Technical data<br />
Technical data<br />
Type <strong>A145</strong> A185 A210 A260 <strong>A300</strong><br />
NEMA ratings<br />
NEMA size 4 — — 5 —<br />
NEMA cont. amp rating (thermal) 135 — — 270 —<br />
NEMA max. HP rating (3PH) 200V 40 — — 75 —<br />
230V 50 — — 100 —<br />
460V/575V 100 — — 200 —<br />
UL / CSA data<br />
Continuous ampere rating A 230 250 300 350 400<br />
Motor rating 3-phase 208V HP 40 50 60 75 100<br />
240V HP 50 60 75 100 100<br />
460/480V HP 100 125 150 200 250<br />
575/600V HP 125 150 200 250 300<br />
Insulation characteristics<br />
Rated insulation voltage U i<br />
according to IEC 947-4-1 and VDE 0110 (Gr. C) V 1000<br />
according to UL/CSA V 600<br />
Rated impulse withstand voltage U imp.<br />
8 kV<br />
Main pole utilization characteristics<br />
Rated operational voltage U e V 1000<br />
Conventional free-air thermal current I th<br />
acc. to IEC 947-4-1, open <strong>contactors</strong> q ≤ 40°C A 250 275 350 400 450<br />
with conductor cross-sectional area mm2 120 150 185 240 300<br />
Rated operational current I e /AC-1 for air temperature<br />
close to contactor<br />
q ≤ 40°C A 250 275 350 400 450<br />
q ≤ 55°C A 230 250 300 350 400<br />
q ≤ 70°C A 180 180 240 290 325<br />
with conductor cross-sectional area mm2 120 150 185 240 300<br />
M<br />
3<br />
{<br />
Utilization category AC-3 for air temperature<br />
close to contactor max. 55°C<br />
Rated operational current I e /AC-3<br />
220 – 230 – 240 V A 145 185 210 260 305<br />
3-phase motors 380 – 400 V A 145 185 210 260 305<br />
415 V A 145 185 210 260 300<br />
440 V A 145 185 210 240 280<br />
500 V A 145 170 210 240 280<br />
690 V A 120 170 210 220 280<br />
Rated operational power AC-3<br />
220 – 230 – 240 V kW 45 55 59 80 90<br />
1500 rpm – 50Hz 380 – 400 V kW 75 90 110 140 160<br />
1800rpm – 60Hz 415 V kW 75 90 110 140 160<br />
3-phase motors M<br />
440 V kW 75 90 110 140 160<br />
3<br />
500 V kW 90 110 132 180 200<br />
690 V kW 110 132 160 200 250<br />
Max. mechanical switching frequency cycles/h 3600 3600 3600 3600 3600<br />
Max. electrical switching for AC-1 cycles/h 300 300 300 300 300<br />
frequency for AC-3 cycles/h 300 300 300 300 300<br />
for AC-4 cycles/h 150 150 150 150 150<br />
Rated making capacity AC-3<br />
12 x I e AC-3<br />
Rated breaking capacity AC-3<br />
8 x I e AC-3<br />
Short-circuit protection for <strong>contactors</strong><br />
without thermal O/L relays – Motor protection excluded<br />
U e ≤ 500 V a.c. – gG (gl) type fuses A 315 355 400 500 500<br />
Rated short-time withstand current I cw 1 s A 1800 2000 2500 3500 3500<br />
at 40°C ambient temp., in free air, 10 s A 1200 1500 1700 2400 2400<br />
from a cold state 30 s A 800 1000 1200 1500 1500<br />
1 min A 600 800 1000 1100 1100<br />
15 min A 280 320 400 500 500<br />
Heat dissipation per pole I e /AC-1 W 13 16 18 25 32<br />
I e /AC-3 W 5 8 9 14 18<br />
Maximum short circuit rating, UL/CSA<br />
MCP Amps/kA @ 480V 400 / 85 400 / 85 800 / 85 800 / 85 800 / 85<br />
MCP Amps/kA @ 600V 400 / 35 400 / 35 800 / 35 800 / 35 800 / 35<br />
Fuse Amps/kA @ 600V 400J / 200 400J / 200 600J / 200 600J / 200 600J / 200<br />
Table of contents: pg 2 Alphanumeric: pg 3 Selection: pg 4 Accessories: pgs 5 – 7 Tech data: pgs 8 – 9 Dimensions: pgs 10 – 13<br />
AC 1035 — 10/1999<br />
8 <strong>ABB</strong> <strong>Control</strong> <strong>Inc</strong>.