

CHARACTERISTIC FEATURES<br />

• regulated output voltage<br />

• easy scalability <strong>of</strong> <strong>the</strong> number <strong>of</strong> outputs<br />

• light compact construction (up to 2 kg)<br />

TABLE OF VERSIONS<br />

Index<br />

Number <strong>of</strong> outputs<br />

Type<br />

<strong>of</strong> protection<br />

Description<br />

Number <strong>of</strong> outputs – number <strong>of</strong> protected outputs <strong>of</strong> <strong>the</strong> power <strong>supply</strong><br />

Type <strong>of</strong> protection – type <strong>of</strong> output protection<br />

T – fuse<br />

P – polyswitch<br />

Varistors<br />

Relay<br />

• LEDs indicating proper operation <strong>of</strong> each output<br />

• protection against overload or short circuit (fuse or polyswitch)<br />

• relay indicating proper operation (option)<br />

• surge protection <strong>of</strong> each output line (option)<br />

Index<br />

Number <strong>of</strong> outputs<br />

Type<br />

<strong>of</strong> protection<br />

ZW4-A T ZW12-A T<br />

ZW4-AW T х ZW12-AW T х<br />

ZW4-AP T х ZW12-AP T х<br />

ZW4-APW<br />

ZW4-B<br />

4<br />

T<br />

P<br />

х х ZW12-APW<br />

ZW12-B<br />

12<br />

T<br />

P<br />

х х<br />

ZW4-BW P х ZW12-BW P х<br />

ZW4-BP P х ZW12-BP P х<br />

ZW4-BPW<br />

P х х ZW12-BPW<br />

P х х<br />

ZW8-A T ZW16-A T<br />

ZW8-AW T х ZW16-AW T х<br />

ZW8-AP T х ZW16-AP T х<br />

ZW8-APW<br />

ZW8-B<br />

8<br />

T<br />

P<br />

х х ZW16-APW<br />

ZW16-B<br />

16<br />

T<br />

P<br />

х х<br />

ZW8-BW P х ZW16-BW P х<br />

ZW8-BP P х ZW16-BP P х<br />

ZW8-BPW<br />

P х х ZW16-BPW<br />

P х х<br />

Varistors<br />

Relay<br />

Varistors – outputs <strong>of</strong> output modules are protected additionally by<br />

varistors<br />

Relay – a relay to indicate 12V voltage failure (three contacts)


TABLE OF VERSIONS OF OUTPUT MODULES MW<br />

Index<br />

Number <strong>of</strong> outputs<br />

Type<br />

<strong>of</strong> protection<br />

Adapters 12V<br />

Varistors<br />

Relay<br />

Index<br />

Type<br />

<strong>of</strong> protection<br />

MW4-A T MW8-A T<br />

MW4-AW T х MW8-AW T х<br />

MW4-AP T х MW8-AP T х<br />

MW4-APW<br />

MW4-B<br />

4<br />

T<br />

P<br />

х х MW8-APW<br />

MW8-B<br />

8<br />

T<br />

P<br />

х х<br />

MW4-BW P х MW8-BW P х<br />

MW4-BP P х MW8-BP P х<br />

MW4-BPW<br />

P х х MW8-BPW<br />

P х х<br />

BASIC PARAMETERS OF THE POWER SUPPLY<br />

Input<br />

Voltage<br />

Output<br />

Voltage<br />

Number <strong>of</strong> outputs<br />

Maximal current<br />

<strong>Power</strong><br />

Operational environment<br />

Allowable working temperature<br />

Allowable working humidity<br />

Electrical safety<br />

EMC immunity<br />

EMC interferences<br />

Number <strong>of</strong> outputs<br />

The adapters to <strong>supply</strong> DC voltage <strong>of</strong> 12V to IT and telecom equipment, devices <strong>of</strong> industrial automation and CCTV. They are outfitted<br />

with 180cm <strong>of</strong> cable terminated by a 5.5/2.1 plug.<br />

BASIC PARAMETERS OF THE POWER SUPPLY<br />

Input<br />

Voltage<br />

Output<br />

100...240Vac<br />

Voltage 12Vdc<br />

Current 1250 mA<br />

Operational environment<br />

Allowable working temperature -10°C...+40°C<br />

Allowable working humidity<br />

Compliance with safety requirements<br />

20%...90%<br />

Electrical safety EN 60950-1, protection class II<br />

Level <strong>of</strong> EMC interferences class B (EN 55022)<br />

Varistors<br />

Relay<br />

TABLE OF VERSIONS<br />

OF POWER MODULES MZ<br />

Index Description<br />

MZ-1<br />

To cooperate with output<br />

modules MW4<br />

MZ-2<br />

To cooperate with output<br />

modules MW8<br />

230Vac +10% -15%<br />

12Vdc<br />

4, 8, 12 or 16<br />

0.5A for each output (1A versions on request)<br />

25W…130W<br />

-10ºC ...+40ºC<br />

20% …90%<br />

EN 60950-1 class I<br />

EN 61000-3-2, EN 61000-4-2/-3/-4/-5/-6/-8/-11<br />

Radio disturbance EN 55022/A1 level B<br />

harmonic EN 61000-3-2<br />

fluctuations EN 61000-3-3<br />

ul. Toruńska 8, 44-122 Gliwice, Poland, phone +48 32 23 99 400, fax +48 32 23 99 409 • www.merawex.com.pl<br />

9


10<br />

<strong>Power</strong> supplies to cooperate with batteries<br />

EL25, EL50<br />

The power supplies EL25 and EL50 are a regulated source <strong>of</strong> DC voltage, power <strong>of</strong> 25W and 50W, respectively. They are constant<br />

frequency switching power supplies. They are devoted to cooperate with a battery bank connected as a buffer.<br />

FUNCTIONS OF THE DEVICE<br />

• UI output characteristic<br />

• protection against overload or short circuit<br />

• visual indication <strong>of</strong> presence <strong>of</strong> output voltage<br />

• indication <strong>of</strong> battery mode<br />

• indication <strong>of</strong> low battery<br />

• possibility to cut <strong>of</strong>f <strong>the</strong> load from output voltage<br />

CHARACTERISTIC FEATURES<br />

• charging current limitation<br />

• protection <strong>of</strong> <strong>the</strong> battery bank against too deep discharge<br />

• possibility to switch <strong>the</strong> unit on from <strong>the</strong> battery – “cold start”<br />

AGM batteries<br />

Maintenance free batteries are used to cooperate with battery backup power supplies. We <strong>of</strong>fer maintenance free batteries <strong>of</strong> <strong>the</strong><br />

following brands: Panasonic, Europower, SSB, Acumax and Alarmtec. Because <strong>of</strong> gas recombination <strong>the</strong>re is no need to replace<br />

electrolyte, and batteries can be applied in rooms without dedicated forced ventilation .<br />

FEATURES<br />

• AGM technology<br />

• design life up to 15 years<br />

• voltage <strong>of</strong> single monoblocks: 2V, 6V i 12V<br />

• range <strong>of</strong> capacity from 0.8 to 300Ah<br />

• small internal resistance<br />

• operation possible in arbitrary orientation<br />

• broad range <strong>of</strong> working temperature<br />

• DIN rail clip<br />

• <strong>the</strong>oretical MTBF <strong>of</strong> 1.5 million hours (according to Telcordia SR-<br />

332, taking into account electrical stress <strong>of</strong> single elements)<br />

Input voltage<br />

184..230..253VAC (47 ÷ 63 Hz)<br />

Protection class Class I according to EN 60950-1<br />

Weight 0.35kg<br />

Dimensions (HxWxD) mm<br />

82 x 47 x 125<br />

EMC immunity<br />

EN 61000-3-2 EN 61000-4-2/-3/-4/-5/-6/-8/-11<br />

Radio disturbance EN 55022/A1 level B<br />

EMC interferences<br />

harmonic EN 61000-3-2<br />

fluctuations EN 61000-3-3<br />

EL25-B EL25- D EL50-B EL50-D<br />

Output parameters<br />

Voltage 13.2V 26.4V 13.6V 27.2V<br />

Nominal current 1.4A 0.7A 2.8A 1.4A<br />

Output current limitation 2.0 ÷ 2.9A 1.0 ÷ 1.45A 4.0 ÷ 5.8A 2 ÷ 2.8A<br />

Charging current limitation<br />

0.5 ÷ 0.7A 0.25 ÷ 0.35A 1.0 ÷ 1.4A 0.5 ÷ 0.7A<br />

Voltage to indicate low battery 11.0 ÷ 11.9V 20.0 ÷ 23.8V 11.0 ÷ 11.9V 20.0 ÷ 23.8V<br />

Voltage to disconnect <strong>the</strong> battery bank 9.2 ÷ 10.4V 18.4 ÷ 20.8V 9.2 ÷ 10.4V 18.4 ÷ 20.8V<br />

___<br />

APPLICATION<br />

• fire protection systems<br />

• emergency light<br />

• UPS<br />

• telecom power systems<br />

• backup power for industrial automation and control<br />

• solar panel systems<br />

• cash register and printers<br />

• mobile and portable devices


ZKS24-4 AC/AC power supplies in IP65 casing<br />

The AC/AC power supplies are dedicated to power speed dome cameras. Two outputs (24Vac or 27Vac) allow for choosing <strong>the</strong> voltage<br />

depending on <strong>the</strong> distance between <strong>the</strong> power <strong>supply</strong> and camera. The power <strong>supply</strong> is enclosed in a plastic casing (ABS) <strong>of</strong> ingress<br />

protection IP65, suitable for fixing to a wall.<br />

CHARACTERISTIC FEATURES<br />

• small dimensions<br />

• IP65 casing<br />

• output voltage 24 and 27Vac<br />

• power 100VA<br />

BASIC PARAMETERS OF THE POWER SUPPLY<br />

Input power<br />

Voltage<br />

Frequency<br />

General<br />

<strong>Power</strong><br />

Output voltage<br />

Output current<br />

Mechanical parameters<br />

Dimensions<br />

Weight<br />

* - both outputs can be loaded simultaneously up to total power <strong>of</strong> 100VA<br />

Battery backup power supplies in wall boxes<br />

The power supplies ZB EL25 and ZB EL50 are designed as wall boxes. They cooperate with a battery bank connected as a buffer. The power<br />

supplies indicate <strong>the</strong> battery mode and low battery. They are outfitted with charging current limitation and protection <strong>of</strong> <strong>the</strong> battery bank<br />

against too deep discharge.<br />

CHARACTERISTIC FEATURES<br />

• light compact construction<br />

• output voltage 12 or 24Vdc<br />

• charging current limitation<br />

• protection <strong>of</strong> <strong>the</strong> battery bank against too deep discharge<br />

• possibility to switch <strong>the</strong> unit on from <strong>the</strong> battery<br />

Input power<br />

Voltage<br />

Frequency<br />

General<br />

Output voltage<br />

Maximal output current<br />

Space for batteries<br />

Mechanical parameters<br />

Dimensions<br />

Weight (without batteries)<br />

ZB EL25-B ZB EL25-D ZB EL50-B ZB EL50-D<br />

184…230…253 Vac<br />

47…63Hz<br />

13.2V 26.4V 13.6V 27.2V<br />

2A 1A<br />

4A 2A<br />

7.2Ah 2 x 5Ah 7.2Ah 2 x 5Ah<br />

157 x 118 x 76 mm<br />

~2.0 kg<br />

ul. Toruńska 8, 44-122 Gliwice, Poland, phone +48 32 23 99 400, fax +48 32 23 99 409 • www.merawex.com.pl<br />

184…230…253 Vac<br />

50Hz<br />

100VA<br />

U1: 24Vac / U2: 27Vac<br />

4A for 24Vac or 3.7A for 27Vac*<br />

157 x 118 x 76 mm<br />

2.0 kg<br />