Report #UCR P5308 South Locker Room Concession Stand<br />

Report<br />

Name<br />

Item/Location<br />

Barrier<br />

(noted feature, item or area does not meet the<br />

new construction criteria detailed below)<br />

Action Priority Target<br />

Date<br />

Estimated<br />

Cost<br />

Interim<br />

Solution<br />

Action<br />

Completion<br />

Date<br />

UCR P5308 1-Doors: North Side<br />

South Entrance to the South<br />

Locker Locker Rooms.<br />

Room &<br />

Concession<br />

Stand<br />

The international symbol of accessibility is<br />

posted at all primary entrances.<br />

Post a sign/decal displaying<br />

the "International Symbol of<br />

Accessibility" at the primary<br />

entrance.<br />

1 $24.51<br />

UCR P5308 3-Floors and Levels:<br />

South Ground Level at the<br />

Locker South Locker Rooms.<br />

Room & [Five carpets / mats.]<br />

Concession<br />

Stand<br />

Carpets or carpet tiles are securely attached<br />

and do not exceed 1/2" in height. Carpet's<br />

exposed edges are fastened to floor surfaces<br />

and have trim along entire length.<br />

Secure loose doormat. 1 $1,225.03<br />

UCR P5308 4-Signage: Ground<br />

South Level at the South<br />

Locker Locker Rooms. [No<br />

Room & signage.]<br />

Concession<br />

Stand<br />

Permanent I.D. signs, when provided, are<br />

installed on the wall adjacent to the latch side of<br />

the door NOTE: At double leaf doors, and when<br />

there is no room on the latch side, signs shall<br />

be placed on the nearest adjacent wall,<br />

preferably on the right.<br />

Install permanent ID sign to<br />

latch side of door.<br />

1 $551.26<br />

UCR P5308 5-Visual/Audible Alarms:<br />

South Ground Level at the<br />

Locker South Locker Rooms.<br />

Room & [Three rooms without<br />

Concession fire alarms.]<br />

Stand<br />

The alarm is integrated into the building or<br />

facility alarm system.<br />

Review the entire alarm<br />

system.<br />

1 $7,115.62<br />

UCR P5308 9-Identification Symbols,<br />

South Restrooms: Men's<br />

Locker Restroom Adjacent to<br />

Room & the Gym Door at the<br />

Concession South Locker Rooms.<br />

Stand<br />

Door mounted signage: Men's - Equilateral<br />

triangle with 12" sides, 1/4" thick with the vertex<br />

pointing up. The triangle symbol contrasts with<br />

the door, light on dark background or dark on<br />

light background. Wall mounted signage:<br />

Symbol of accessibility is mounted on wall sign<br />

adjacent to latch side of door [ADAAG 703.6.1 &<br />

CBC 1117B.5.5 Item 4 Pictograms shall have a<br />

field height of 6" ADAAG 703.6.1 Characters<br />

and Braille shall not be located in the pictogram<br />

field].<br />

Install door-mounted sign on<br />

single door. Install wallmounted<br />

sign at single<br />

entrance.<br />

3 $367.51<br />