SD-821<br />
Issue: 5.1<br />
Date Of Issue: 25/05/2012<br />
© 2012 <strong>Sontay</strong> Limited. All rights reserved.<br />
Installation<br />
Connections<br />
1. The SD-821 should only be installed by a competent,<br />
suitably trained technician, experienced in installation<br />
with hazardous voltages.<br />
(>50Vac & 75Vdc & 1500Vdc)<br />
2. Ensure that all power is disconnected before carrying out<br />
any work on the SD-821.<br />
1 2 3 4 5 6<br />
COM NC COM NC +IN GND<br />
3. If the sensor is mounted outside, it is recommended<br />
that the unit be mounted with the cable entry at the<br />
bottom. If the cable is fed from above then into the<br />
cable gland at the bottom, it is recommended that a rain<br />
loop be placed in the cable before entry into the sensor.<br />
RELAY<br />
OUT<br />
FAULT<br />
RELAY<br />
OUT<br />
SMOKE DET.<br />
SUPPLY<br />
IN<br />
24Vac/dc<br />
TEST<br />
4. Drill a 22mm diameter hole, make sure to align the holes<br />
in the probe so that they point into the air flow, not at<br />
right angles to it. Drill two holes at 85mm centres and fix<br />
the IP65 housing to the duct with appropriate screws.<br />
Terminals;<br />
Test & Reset<br />
button<br />
LED<br />
5. Remove the front cover by twisting the lid and<br />
separating from the main body.<br />
6. Feed the cable through the waterproof gland and<br />
terminate the cores at the terminal block. Leaving some<br />
slack inside the unit, tighten the cable gland onto the<br />
cable to ensure water tightness.<br />
7. Maximum cable is 2.5mm², care must be taken not to<br />
over tighten terminals.<br />
1 Fault Output Common<br />
2 Fault Output Normally Closed<br />
3 <strong>Smoke</strong> Detection Output Common<br />
4 <strong>Smoke</strong> Detection Output Normally Closed<br />
5 Supply +24Vac/dc<br />
6 Supply 0V<br />
Manual Reset Button<br />
8. Ensure the supply voltage is within the specified<br />
tolerances.<br />
9. Replace the lid tightly.<br />
Self-Test<br />
The output of the SD-821 can be manually overridden, to<br />
check integrity of the field wiring.<br />
Manual rest button<br />
Press the PCB mounted button for no more than 4 seconds,<br />
otherwise it change the reset mode function. In test mode<br />
both relay outputs will open, the external led will be yellow<br />
and the internal LED red.<br />
Failure Mode<br />
The external LED will flash red if the detector fails.<br />
UK Sales Tel: 0845 345 7253 International Tel: +44 1732 861225<br />
Page 3 of 3<br />
For the latest information and product updates, register at www.sontay.com<br />
Whilst every effort has been made to ensure the accuracy of this specification, <strong>Sontay</strong> cannot accept responsibility for damage, injury, loss or<br />
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.