FIELD PROGRAMMING OPTIONS<br />

AUTOPROGRAM<br />

Autoprogram is a timesaving feature of the AFP-400. It is<br />

AUTOPROGRAM PLEASE WAIT<br />

a special software routine that allows the AFP-400 to “learn”<br />

what devices are physically connected and automatically<br />

load them in the program with default values for all parameters.<br />

Requiring less than 30 seconds to run, this routine<br />

allows the user to have almost immediate fire protection in<br />

L1:80 DETS, 15 MODS L2:93 DETS, 35 MODS<br />

a new installation, even if only a portion of the detectors<br />

PANEL OUTPUTS:24 BELLS: 04<br />

are installed. The routine will find all intelligent detectors<br />

and modules, and present them to the installer for edit of<br />

the default option selections, if desired. If a device is found that already exists in memory, autoprogram skips over that device<br />

(only new devices or missing devices are presented to the installer). Often the installer will perform autoprogram as a first step<br />

in a new installation, then upload the program into VeriFire to add all custom labels and other information, then download from<br />

VeriFire to the AFP-400.<br />

KEYPAD PROGRAM EDIT<br />

The AFP-400, like all NOTIFIER intelligent panels, has the<br />

exclusive feature of full program creation and edit capability<br />

from the front panel keypad, while continuing to provide<br />

fire protection. The architecture of the AFP-400<br />

software is such that each point entry carries its own program,<br />

including control-by-event links to other points. This<br />

allows the program to be entered with independent perpoint<br />

segments, while the AFP-400 simultaneously monitors<br />

other (already installed) points for alarm conditions.<br />

ENTER PROG OR STAT PASSWORD, THEN<br />

ENTER (ESCAPE TO ABORT) *****<br />

0=CLR 1=AUTO 2=POINT 3=PASSWD 4=MESSAGE<br />

5=ZONES 6=SPL FUNCT 7=SYSTEM 8=CHECK PRG<br />

In addition to avoiding system shutdown, program edit from the panel keypad has the advantage of not requiring an on-site PC.<br />

This can save significant installation time for minor program changes. The AFP-400 site-specific program is password<br />

protected, and all information is stored in non-volatile memory. Menu “trees” are provided to lead the trained installer through<br />

the program steps without the necessity to refer to the programming manual.<br />

VeriFire<br />

VeriFire is an off-line programing and test utility that can<br />

greatly reduce installation programming time, and increase<br />

confidence in the site-specific software. It is Windows®<br />

based and provides technologically advanced capabilities<br />

to aid the installer. The installer may create the<br />

entire program for the AFP-400 in the comfort of the office,<br />

test it, store a backup file, then bring it to the site and<br />

download from a laptop into the panel.<br />

The program includes error checks for common programming<br />

mistakes, such as an input point that does not activate<br />

any outputs, or an output point that is not linked to<br />

any inputs. It also includes a simulation routine that will<br />

list all of the output points that are activated by a particular<br />

input point (alternatively, it will list all the input points<br />

that are linked to a particular output). Although this does<br />

not eliminate on-site testing, it greatly increases confidence<br />

in the final installation. For example, a 200-input<br />

and 100-output point system, without using VeriFire, could<br />

require 20,000 test observations to verify all possible I/O<br />

links.<br />

VeriFire includes a compare routine, pictured at right,<br />

that can also greatly help the installer. When a new<br />

program is created, it may be compared with a previous<br />

version and differences are highlighted. If the program is<br />

modified from the panel keypad, it may be uploaded into<br />

VeriFire, and compared with the previous version stored<br />

on disk. The identification of program differences greatly<br />

helps the installer in testing the installation. NFPA 72<br />

requires that reacceptance test of a fire alarm system be<br />

performed on 100% of all points that are “known” to be<br />

modified. VeriFire allows the installer to determine the<br />

exact points that are changed.<br />