Technical data<br />

Technical data<br />

Type <strong>A145</strong> A185 A210 A260 <strong>A300</strong><br />

NEMA ratings<br />

NEMA size 4 — — 5 —<br />

NEMA cont. amp rating (thermal) 135 — — 270 —<br />

NEMA max. HP rating (3PH) 200V 40 — — 75 —<br />

230V 50 — — 100 —<br />

460V/575V 100 — — 200 —<br />

UL / CSA data<br />

Continuous ampere rating A 230 250 300 350 400<br />

Motor rating 3-phase 208V HP 40 50 60 75 100<br />

240V HP 50 60 75 100 100<br />

460/480V HP 100 125 150 200 250<br />

575/600V HP 125 150 200 250 300<br />

Insulation characteristics<br />

Rated insulation voltage U i<br />

according to IEC 947-4-1 and VDE 0110 (Gr. C) V 1000<br />

according to UL/CSA V 600<br />

Rated impulse withstand voltage U imp.<br />

8 kV<br />

Main pole utilization characteristics<br />

Rated operational voltage U e V 1000<br />

Conventional free-air thermal current I th<br />

acc. to IEC 947-4-1, open <strong>contactors</strong> q ≤ 40°C A 250 275 350 400 450<br />

with conductor cross-sectional area mm2 120 150 185 240 300<br />

Rated operational current I e /AC-1 for air temperature<br />

close to contactor<br />

q ≤ 40°C A 250 275 350 400 450<br />

q ≤ 55°C A 230 250 300 350 400<br />

q ≤ 70°C A 180 180 240 290 325<br />

with conductor cross-sectional area mm2 120 150 185 240 300<br />

M<br />

3<br />

{<br />

Utilization category AC-3 for air temperature<br />

close to contactor max. 55°C<br />

Rated operational current I e /AC-3<br />

220 – 230 – 240 V A 145 185 210 260 305<br />

3-phase motors 380 – 400 V A 145 185 210 260 305<br />

415 V A 145 185 210 260 300<br />

440 V A 145 185 210 240 280<br />

500 V A 145 170 210 240 280<br />

690 V A 120 170 210 220 280<br />

Rated operational power AC-3<br />

220 – 230 – 240 V kW 45 55 59 80 90<br />

1500 rpm – 50Hz 380 – 400 V kW 75 90 110 140 160<br />

1800rpm – 60Hz 415 V kW 75 90 110 140 160<br />

3-phase motors M<br />

440 V kW 75 90 110 140 160<br />

3<br />

500 V kW 90 110 132 180 200<br />

690 V kW 110 132 160 200 250<br />

Max. mechanical switching frequency cycles/h 3600 3600 3600 3600 3600<br />

Max. electrical switching for AC-1 cycles/h 300 300 300 300 300<br />

frequency for AC-3 cycles/h 300 300 300 300 300<br />

for AC-4 cycles/h 150 150 150 150 150<br />

Rated making capacity AC-3<br />

12 x I e AC-3<br />

Rated breaking capacity AC-3<br />

8 x I e AC-3<br />

Short-circuit protection for <strong>contactors</strong><br />

without thermal O/L relays – Motor protection excluded<br />

U e ≤ 500 V a.c. – gG (gl) type fuses A 315 355 400 500 500<br />

Rated short-time withstand current I cw 1 s A 1800 2000 2500 3500 3500<br />

at 40°C ambient temp., in free air, 10 s A 1200 1500 1700 2400 2400<br />

from a cold state 30 s A 800 1000 1200 1500 1500<br />

1 min A 600 800 1000 1100 1100<br />

15 min A 280 320 400 500 500<br />

Heat dissipation per pole I e /AC-1 W 13 16 18 25 32<br />

I e /AC-3 W 5 8 9 14 18<br />

Maximum short circuit rating, UL/CSA<br />

MCP Amps/kA @ 480V 400 / 85 400 / 85 800 / 85 800 / 85 800 / 85<br />

MCP Amps/kA @ 600V 400 / 35 400 / 35 800 / 35 800 / 35 800 / 35<br />

Fuse Amps/kA @ 600V 400J / 200 400J / 200 600J / 200 600J / 200 600J / 200<br />

Table of contents: pg 2 Alphanumeric: pg 3 Selection: pg 4 Accessories: pgs 5 – 7 Tech data: pgs 8 – 9 Dimensions: pgs 10 – 13<br />