Physical & electrical location.<br />
Location, Location, Location.<br />
It’s a familiar line but very true.<br />
Getting the location of an SPD<br />
right is paramount to success.<br />
It should be located as close<br />
as possible to Main Switch or<br />
metering point – within Main<br />
SWB if possible. The earthing<br />
point for the SPD (for Main<br />
SWBs) must be located within<br />
a short distance. The main<br />
earthing point is where you<br />
want the excess energy to end<br />
up being safely dissipated.<br />
Safety disconnectors.<br />
It is preferred to use HRC<br />
Gg/Gl fuses, not CBs. HRC<br />
fuses perform better than<br />
CB’s which are not designed<br />
for surge waveforms and fast<br />
rising transients. For medium<br />
& high-current services<br />
<br />
fuse as recommended by the<br />
manufacturer. For low-current<br />
services (