CHECKLIST<br />

EXAMPLES OF REQUIRED PLANS<br />

THREE COMPLETE SETS OF PLANS ARE<br />

REQUIRED INDICATING:<br />

Authorization from building owner/<br />

property manager for proposed work &<br />

intended use.<br />

Overall Building Plan, including:<br />

• Overall building area with dimensions<br />

• Number <strong>of</strong> <strong>storey</strong>s<br />

• Year <strong>of</strong> construction<br />

• High rise measure (if applicable)<br />

• Adjacent <strong>tenant</strong>s<br />

• Previous <strong>tenant</strong><br />

• Building fire safety systems (sprinklers,<br />

standpipe, fire alarm system, emergency<br />

lighting, exit signs)<br />

• Type <strong>of</strong> construction (concrete/steel/<br />

wood, etc.)<br />

Scale 1:100<br />

3/4 hour<br />

fire rating<br />

<br />

<br />

<br />

Tenant Space Floor Plan, Including:<br />

• Area <strong>of</strong> rental space (metric or imperial)<br />

• Scale and dimensions (metric or imperial)<br />

• Existing walls (include types <strong>of</strong> materials)<br />

• Walls to be constructed (include<br />

materials)<br />

• Door sizes and fire ratings<br />

• New ceiling (if applicable include<br />

acceptable materials testing agency<br />

assembly number)<br />

• Windows with glazing (include type and<br />

sizes)<br />

Additional Information<br />

• Structural drawings<br />

• Electrical drawings<br />

• Mechanical drawings<br />

SUBJECT OF ACCEPTANCE:<br />

Tenant:<br />

Previous Use:<br />

Adjacent Uses:<br />

Specifications:<br />

Unit ‘A’ - General Insurance Office<br />

Lawyers’ Office<br />

Unit ‘B’ - Lawyers’ Office<br />

Unit ‘G’ - Engineering Office<br />

No sprinkler system<br />

Fire alarm system<br />

Building Area - 1260 m 2 (13,563 sq. ft.)<br />

4 <strong>storey</strong>s - pre-cast concrete structure<br />

Constructed in 1979<br />

Overall Building Floor Plan<br />

Scale 1:200<br />

North<br />

20 minute labelled door<br />

and frame with listed<br />

UNIT ‘A’ - 144 m 2 (1,550 sq. ft.)<br />

hardware<br />

GENERAL NOTES:<br />

1. Interior partition walls constructed <strong>of</strong> 12.7 mm (1/2 in.) drywall both sides with 38<br />

x 89 mm (2 x 4 in.) steel studs @ 400 mm (16 in.) o.c.<br />

2. Demising walls and corridor walls constructed <strong>of</strong> 15.9 mm (5/8 in.) U.L. drywall<br />

each side to underside <strong>of</strong> ro<strong>of</strong> deck with 38 x 89 mm (2 x 4 in.) steel studs @ 400<br />

mm<br />

(16 in.) o.c.<br />

3. All <strong>of</strong>fice doors are 813 x 2032 mm (32 x 80 in.) ; corridor doors are 914 x 2134 mm<br />

(36 x 84 in.) with a twenty (20) minute fire labelled assembly.<br />

4. Walls to be constructed.<br />

5. Existing walls to remain.<br />

6. Walls to be removed.<br />

ADDITIONAL INFORMATION:<br />

1. The flame spread ratings <strong>of</strong> interior wall and ceiling finishes including glazing and<br />

skylights shall not exceed 150.<br />

2. Exit doors shall be openable from the inside without requiring keys, special devices,<br />

or specialized knowledge <strong>of</strong> the door opening mechanism.<br />