Low Voltage Products - VAE ProSys sro
Low Voltage Products - VAE ProSys sro
Low Voltage Products - VAE ProSys sro
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Motorized change-over switches<br />
Technical data<br />
Data for motorized change-over switches OEM according to IEC 60947-3<br />
Switch size<br />
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<br />
Rated insulation voltage and rated<br />
operational voltage AC20/DC20 Pollution degree 3 V 1000 1000 1000<br />
Dielectric strength 50 Hz 1min. kV 8 8 8<br />
Rated impulse withstand voltage kV 8 8 8<br />
Rated thermal current and rated<br />
operational current AC20/DC20 / ambient 40°C In open air A 1000 1250 1600<br />
/ ambient 40°C In enclosure A 1000 1250 1600<br />
/ ambient 60°C In enclosure A 900 1000 1250<br />
..with minimum conductor cross section Cu mm 2 2x 2x 2x<br />
(60x5) (80x5) (100x5)<br />
Rated operational current, AC-21A up to 690 V A 1000 1250 1600<br />
1000 V A 1000 1000 1000<br />
Rated operational current, AC-22A up to 500 V A 1000 1250 1600<br />
Rated operational current, AC-23A up to 415 V A 800 800 800<br />
440 V A 800 800 800<br />
500 V A 800 800 800<br />
Rated operational power, The kW-ratings are 220-240 V kW 250 250 250<br />
AC-23A accurate for 3-phase 400-415 V kW 400 400 400<br />
1500 R.P.M. standard 440 V kW 400 400 400<br />
asynchronous motors. 500 V kW 450 450 450<br />
Rated conditional short-circuit I p (r.m.s.) : 50 kA, ≤ 690 V î c (peak) kA 105 105 105<br />
current I p (r.m.s.) and<br />
corresponding max. allowed<br />
cut-off current î c (peak) 1)<br />
Rated short-time withstand current I cw (r.m.s.) 690V, 1s kA 50 2) 50 2) 50 2)<br />
Rated short-circuit making capacity I cm (peak) 690V/500V kA 105 105 105<br />
Mechanical endurance Number of operating cycles 3) Cycles 3 000 3 000 3 000<br />
Mechanical endurance / switch Number of operations Oper. 6000 6000 6000<br />
Terminal bolt size Metric thread diameter x length mm 12x60 12x60 12x60<br />
Terminal tightening torque Counter torque required Nm 50...75 50...75 50...75<br />
Operating torque 3-pole switches Nm 25 25 25<br />
A<br />
OEM<br />
1000<br />
OEM<br />
1250<br />
OEM<br />
1600<br />
Data according to IEC 60947-6-1<br />
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .<br />
Rated operational current, AC-31B up to 415 V A 1000 1250 1600<br />
Rated operational current, AC-33B up to 415 V A 800 800 800<br />
Rated operational current, AC-31A up to 415 V A 1000 1250 1600<br />
Rated operational current, AC-33A up to 415 V A 450 450 450<br />
1)<br />
The cut-off current î c refers to values listed by fuse manufacturers (single phase test acc. to IEC60269).<br />
2)<br />
Maximum distance between busbar support and switch terminal 70 mm.<br />
3)<br />
Operating cycle: O - I - O - II - O<br />
10<br />
1SCC303003C0201