Question 27<br />

State the maximum value of permitted earth<br />

electrode resistance for a TT system when<br />

protection is afforded by a 500mA r.c.d.<br />

GN3 Page 50 2.3 (Earth electrode for RCD’s)<br />

Table 2.3 Normal 100 Special locations 50<br />

By calculation 50V/0.5A = 100 Dry<br />

25V/0.5A = 50 Special Loc