FIELD PROGRAMMING OPTIONS<br />
AUTOPROGRAM<br />
Autoprogram is a timesaving feature of the AFP-400. It is<br />
AUTOPROGRAM PLEASE WAIT<br />
a special software routine that allows the AFP-400 to “learn”<br />
what devices are physically connected and automatically<br />
load them in the program with default values for all parameters.<br />
Requiring less than 30 seconds to run, this routine<br />
allows the user to have almost immediate fire protection in<br />
L1:80 DETS, 15 MODS L2:93 DETS, 35 MODS<br />
a new installation, even if only a portion of the detectors<br />
PANEL OUTPUTS:24 BELLS: 04<br />
are installed. The routine will find all intelligent detectors<br />
and modules, and present them to the installer for edit of<br />
the default option selections, if desired. If a device is found that already exists in memory, autoprogram skips over that device<br />
(only new devices or missing devices are presented to the installer). Often the installer will perform autoprogram as a first step<br />
in a new installation, then upload the program into VeriFire to add all custom labels and other information, then download from<br />
VeriFire to the AFP-400.<br />
KEYPAD PROGRAM EDIT<br />
The AFP-400, like all NOTIFIER intelligent panels, has the<br />
exclusive feature of full program creation and edit capability<br />
from the front panel keypad, while continuing to provide<br />
fire protection. The architecture of the AFP-400<br />
software is such that each point entry carries its own program,<br />
including control-by-event links to other points. This<br />
allows the program to be entered with independent perpoint<br />
segments, while the AFP-400 simultaneously monitors<br />
other (already installed) points for alarm conditions.<br />
ENTER PROG OR STAT PASSWORD, THEN<br />
ENTER (ESCAPE TO ABORT) *****<br />
0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE<br />
5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG<br />
In addition to avoiding system shutdown, program edit from the panel keypad has the advantage of not requiring an on-site PC.<br />
This can save significant installation time for minor program changes. The AFP-400 site-specific program is password<br />
protected, and all information is stored in non-volatile memory. Menu “trees” are provided to lead the trained installer through<br />
the program steps without the necessity to refer to the programming manual.<br />
VeriFire<br />
VeriFire is an off-line programing and test utility that can<br />
greatly reduce installation programming time, and increase<br />
confidence in the site-specific software. It is Windows®<br />
based and provides technologically advanced capabilities<br />
to aid the installer. The installer may create the<br />
entire program for the AFP-400 in the comfort of the office,<br />
test it, store a backup file, then bring it to the site and<br />
download from a laptop into the panel.<br />
The program includes error checks for common programming<br />
mistakes, such as an input point that does not activate<br />
any outputs, or an output point that is not linked to<br />
any inputs. It also includes a simulation routine that will<br />
list all of the output points that are activated by a particular<br />
input point (alternatively, it will list all the input points<br />
that are linked to a particular output). Although this does<br />
not eliminate on-site testing, it greatly increases confidence<br />
in the final installation. For example, a 200-input<br />
and 100-output point system, without using VeriFire, could<br />
require 20,000 test observations to verify all possible I/O<br />
links.<br />
VeriFire includes a compare routine, pictured at right,<br />
that can also greatly help the installer. When a new<br />
program is created, it may be compared with a previous<br />
version and differences are highlighted. If the program is<br />
modified from the panel keypad, it may be uploaded into<br />
VeriFire, and compared with the previous version stored<br />
on disk. The identification of program differences greatly<br />
helps the installer in testing the installation. NFPA 72<br />
requires that reacceptance test of a fire alarm system be<br />
performed on 100% of all points that are “known” to be<br />
modified. VeriFire allows the installer to determine the<br />
exact points that are changed.<br />
Page 6 of 10 — <strong>DN</strong>-<strong>5262CH</strong>