D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Standards<br />
The <strong>SECUB</strong>-2 has been successfully type tested at IPH laboratory in Berlin.<br />
According to standards:<br />
• IEC 61992-2:2006<br />
• EN 50123-2:2003<br />
Approved type test reports available.<br />
Main features related to <strong>SECUB</strong>-2 breaker cubicle<br />
Rated voltage (Une)<br />
Rated insulation voltage<br />
Rated service current (Ine)<br />
Rated making & breaking capacity (Înss/Inss)<br />
Rated track time constant (Tnc)<br />
Duty classes<br />
900VDC<br />
1800VDC<br />
2600A<br />
100/150kA<br />
31.5ms<br />
f, e, d<br />
SG820794BEN_B00-05.13<br />
Sécheron SA<br />
Rue du Pré-Bouvier 25<br />
1217 Meyrin - Geneva<br />
CH-Switzerland<br />
Tel: +41 (0)22 739 41 11<br />
Fax: +41 (0)22 739 48 11<br />
substations@secheron.com<br />
www.secheron.com<br />
This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product,<br />
whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances,<br />
of the product’s maintenance conditions and requirements. Séche ron reserves all rights, especially those arising from our “General Delivery Conditions”.<br />
Copyright© 2007 Sécheron SA