D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Main technical data<br />
Symbol<br />
Unit<br />
Cubicle type<br />
<strong>SECUB</strong>-2 UR15 <strong>SECUB</strong>-2 UR26<br />
Rated service current I Ne [A] 1500 A 2600 A<br />
Rated voltage UNe [VDC] 900 900<br />
Rated insultation voltage Unm [VDC] 1800 1800<br />
Nominal voltage Un [VDC] 600/750 600/750<br />
Power frequency withstand voltage Ua [kV] 6.9 kV, 50 Hz, 1min.<br />
Rated service current<br />
Main busbar [kA] 2400A 2400A / 4000A*<br />
Rated short-circuit current INss / ÎNss [kA] 12 / 18 100 / 150<br />
Protection degree (doors and walls)<br />
IP30<br />
Protection degree (roof)<br />
IP20 / IP32** / IP42**<br />
Ambient temperature range [VDC] -5 °C ... +40 °C<br />
Typical weights (Without disconnector) [kg] 330 350<br />
Dimensions (WxDxH) [mm] 450x1400x2200<br />
* 4000A: option<br />
** IP32/IP42: option<br />
Designed according to standard specifications EN 501 23 and IEC 61992<br />
Composition<br />
Unique feature:<br />
Key components of the switchgear are designed and manufactured by Sécheron and are fully compatible.<br />
SEPCOS<br />
Protection relay<br />
SWS18.20<br />
Disconnecting Switch<br />
SEPCOS<br />
Touch-screen display<br />
VM10<br />
Isolated amplifier for<br />
Voltage Measurement<br />
UR26.81S<br />
High-speed circuit breaker<br />
MIU10<br />
Isolated amplifier for<br />
Current Measurement