Main technical data<br />

Symbol<br />

Unit<br />

Cubicle type<br />

<strong>SECUB</strong>-2 UR15 <strong>SECUB</strong>-2 UR26<br />

Rated service current I Ne [A] 1500 A 2600 A<br />

Rated voltage UNe [VDC] 900 900<br />

Rated insultation voltage Unm [VDC] 1800 1800<br />

Nominal voltage Un [VDC] 600/750 600/750<br />

Power frequency withstand voltage Ua [kV] 6.9 kV, 50 Hz, 1min.<br />

Rated service current<br />

Main busbar [kA] 2400A 2400A / 4000A*<br />

Rated short-circuit current INss / ÎNss [kA] 12 / 18 100 / 150<br />

Protection degree (doors and walls)<br />

IP30<br />

Protection degree (roof)<br />

IP20 / IP32** / IP42**<br />

Ambient temperature range [VDC] -5 °C ... +40 °C<br />

Typical weights (Without disconnector) [kg] 330 350<br />

Dimensions (WxDxH) [mm] 450x1400x2200<br />

* 4000A: option<br />

** IP32/IP42: option<br />

Designed according to standard specifications EN 501 23 and IEC 61992<br />

Composition<br />

Unique feature:<br />

Key components of the switchgear are designed and manufactured by Sécheron and are fully compatible.<br />

SEPCOS<br />

Protection relay<br />

SWS18.20<br />

Disconnecting Switch<br />

SEPCOS<br />

Touch-screen display<br />

VM10<br />

Isolated amplifier for<br />

Voltage Measurement<br />

UR26.81S<br />

High-speed circuit breaker<br />

MIU10<br />

Isolated amplifier for<br />

Current Measurement