SUBSTATIONS<br />

D.C. <strong>Switchgear</strong> <strong>Range</strong><br />

<strong>Type</strong> <strong>SECUB</strong>-2


A domain of expertise<br />

With a complete range of equipment and a leading expertise<br />

in DC traction power substations, Sécheron SA is a world<br />

leader and major partner for electrification of DC traction<br />

networks. Covering all activities from calculation, network<br />

design and engineering, up to the production of the DC<br />

Systems, Sécheron SA can offer customers and partners<br />

tailor made solutions based on a modular concept and<br />

standard products.<br />

Our equipment is developed on world leading technology<br />

and proven worldwide design and acceptance. In-house<br />

technology covers all key devices applied in the DC Systems<br />

(rectifiers, DC HSCB, Disconnecting Switches, Protection<br />

relays, measuring amplifiers, etc.).<br />

<strong>SECUB</strong>-2: DC switchgear for light rail applications<br />

The <strong>SECUB</strong>-2 cubicle is a compact DC switchgear solution<br />

designed for DC traction substations powering light transportation<br />

systems such as tramways, LRT, trolleybuses, monorails<br />

and LIM.<br />

<strong>SECUB</strong>-2 completes the range of Sécheron DC switchgear<br />

that covers heavy duty transportation systems.<br />

<strong>SECUB</strong>-2 is the improved evolution of the <strong>SECUB</strong> which has<br />

widely been installed in various networks since more than 10<br />

years.<br />

Main features<br />

• Rated current up to 2400 A (main circuit)<br />

• Rated voltage up to 900 Vdc<br />

• Metal enclosed switchgear compartment equipped with high-speed<br />

circuit-breaker<br />

• Bi-directional current interruption<br />

• Rated short-circuit current up to 100 kA (150 kA peak)<br />

• Equipped with a high-performance Protection and Control Relay type<br />

SEPCOS<br />

• Strong, compact and durable cubicle<br />

• Modular construction<br />

• Limited and easy maintenance<br />

• Designed according to EN 50123 & IEC 61992 standards<br />

New features:<br />

• Possibility to integrate a disconnecting switch in the rear compartment<br />

• Access from the front of the cubicle after having fully removed the drawer


Description<br />

The metal enclosed compartmented DC switchgear type <strong>SECUB</strong>-2 integrates three separated compartments for high and low<br />

voltage equipment:<br />

• Low voltage compartment including protection and control devices<br />

• High-speed circuit-breaker compartment<br />

• Rear high voltage busbar compartment including optional disconnecting switch<br />

Protection and control compartment<br />

Accessible from the front of the cubicle, the low voltage compartment includes the protection and control relay SEPCOS, the<br />

low voltage equipment (MCBs, relays etc.).<br />

High speed circuit breaker compartment<br />

The HV compartment includes the high-speed circuit-breaker which is mounted on a withdrawable drawer.<br />

The drawer can easily be drawn in or out of the cubicle and connected or disconnected from buses by means of power finger<br />

connectors.<br />

The HSCB’s auxiliary circuits can be connected or disconnected thanks to a multiple connector.<br />

The unlocking mechanism of the door ensures a trip of the HSCB before opening.<br />

Behind this door, a polycarbonate protecting screen ensures the security of personel and prevent contact with live parts.<br />

With the door open, the drawer can be drawn in or out with a handle located on the drawer frame (linked to a locking system).<br />

When the drawer has been drawn out, it can be easily placed on a trolley (optional) allowing easy maintenance operations and<br />

access inside the cubicle.<br />

The withdrawable circuit breaker drawer has four different positions:<br />

• Service<br />

• Test<br />

• Disconnected<br />

• Removed<br />

It is possible to see the physical<br />

state of the HSCB (opened or<br />

closed) as well as the drawer<br />

position (service or test) trough a<br />

window located on the front door.<br />

A counter showing the number<br />

of HSCB operation is also visible<br />

through this window.<br />

The drawer also contains a measuring shunt. The isolated amplifiers for current (MIU10) and voltage (VM10) measurement as well<br />

as the line test components are mounted on a retractable plate located below the drawer.<br />

With the plate removed, the power cable connection compartment is easily accessible inside the cubicle. This feature makes the<br />

installation against the wall possible.<br />

This compartment is separated from the busbar compartment thanks to isolating shutters.<br />

Rear high voltage busbar compartment<br />

The busbar rear compartment is composed of two main parts:<br />

• Main incoming busbar<br />

• Connection for outgoing cables, copper bars are provided to connect the power cable to the third rail or the catenary<br />

• As an option, an off load disconnecting switch can be mounted to insure the by-pass or line isolating function


Main technical data<br />

Symbol<br />

Unit<br />

Cubicle type<br />

<strong>SECUB</strong>-2 UR15 <strong>SECUB</strong>-2 UR26<br />

Rated service current I Ne [A] 1500 A 2600 A<br />

Rated voltage UNe [VDC] 900 900<br />

Rated insultation voltage Unm [VDC] 1800 1800<br />

Nominal voltage Un [VDC] 600/750 600/750<br />

Power frequency withstand voltage Ua [kV] 6.9 kV, 50 Hz, 1min.<br />

Rated service current<br />

Main busbar [kA] 2400A 2400A / 4000A*<br />

Rated short-circuit current INss / ÎNss [kA] 12 / 18 100 / 150<br />

Protection degree (doors and walls)<br />

IP30<br />

Protection degree (roof)<br />

IP20 / IP32** / IP42**<br />

Ambient temperature range [VDC] -5 °C ... +40 °C<br />

Typical weights (Without disconnector) [kg] 330 350<br />

Dimensions (WxDxH) [mm] 450x1400x2200<br />

* 4000A: option<br />

** IP32/IP42: option<br />

Designed according to standard specifications EN 501 23 and IEC 61992<br />

Composition<br />

Unique feature:<br />

Key components of the switchgear are designed and manufactured by Sécheron and are fully compatible.<br />

SEPCOS<br />

Protection relay<br />

SWS18.20<br />

Disconnecting Switch<br />

SEPCOS<br />

Touch-screen display<br />

VM10<br />

Isolated amplifier for<br />

Voltage Measurement<br />

UR26.81S<br />

High-speed circuit breaker<br />

MIU10<br />

Isolated amplifier for<br />

Current Measurement


Main dimensions<br />

1. Circuit-breaker<br />

450<br />

1400<br />

2. Withdrawable breaker drawer<br />

3. Low-voltage compartment<br />

(protection and control circuits)<br />

4. Main plugs (power circuit)<br />

100<br />

3<br />

1075<br />

325<br />

5. Shunt (current)<br />

6. Current measuring amplifier<br />

7. Voltage measuring amplifier<br />

8<br />

10<br />

8. Busbar compartment<br />

9. Output cable<br />

2200<br />

11<br />

10. Bypass busbar (option)<br />

11. Disconnecting switch (option)<br />

12. Main busbar<br />

1<br />

12<br />

4<br />

1430<br />

2<br />

5<br />

6<br />

7<br />

9<br />

<strong>SECUB</strong>-2 HSCB cubicle: Main applications<br />

Main configurations:<br />

MAIN BUSBAR<br />

MAIN BUSBAR<br />

MAIN BUSBAR<br />

1. Line feeder<br />

E SEPCOS E SEPCOS E SEPCOS<br />

2. Line feeder with isolating switch<br />

Line Test<br />

I ><br />

Line Test<br />

I > I ><br />

I I I<br />

Line Test<br />

3. Line feeder with earthing switch<br />

MIU10<br />

MIU10<br />

MIU10<br />

4. Rectifier breaker<br />

U<br />

VM10<br />

M<br />

U<br />

VM10<br />

U<br />

VM10<br />

5. Line feeder with bypass<br />

1<br />

2 3<br />

MAIN BUSBAR<br />

MAIN BUSBAR<br />

BY-PASS BUSBAR<br />

E<br />

SEPCOS<br />

E<br />

SEPCOS<br />

I ><br />

I ><br />

I<br />

MIU10<br />

Line Test<br />

I<br />

MIU10<br />

M<br />

U<br />

VM10<br />

4<br />

5


SEPCOS control and protection relay<br />

SEPCOS is a protection and control unit that is applied to the outgoing feeder or the<br />

incoming HSCB cubicles in the DC traction substation.<br />

Main features:<br />

• Modular PLC concept, PLC programming, IEC61131 normalized programming.<br />

• Fully approved in railway substation environment EN50255-22.<br />

• High noise immunity thanks to sampling rate at 40 microseconds and<br />

16 bits A-D converter.<br />

Protection functions:<br />

• All typical protection functions (e.g. Function DDL +/-, Imax +/-, etc.).<br />

Control functions:<br />

• HSCB ON / OFF control with electric or magnetic holding.<br />

• Intertripping, automatic reclosing, anti-pumping, line test function.<br />

• External synchronization of the PLC, measurement supervisor control.<br />

Open to all customer network and protocols:<br />

• TCP/IP: MODBUS-TCP<br />

• Specific TCP/IP based power distribution protocols:<br />

- IEC60870-5-104<br />

- DNP3<br />

- IEC61850<br />

• Fieldbus: MODBUS-RTU, Profibus DP<br />

SEPCOS in the low-voltage compartment<br />

The SEPCOS may be controlled and parametrized<br />

through a user friendly 7″ color Touch Screen display<br />

which is located on the front door of the cubicle.<br />

All functions are available through a web server<br />

(S-Web), including visualization of trends.<br />

Products and Services<br />

Sécheron provides complete DC substations systems including:<br />

• Transformer-rectifier group<br />

• DC switchgear including:<br />

- DC HSCB cubicles<br />

- Disconnector cubicles<br />

- Contactor cubicles<br />

• Voltage limiting devices<br />

• Protection and control systems<br />

• Human Machine Interfaces<br />

Sécheron also provides services in order to support customers in network design and installation of our systems:<br />

• DC System Engineering<br />

• Dynamic simulation of complete networks<br />

• Short-circuit, earthing circuit and harmonic calculation<br />

• Supervision of installation and commissioning<br />

• In line and field testing


Full compact lightrail solution<br />

With years of experience in the field of traction rectifiers, today proposes a cubicle which integrates both functions of rectifier and<br />

isolating switch.<br />

This cubicle is normally used combined with the <strong>SECUB</strong>-2.<br />

It is a compact solution for LRT’s substation building and reserves ample space for convenient maintenance operation.<br />

Example of Rectifier+AIS cubicle delivered for a tramway substation<br />

Power Diode Blocks<br />

Diodes fitted in heatsinks combined<br />

with snubbers and optional fuses<br />

Reverse current<br />

detection<br />

RC Filter<br />

Combined with base-load<br />

resistor<br />

SWS / SWG<br />

Bipolar off-load motorized<br />

disconnecting swich with<br />

optional earthing connection<br />

Touch Voltage Protection<br />

Optional Negative-earth<br />

voltage threshold relay<br />

MIU10 / VM10<br />

Isolated amplifiers for current and<br />

voltage measurement<br />

Frame leakage detection<br />

Frame-earth current<br />

threshold relay<br />

IPT<br />

Optional Interphase coil<br />

for connection with coupled<br />

rectifier transformers<br />

Side view of rectifier+AIS cubicle (right side)<br />

Technical data<br />

Symbol<br />

Unit<br />

Rated service current I Ne [A] up to 1600 A<br />

Rated Power P [W] upt to 1200 kW<br />

Rated voltage U Ne [VDC] 900<br />

Rated insultation voltage U nm [VDC] 1800<br />

Nominal voltage U n [VDC] 600/750<br />

Power frequency withstand voltage U a [kV] 6.9 kV, 50 Hz, 1min.<br />

Output signal<br />

6 or 12 pulses<br />

Connection scheme<br />

1 or 2 Graetz bridges in parallel<br />

Protection degree (basic)<br />

IP20<br />

Ambient temperature range [VDC] -5 °C ... +40 °C<br />

Typical weight [kg] 950<br />

Dimensions (WxDxH) [mm] 1600x1400x2200<br />

Cooling<br />

Natural Air


Standards<br />

The <strong>SECUB</strong>-2 has been successfully type tested at IPH laboratory in Berlin.<br />

According to standards:<br />

• IEC 61992-2:2006<br />

• EN 50123-2:2003<br />

Approved type test reports available.<br />

Main features related to <strong>SECUB</strong>-2 breaker cubicle<br />

Rated voltage (Une)<br />

Rated insulation voltage<br />

Rated service current (Ine)<br />

Rated making & breaking capacity (Înss/Inss)<br />

Rated track time constant (Tnc)<br />

Duty classes<br />

900VDC<br />

1800VDC<br />

2600A<br />

100/150kA<br />

31.5ms<br />

f, e, d<br />

SG820794BEN_B00-05.13<br />

Sécheron SA<br />

Rue du Pré-Bouvier 25<br />

1217 Meyrin - Geneva<br />

CH-Switzerland<br />

Tel: +41 (0)22 739 41 11<br />

Fax: +41 (0)22 739 48 11<br />

substations@secheron.com<br />

www.secheron.com<br />

This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product,<br />

whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances,<br />

of the product’s maintenance conditions and requirements. Séche ron reserves all rights, especially those arising from our “General Delivery Conditions”.<br />

Copyright© 2007 Sécheron SA