12<br />
Pump Panels<br />
Irrigation<br />
Product Family Overview<br />
Irrigation Pump Panel<br />
<strong>Catalog</strong> Number Selection<br />
Table 17. Irrigation Pump Panel <strong>Catalog</strong> Number Selection<br />
Design<br />
P = Irrigation<br />
Class<br />
54 = Type 3R Pump Panel with Disconnect<br />
55 = Type 3R Pump Panel with HMCP<br />
12 = Size 1/3R<br />
22 = Size 2/3R<br />
32 = Size 3/3R<br />
E C<br />
NEMA Size / Enclosure<br />
Product Description<br />
Cutler-Hammer ® Irrigation Pump<br />
Controllers, from Eaton’s electrical<br />
business, are combination starters<br />
designed to meet the requirements<br />
of the agricultural industry. The<br />
enclosure is UL Type 3R rated to<br />
provide weathertight protection and<br />
is available in two sizes. Irrigation<br />
application specific accessories and<br />
modifications are available to fit the<br />
customer’s requirements.<br />
The Irrigation Pump Panels use Freedom<br />
Series Motor Starting Technology<br />
to control motors up to 100 hp @ 460V.<br />
These controllers have two styles of<br />
overload protection available, interchangeable<br />
heater and solid-state<br />
overload (SSOL).<br />
P 5 4 1 2 B A B -<br />
42 = Size 4/3R<br />
52 = Size 5/3R<br />
62 = Size 6/3R<br />
Voltage<br />
A = 120V/60 or 110/50<br />
B = 240V/60 or 220/50<br />
C = 460V/60 or 440/50<br />
Cover Control<br />
A = None<br />
June 2006<br />
■ The interchangeable heater overload<br />
(C306) utilizes individual heater<br />
packs to allow customers the ability<br />
to use various heater styles.<br />
■ The solid-state overload relay provides<br />
enhanced protection and<br />
adjustment ranges as compared to<br />
bimetallic overload relays. Trip Class<br />
10 and 20 are available, along with a<br />
very wide trip current range to make<br />
setup very easy.<br />
Standards and Certifications<br />
■ UL Listed<br />
■ cUL Listed (indicates appropriate<br />
CSA Standard investigation)<br />
■ ABS Type Approval<br />
Modification Code/<br />
Relay Code<br />
Disconnect Fuse Clip Ratings<br />
A = None<br />
H = 200A/250V R<br />
B = 30A/250V R J = 200A/600V R<br />
C = 30A/600V R K = 400A/250V R<br />
D = 60A/250V R L = 400A/600V R<br />
E = 60A/600V R M = 600A/250V R<br />
F = 100A/250V R<br />
G = 100A/600V R<br />
N = 600A/600V R<br />
Breaker Ratings<br />
B = 3 Amp G = 100 Amp<br />
C = 7 Amp H = 150 Amp<br />
D = 15 Amp N = 175 Amp<br />
E = 30 Amp Q =<br />
F = 50 Amp<br />
� Thermal Magnetic Breakers.<br />
�<br />
225 Amp �<br />
For more information visit: www.Eaton<strong>Electric</strong>al.com CA05804001E
June 2006<br />
Product Selection<br />
Pump Panels<br />
Irrigation<br />
Pump Panels with Interchangeable Heater Overload<br />
Standard ECP54 controllers have a<br />
HAND/OFF/AUTO selector switch and<br />
START pushbutton mounted on the<br />
enclosure and are wired as illustrated<br />
in Figure 7.<br />
Table 18. Class ECP54 — Freedom Fusible Irrigation Pump Panels with Interchangeable Heater<br />
Overload<br />
Motor<br />
Voltage �<br />
230<br />
460<br />
—<br />
230<br />
460<br />
—<br />
230<br />
460<br />
—<br />
Starters do not include heater packs. Select 1 carton of 3 heater packs.<br />
Heater pack selection, <strong>Page</strong> 72.<br />
� Dual element fuse ratings.<br />
� Class R fuse clips.<br />
For Other Volts and Hertz Applications<br />
For other than listed volts and hertz,<br />
select required controller by <strong>Catalog</strong><br />
Number and replace the magnet coil<br />
alpha designation, 8th digit in <strong>Catalog</strong><br />
Number with proper Code Suffix from<br />
Table 19.<br />
Fuse Clips<br />
Max. hp<br />
50/60 Hz<br />
7-1/2<br />
10<br />
—<br />
15<br />
25<br />
—<br />
NEMA<br />
Size<br />
1 30<br />
30<br />
Not Installed<br />
2 60<br />
60<br />
Not Installed<br />
Table 20. C351 — Fuse Clip Selection — 3-Pole (3 Fuses)<br />
NEMA<br />
Size<br />
30<br />
50<br />
—<br />
Motor<br />
Voltage<br />
1 200/230<br />
460 – 575<br />
2 200<br />
230<br />
460 – 575<br />
3 100<br />
100<br />
Not Installed<br />
Fuse Clip Rating � Standard Width<br />
Amperes Volts <strong>Catalog</strong><br />
Number<br />
250<br />
600<br />
Not Installed<br />
250<br />
600<br />
Not Installed<br />
250<br />
600<br />
Not Installed<br />
ECP5412BAB<br />
ECP5412CAC<br />
ECP5412AAA<br />
ECP5422BAD<br />
ECP5422CAE<br />
ECP5422AAA<br />
ECP5432BAF<br />
ECP5432CAG<br />
ECP5432AAA<br />
Example: For 600V 60 Hz coil, change<br />
ECP5412BAB to ECP5412DAB<br />
Table 19. Coil Voltage<br />
Coil Volts and Hertz Suffix Code<br />
120/60 or 110/50<br />
240/60 or 220/50<br />
480/60 or 440/50<br />
600/60 or 550/50<br />
208/60<br />
Fuse Clip Rating Fuse Clip Kit for Field Installation in<br />
Non-fusible Starter<br />
Amperes Volts For Non-rejection<br />
Type Fuses<br />
<strong>Catalog</strong><br />
Number<br />
30<br />
30<br />
60<br />
60<br />
60<br />
250<br />
600<br />
250<br />
250<br />
600<br />
C351KC21<br />
C351KD22-61<br />
C351KD22-61<br />
C351KD22-61<br />
C351KD62<br />
3 200<br />
100 250 C351KE23-63<br />
C351KE23-63<br />
230<br />
100 250 C351KE23-63<br />
460 – 575 100 600 C351KE23-63<br />
� Fuse clip “R” rejection members for use with Class R fuses are supplied loose both in Fuse Clip<br />
Kits and when fuse clips are factory installed.<br />
�<br />
C351KE23-63 �<br />
C351KE23-63 �<br />
CA05804001E For more information visit: www.Eaton<strong>Electric</strong>al.com<br />
A<br />
B<br />
C<br />
D<br />
E<br />
For use with “R”<br />
Rejection Type Fuses<br />
<strong>Catalog</strong><br />
Number<br />
C351KC21R<br />
C351KD22-61R<br />
C351KD22-61R<br />
C351KD22-61R<br />
C351KD62R<br />
Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <strong>Page</strong> 4<br />
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . <strong>Page</strong> 16<br />
Modifications Codes . . . . . . . . . . . . . . . . . . <strong>Page</strong> 73<br />
13
14<br />
Pump Panels<br />
Irrigation<br />
Pump Panels with Solid-State Overload<br />
Product Selection<br />
Table 21. Class ECP54 — Freedom Fusible Irrigation Pump Panels with Solid-State Overload<br />
Protection, Manual Reset Button and Class 20 Trip �<br />
Motor<br />
Voltage<br />
Max.<br />
hp<br />
240V 1<br />
3<br />
7-1/2<br />
10<br />
15<br />
480V 1<br />
2<br />
5<br />
10<br />
20<br />
25<br />
NEMA<br />
Size<br />
1<br />
1<br />
1<br />
2<br />
2<br />
Fuse Clip<br />
Amperes<br />
30<br />
30<br />
30<br />
60<br />
60<br />
Volts Trip<br />
Range<br />
250<br />
250<br />
250<br />
250<br />
250<br />
1.6 – 5.0<br />
3.7 – 12<br />
12 – 32<br />
12 – 37<br />
14 – 45<br />
<strong>Catalog</strong><br />
Number<br />
ECP5412BAB-R50/G84<br />
ECP5412BAB-R50/G85<br />
ECP5412BAB-R50/G86<br />
ECP5422BAD-R50/G87<br />
ECP5422BAD-R50/G88<br />
25 3 100 250 26 – 85 ECP5432BAF-R50/G89<br />
1<br />
1<br />
1<br />
1<br />
2<br />
2<br />
30<br />
30<br />
30<br />
30<br />
60<br />
60<br />
600<br />
600<br />
600<br />
600<br />
600<br />
600<br />
1.0 – 2.9<br />
1.6 – 5.0<br />
3.7 – 12<br />
12 – 32<br />
12 – 37<br />
14 – 45<br />
ECP5412CAC-R50/G83<br />
ECP5412CAC-R50/G84<br />
ECP5412CAC-R50/G85<br />
ECP5412CAC-R50/G86<br />
ECP5422CAE-R50/G87<br />
ECP5422CAE-R50/G88<br />
50 3 100 600 26 – 85 ECP5432CAG-R50/G89<br />
� Motor FLA based on NEC table. For Class 10, Automatic Reset and other trip ranges see<br />
Table 24.<br />
Table 22. Class ECP55 — Freedom Breaker Irrigation Pump Panels with Solid-State Overload<br />
Protection, Manual Reset Button and Class 20 Trip �<br />
Motor<br />
Voltage<br />
Max.<br />
hp<br />
240V 1<br />
3<br />
7-1/2<br />
10<br />
15<br />
NEMA<br />
Size<br />
1<br />
1<br />
1<br />
2<br />
2<br />
Breaker<br />
Rating<br />
7<br />
15<br />
30<br />
50<br />
50<br />
Trip<br />
Range<br />
1.6 – 5.0<br />
3.7 – 12<br />
12 – 32<br />
12 – 37<br />
14 – 45<br />
<strong>Catalog</strong><br />
Number<br />
ECP5512BAC-R50/G84<br />
ECP5512BAD-R50/G85<br />
ECP5512BAE-R50/G86<br />
ECP5522BAF-R50/G87<br />
ECP5522BAF-R50/G88<br />
25 3 100 26 – 85 ECP5532BAG-R50/G89<br />
50 4 150 57 – 180 ECP5542BAQ-R50/G92<br />
480V 1 1<br />
3<br />
1.0 – 2.9 ECP5512CAB-R50/G83<br />
3 1<br />
7<br />
1.6 – 5.0 ECP5512CAC-R50/G84<br />
5 1<br />
15<br />
3.7 – 12 ECP5512CAD-R50/G85<br />
10 1<br />
30<br />
12 – 32 ECP5512CAE-R50/G86<br />
10 2<br />
30<br />
12 – 37 ECP5522CAE-R50/G87<br />
25 2<br />
50<br />
14 – 45 ECP5522CAF-R50/G88<br />
50 3 100 26 – 85 ECP5532CAG-R50/G89<br />
100 4 150 57 – 180 ECP5542CAN-R50/G92<br />
� Motor FLA based on NEC table. For Class 10, Automatic Reset and other trip ranges see<br />
Table 24.<br />
Table 23. Class ECP55 — Freedom Breaker Irrigation Pump Panels with Interchangeable Heater<br />
Overload<br />
Motor<br />
Voltage<br />
Max.<br />
hp<br />
240V 1<br />
3<br />
7-1/2<br />
10<br />
15<br />
NEMA<br />
Size<br />
1<br />
1<br />
1<br />
2<br />
2<br />
Breaker<br />
Rating<br />
7<br />
15<br />
30<br />
50<br />
50<br />
<strong>Catalog</strong><br />
Number<br />
ECP5512BAC<br />
ECP5512BAD<br />
ECP5512BAE<br />
ECP5522BAF<br />
ECP5522BAF<br />
25 3 100 ECP5532BAG<br />
50 4 150 ECP5542BAQ<br />
480V 1<br />
1<br />
3<br />
ECP5512CAB<br />
3<br />
1<br />
7<br />
ECP5512CAC<br />
5<br />
1<br />
15<br />
ECP5512CAD<br />
10<br />
1<br />
30<br />
ECP5512CAE<br />
10<br />
2<br />
30<br />
ECP5522CAE<br />
25<br />
2<br />
50<br />
ECP5522CAF<br />
50 3 100 ECP5532CAG<br />
100 4 150 ECP5542CAN<br />
June 2006<br />
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . <strong>Page</strong> 16<br />
Modifications Codes. . . . . . . . . . . . . . . . . . <strong>Page</strong> 73<br />
For more information visit: www.Eaton<strong>Electric</strong>al.com CA05804001E
June 2006<br />
Relays<br />
Table 24. Freedom Solid-State Overload Relays<br />
CEP7<br />
Frame<br />
NEMA<br />
Size<br />
Pump Panels<br />
Irrigation<br />
Pump Panels with Solid-State Overload<br />
Example: R53/G144 = Class 10, 1.6 – 5.0 ampere overload for Size 0 or 1 starters.<br />
Wiring Diagram<br />
Full Load<br />
Current<br />
Adjustment<br />
Range (A)<br />
Figure 7. Typical Wiring Diagram<br />
3-Phase<br />
Manual Reset<br />
Overload<br />
3-Phase<br />
Automatic/Manual<br />
Reset<br />
Class 10 Class 20 Class 10 Class 20<br />
<strong>Catalog</strong> Number Suffix ➟ R52 R50 R53 R51<br />
M32 00 0.1 – 0.32<br />
0.32 – 1.0<br />
1.0 – 2.9<br />
1.6 – 5.0<br />
3.7 – 12<br />
0 & 1 0.1 – 0.32<br />
0.32 – 1.0<br />
1.0 – 2.9<br />
1.6 – 5.0<br />
3.7 – 12<br />
12 – 32<br />
G101<br />
G102<br />
G103<br />
G104<br />
G105<br />
G101<br />
G102<br />
G103<br />
G104<br />
G105<br />
G106<br />
G81<br />
G82<br />
G83<br />
G84<br />
G85<br />
G81<br />
G82<br />
G83<br />
G84<br />
G85<br />
G86<br />
G141<br />
G142<br />
G143<br />
G144<br />
G145<br />
G141<br />
G142<br />
G143<br />
G144<br />
G145<br />
G146<br />
G121<br />
G122<br />
G123<br />
G124<br />
G125<br />
G121<br />
G122<br />
G123<br />
G124<br />
G125<br />
G126<br />
M37 2 12 – 37 G107 G87 G147 G127<br />
M45 14 – 45 G108 G88 G148 G128<br />
M85 3 26 – 85 G109 G89 G149 G129<br />
M110 66 – 110 G110 G90 G150 G130<br />
M180 4 57 – 180 G112 G92 G152 G132<br />
M<br />
OL<br />
L1<br />
L2 L3<br />
Circuit<br />
Breaker or<br />
Motor Circ.<br />
Switch<br />
T1<br />
T2<br />
T3<br />
Motor<br />
Hand<br />
OFF<br />
Auto<br />
Pressure Switch<br />
Start M OL<br />
M<br />
CA05804001E For more information visit: www.Eaton<strong>Electric</strong>al.com<br />
15
16<br />
Pump Panels<br />
Irrigation<br />
Dimensions<br />
Dimensions<br />
Table 25. Minimum Enclosure Box Numbers<br />
Size Top Entry Bottom Entry<br />
1<br />
2<br />
2-1/2<br />
3<br />
3-1/2<br />
4<br />
HMCPE/<br />
BKR<br />
C362 Fused<br />
C362<br />
HMCPE/<br />
BKR<br />
C362 Fused<br />
C362<br />
Box No. Box No. Box No. Box No. Box No. Box No.<br />
8<br />
8<br />
8<br />
8<br />
8<br />
9<br />
SSOL Option<br />
1<br />
2<br />
2-1/2<br />
3<br />
3-1/2<br />
4<br />
8<br />
8<br />
8<br />
8 �<br />
8 �<br />
9<br />
8<br />
8<br />
8<br />
8<br />
8<br />
—<br />
8<br />
8<br />
8<br />
8 �<br />
8 �<br />
—<br />
8<br />
8<br />
8<br />
9<br />
9<br />
—<br />
8<br />
8<br />
8<br />
9<br />
9<br />
—<br />
� Irrigation pump panels with a Generation 2 solid-state overload are<br />
sized in a Box 8. Those with the Generation 1 overload are sized in a<br />
Box 9.<br />
20.02<br />
(508.5)<br />
2.63<br />
(66.8)<br />
25.50<br />
(647.7)<br />
Max.<br />
8.47<br />
(215.1)<br />
Mtg. for (4) 1/4-20 Screws<br />
14.25 (362.0) Max.<br />
9.00<br />
(228.6)<br />
9.00<br />
(228.6)<br />
3.00 3.00<br />
(76.2) (76.2)<br />
4.00<br />
(101.6)<br />
2.63<br />
(66.8)<br />
Figure 8. Box 8, Type 3R — Approximate Dimensions in Inches (mm)<br />
8<br />
8<br />
8<br />
8<br />
8<br />
9<br />
.55<br />
(14.0)<br />
8<br />
8<br />
8<br />
8 �<br />
8 �<br />
9<br />
27.50<br />
(698.5)<br />
3.50<br />
(88.9)<br />
2.04<br />
(51.8)<br />
8<br />
8<br />
8<br />
8<br />
8<br />
—<br />
8<br />
8<br />
8<br />
8 �<br />
8 �<br />
—<br />
8<br />
8<br />
8<br />
9<br />
9<br />
—<br />
8<br />
8<br />
8<br />
9<br />
9<br />
—<br />
Removable Top Cover<br />
Provides Usage of Safety<br />
Switch Hubs per Table Below<br />
29.10<br />
(739.1)<br />
Max.<br />
Plugs for<br />
Optional<br />
Flange<br />
Control<br />
3.50<br />
(88.9)<br />
9.29 (236.0)<br />
to Optional<br />
Cover Controls<br />
Concentric Knockouts for<br />
1-1/4", 1-1/2" & 2" Conduit – (2) Required<br />
Concentric Knockouts for<br />
1/2", 3/4" & 1" Conduit – (2) Required<br />
Conduit Size Cat. No.<br />
3/4" DS075H1<br />
1" DS100H1<br />
1-1/2" DS150H1<br />
2" DS200H1<br />
28.00W x 61.75H x 10.68D<br />
2.76<br />
(70.1)<br />
25.50<br />
(647.7)<br />
Max.<br />
31.14<br />
(791.0)<br />
8.41<br />
(213.6)<br />
3.50<br />
(88.9)<br />
25.50 (647.7) Max.<br />
20.00 (508.0)<br />
20.00<br />
(508.0)<br />
6.00<br />
(152.4)<br />
2.75<br />
(69.9)<br />
3.50<br />
(88.9)<br />
6.14<br />
(156.0)<br />
Mtg. for (4)<br />
1/4-20 Screws<br />
.55<br />
(14.0)<br />
29.10<br />
(739.1)<br />
Max.<br />
27.50<br />
(689.5)<br />
Concentric Knockouts for<br />
1-1/4", 1-1/2" and 2" Conduit –<br />
(2 Required)<br />
Concentric Knockouts<br />
for 1/2", 3/4" Conduit –<br />
(2 Required)<br />
3.50<br />
(88.9)<br />
Plugs for<br />
Optional<br />
Flange<br />
Control<br />
Conduit Size<br />
3/4"<br />
1"<br />
1-1/4"<br />
1-1/2"<br />
2"<br />
June 2006<br />
Removable Top Cover<br />
Provides Usage of<br />
Safety Switch Hubs<br />
per Table Below<br />
3.50<br />
(88.9)<br />
9.31 (236.5)<br />
to Optional<br />
Cover Controls<br />
Cat. No.<br />
DS075H1<br />
DS100H1<br />
DS125H1<br />
DS150H1<br />
DS200H1<br />
8.50W x 32.98H x 6.66D<br />
Figure 9. Box 9, Type 3R — Approximate Dimensions in Inches (mm)<br />
For more information visit: www.Eaton<strong>Electric</strong>al.com CA05804001E
June 2006<br />
Cover Control<br />
Non-reversing<br />
Flange Control Kits<br />
For on-the-job conversion of Type 1, 3R,<br />
4X and 12 enclosed starters. Knockouts<br />
are provided on the Type 1 flange. Type<br />
3R, 4X and 12 have prepunched holes<br />
with removable hole plugs.<br />
Factory Installed Pilot Devices<br />
To order factory installed pilot devices,<br />
change the 9th character of the<br />
<strong>Catalog</strong> Number to the alpha shown in<br />
the table below. Example: to order an<br />
ECN0514CAA with START/STOP<br />
pushbuttons and a red pilot light,<br />
change the A to a C, i.e. ECN0514CCA.<br />
Figure 10. Figure 11.<br />
Standards and Certifications<br />
■ UL Listed<br />
■ cUL Listed (indicates appropriate<br />
CSA Standard investigation)<br />
■ ABS Type Approval<br />
Dimensions<br />
Table 26. Type 1, 3R, 4X, 12 Duplex Pump<br />
Panels Non-combination<br />
NEMA Size Box No. Shipping Wt.<br />
Lbs. (kg)<br />
0 – 2 G 44 (20)<br />
3 – 4 G1 120 (54)<br />
5 – 6 F1E 405 (184)<br />
Table 27. Type 1, 3R, 4X, 12 Duplex Pump<br />
Panels Combination<br />
NEMA Size Box No. Shipping Wt.<br />
Lbs. (kg)<br />
0 – 2 H 75 (34)<br />
3 – 4 H1 180 (82)<br />
5 – 6 F1E 425 (193)<br />
Note: For Box Dimensions, see Enclosed<br />
Control Product Guide.<br />
Pump Panels<br />
Duplex Pump Panels<br />
Product Family Overview<br />
Table 28. Non-reversing Pilot Devices<br />
Description Factory Installed Flange Control Field Installation Kits<br />
Position Non- Combination Non- Combination<br />
9 Alpha combination (NEMA only) combination (NEMA only)<br />
�<br />
�<br />
�<br />
�<br />
See See<br />
See See<br />
Figure 10 Figure 11 Figure 10 Figure 11<br />
<strong>Catalog</strong> <strong>Catalog</strong><br />
Number Number<br />
No Cover Mounted Pilot Devices A<br />
■<br />
■ C400GK0<br />
START/STOP Pushbuttons B<br />
■<br />
■ C400GK1<br />
with Red RUN Pilot Light C<br />
■<br />
■ C400GK12<br />
with Red RUN/Green OFF Lights D<br />
■<br />
■<br />
�<br />
C400GK16 �<br />
—<br />
C400T1<br />
—<br />
—<br />
ON/OFF Pushbuttons<br />
E<br />
—<br />
■ —<br />
C400T2<br />
with Red RUN Pilot Light F<br />
—<br />
■ —<br />
—<br />
with Red RUN/Green OFF Lights G<br />
—<br />
■ —<br />
—<br />
HAND/OFF/AUTO Selector Switch H<br />
■<br />
■ C400GK3<br />
with Red RUN Pilot Light J<br />
■<br />
■ C400GK32<br />
with Red RUN/Green OFF Lights K<br />
■<br />
■<br />
�<br />
C400GK36 �<br />
C400T12<br />
—<br />
—<br />
START Pushbutton<br />
L<br />
—<br />
■ —<br />
ON Pushbutton<br />
M<br />
—<br />
■ —<br />
OFF Pushbutton<br />
N<br />
—<br />
■ —<br />
Red RUN Pilot Light<br />
P<br />
■<br />
■ C400GK42<br />
Green OFF<br />
Q<br />
■<br />
■<br />
Red RUN/Green OFF Pilot Lights R<br />
■<br />
■<br />
�<br />
C400GK41 �<br />
C400GK46 �<br />
C400T3<br />
C400T4<br />
C400T5<br />
C400T9 �<br />
C400T10 �<br />
C400T11 �<br />
START/STOP Selector Switch S<br />
—<br />
■ —<br />
C400T13<br />
with Red RUN Pilot Light T<br />
—<br />
■ —<br />
—<br />
with Red RUN/Green OFF Lights U<br />
—<br />
■ —<br />
—<br />
ON/OFF Selector Switch<br />
V<br />
—<br />
■ —<br />
C400T14<br />
with Red RUN Pilot Light W<br />
—<br />
■ —<br />
—<br />
with Red RUN/Green OFF Lights X<br />
—<br />
■ —<br />
—<br />
� Type 1, NEMA Sizes 00 – 4/IEC Frames A – M Non-combination ONLY.<br />
� Type 1, NEMA Sizes 5 – 9/IEC Frames N – V Non-combination PLUS all Type 3R, 4X, 12<br />
Non-combination PLUS all Combination — NEMA Sizes only.<br />
� Add Code Letter from the table below to <strong>Catalog</strong> Number for voltage — Kits only. Example:<br />
C400T9B.<br />
Rating Code Letter Rating Code Letter Rating Code Letter<br />
120V 60 Hz<br />
208V 60 Hz<br />
CA05804001E For more information visit: www.Eaton<strong>Electric</strong>al.com<br />
A<br />
E<br />
240V 60 Hz<br />
380V 50 Hz<br />
B<br />
L<br />
480V 60 Hz<br />
600V 60 Hz<br />
C<br />
D<br />
17