D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
D.C. Switchgear Range Type SECUB-2 - Secheron
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SUBSTATIONS<br />
D.C. <strong>Switchgear</strong> <strong>Range</strong><br />
<strong>Type</strong> <strong>SECUB</strong>-2
A domain of expertise<br />
With a complete range of equipment and a leading expertise<br />
in DC traction power substations, Sécheron SA is a world<br />
leader and major partner for electrification of DC traction<br />
networks. Covering all activities from calculation, network<br />
design and engineering, up to the production of the DC<br />
Systems, Sécheron SA can offer customers and partners<br />
tailor made solutions based on a modular concept and<br />
standard products.<br />
Our equipment is developed on world leading technology<br />
and proven worldwide design and acceptance. In-house<br />
technology covers all key devices applied in the DC Systems<br />
(rectifiers, DC HSCB, Disconnecting Switches, Protection<br />
relays, measuring amplifiers, etc.).<br />
<strong>SECUB</strong>-2: DC switchgear for light rail applications<br />
The <strong>SECUB</strong>-2 cubicle is a compact DC switchgear solution<br />
designed for DC traction substations powering light transportation<br />
systems such as tramways, LRT, trolleybuses, monorails<br />
and LIM.<br />
<strong>SECUB</strong>-2 completes the range of Sécheron DC switchgear<br />
that covers heavy duty transportation systems.<br />
<strong>SECUB</strong>-2 is the improved evolution of the <strong>SECUB</strong> which has<br />
widely been installed in various networks since more than 10<br />
years.<br />
Main features<br />
• Rated current up to 2400 A (main circuit)<br />
• Rated voltage up to 900 Vdc<br />
• Metal enclosed switchgear compartment equipped with high-speed<br />
circuit-breaker<br />
• Bi-directional current interruption<br />
• Rated short-circuit current up to 100 kA (150 kA peak)<br />
• Equipped with a high-performance Protection and Control Relay type<br />
SEPCOS<br />
• Strong, compact and durable cubicle<br />
• Modular construction<br />
• Limited and easy maintenance<br />
• Designed according to EN 50123 & IEC 61992 standards<br />
New features:<br />
• Possibility to integrate a disconnecting switch in the rear compartment<br />
• Access from the front of the cubicle after having fully removed the drawer
Description<br />
The metal enclosed compartmented DC switchgear type <strong>SECUB</strong>-2 integrates three separated compartments for high and low<br />
voltage equipment:<br />
• Low voltage compartment including protection and control devices<br />
• High-speed circuit-breaker compartment<br />
• Rear high voltage busbar compartment including optional disconnecting switch<br />
Protection and control compartment<br />
Accessible from the front of the cubicle, the low voltage compartment includes the protection and control relay SEPCOS, the<br />
low voltage equipment (MCBs, relays etc.).<br />
High speed circuit breaker compartment<br />
The HV compartment includes the high-speed circuit-breaker which is mounted on a withdrawable drawer.<br />
The drawer can easily be drawn in or out of the cubicle and connected or disconnected from buses by means of power finger<br />
connectors.<br />
The HSCB’s auxiliary circuits can be connected or disconnected thanks to a multiple connector.<br />
The unlocking mechanism of the door ensures a trip of the HSCB before opening.<br />
Behind this door, a polycarbonate protecting screen ensures the security of personel and prevent contact with live parts.<br />
With the door open, the drawer can be drawn in or out with a handle located on the drawer frame (linked to a locking system).<br />
When the drawer has been drawn out, it can be easily placed on a trolley (optional) allowing easy maintenance operations and<br />
access inside the cubicle.<br />
The withdrawable circuit breaker drawer has four different positions:<br />
• Service<br />
• Test<br />
• Disconnected<br />
• Removed<br />
It is possible to see the physical<br />
state of the HSCB (opened or<br />
closed) as well as the drawer<br />
position (service or test) trough a<br />
window located on the front door.<br />
A counter showing the number<br />
of HSCB operation is also visible<br />
through this window.<br />
The drawer also contains a measuring shunt. The isolated amplifiers for current (MIU10) and voltage (VM10) measurement as well<br />
as the line test components are mounted on a retractable plate located below the drawer.<br />
With the plate removed, the power cable connection compartment is easily accessible inside the cubicle. This feature makes the<br />
installation against the wall possible.<br />
This compartment is separated from the busbar compartment thanks to isolating shutters.<br />
Rear high voltage busbar compartment<br />
The busbar rear compartment is composed of two main parts:<br />
• Main incoming busbar<br />
• Connection for outgoing cables, copper bars are provided to connect the power cable to the third rail or the catenary<br />
• As an option, an off load disconnecting switch can be mounted to insure the by-pass or line isolating function
Main technical data<br />
Symbol<br />
Unit<br />
Cubicle type<br />
<strong>SECUB</strong>-2 UR15 <strong>SECUB</strong>-2 UR26<br />
Rated service current I Ne [A] 1500 A 2600 A<br />
Rated voltage UNe [VDC] 900 900<br />
Rated insultation voltage Unm [VDC] 1800 1800<br />
Nominal voltage Un [VDC] 600/750 600/750<br />
Power frequency withstand voltage Ua [kV] 6.9 kV, 50 Hz, 1min.<br />
Rated service current<br />
Main busbar [kA] 2400A 2400A / 4000A*<br />
Rated short-circuit current INss / ÎNss [kA] 12 / 18 100 / 150<br />
Protection degree (doors and walls)<br />
IP30<br />
Protection degree (roof)<br />
IP20 / IP32** / IP42**<br />
Ambient temperature range [VDC] -5 °C ... +40 °C<br />
Typical weights (Without disconnector) [kg] 330 350<br />
Dimensions (WxDxH) [mm] 450x1400x2200<br />
* 4000A: option<br />
** IP32/IP42: option<br />
Designed according to standard specifications EN 501 23 and IEC 61992<br />
Composition<br />
Unique feature:<br />
Key components of the switchgear are designed and manufactured by Sécheron and are fully compatible.<br />
SEPCOS<br />
Protection relay<br />
SWS18.20<br />
Disconnecting Switch<br />
SEPCOS<br />
Touch-screen display<br />
VM10<br />
Isolated amplifier for<br />
Voltage Measurement<br />
UR26.81S<br />
High-speed circuit breaker<br />
MIU10<br />
Isolated amplifier for<br />
Current Measurement
Main dimensions<br />
1. Circuit-breaker<br />
450<br />
1400<br />
2. Withdrawable breaker drawer<br />
3. Low-voltage compartment<br />
(protection and control circuits)<br />
4. Main plugs (power circuit)<br />
100<br />
3<br />
1075<br />
325<br />
5. Shunt (current)<br />
6. Current measuring amplifier<br />
7. Voltage measuring amplifier<br />
8<br />
10<br />
8. Busbar compartment<br />
9. Output cable<br />
2200<br />
11<br />
10. Bypass busbar (option)<br />
11. Disconnecting switch (option)<br />
12. Main busbar<br />
1<br />
12<br />
4<br />
1430<br />
2<br />
5<br />
6<br />
7<br />
9<br />
<strong>SECUB</strong>-2 HSCB cubicle: Main applications<br />
Main configurations:<br />
MAIN BUSBAR<br />
MAIN BUSBAR<br />
MAIN BUSBAR<br />
1. Line feeder<br />
E SEPCOS E SEPCOS E SEPCOS<br />
2. Line feeder with isolating switch<br />
Line Test<br />
I ><br />
Line Test<br />
I > I ><br />
I I I<br />
Line Test<br />
3. Line feeder with earthing switch<br />
MIU10<br />
MIU10<br />
MIU10<br />
4. Rectifier breaker<br />
U<br />
VM10<br />
M<br />
U<br />
VM10<br />
U<br />
VM10<br />
5. Line feeder with bypass<br />
1<br />
2 3<br />
MAIN BUSBAR<br />
MAIN BUSBAR<br />
BY-PASS BUSBAR<br />
E<br />
SEPCOS<br />
E<br />
SEPCOS<br />
I ><br />
I ><br />
I<br />
MIU10<br />
Line Test<br />
I<br />
MIU10<br />
M<br />
U<br />
VM10<br />
4<br />
5
SEPCOS control and protection relay<br />
SEPCOS is a protection and control unit that is applied to the outgoing feeder or the<br />
incoming HSCB cubicles in the DC traction substation.<br />
Main features:<br />
• Modular PLC concept, PLC programming, IEC61131 normalized programming.<br />
• Fully approved in railway substation environment EN50255-22.<br />
• High noise immunity thanks to sampling rate at 40 microseconds and<br />
16 bits A-D converter.<br />
Protection functions:<br />
• All typical protection functions (e.g. Function DDL +/-, Imax +/-, etc.).<br />
Control functions:<br />
• HSCB ON / OFF control with electric or magnetic holding.<br />
• Intertripping, automatic reclosing, anti-pumping, line test function.<br />
• External synchronization of the PLC, measurement supervisor control.<br />
Open to all customer network and protocols:<br />
• TCP/IP: MODBUS-TCP<br />
• Specific TCP/IP based power distribution protocols:<br />
- IEC60870-5-104<br />
- DNP3<br />
- IEC61850<br />
• Fieldbus: MODBUS-RTU, Profibus DP<br />
SEPCOS in the low-voltage compartment<br />
The SEPCOS may be controlled and parametrized<br />
through a user friendly 7″ color Touch Screen display<br />
which is located on the front door of the cubicle.<br />
All functions are available through a web server<br />
(S-Web), including visualization of trends.<br />
Products and Services<br />
Sécheron provides complete DC substations systems including:<br />
• Transformer-rectifier group<br />
• DC switchgear including:<br />
- DC HSCB cubicles<br />
- Disconnector cubicles<br />
- Contactor cubicles<br />
• Voltage limiting devices<br />
• Protection and control systems<br />
• Human Machine Interfaces<br />
Sécheron also provides services in order to support customers in network design and installation of our systems:<br />
• DC System Engineering<br />
• Dynamic simulation of complete networks<br />
• Short-circuit, earthing circuit and harmonic calculation<br />
• Supervision of installation and commissioning<br />
• In line and field testing
Full compact lightrail solution<br />
With years of experience in the field of traction rectifiers, today proposes a cubicle which integrates both functions of rectifier and<br />
isolating switch.<br />
This cubicle is normally used combined with the <strong>SECUB</strong>-2.<br />
It is a compact solution for LRT’s substation building and reserves ample space for convenient maintenance operation.<br />
Example of Rectifier+AIS cubicle delivered for a tramway substation<br />
Power Diode Blocks<br />
Diodes fitted in heatsinks combined<br />
with snubbers and optional fuses<br />
Reverse current<br />
detection<br />
RC Filter<br />
Combined with base-load<br />
resistor<br />
SWS / SWG<br />
Bipolar off-load motorized<br />
disconnecting swich with<br />
optional earthing connection<br />
Touch Voltage Protection<br />
Optional Negative-earth<br />
voltage threshold relay<br />
MIU10 / VM10<br />
Isolated amplifiers for current and<br />
voltage measurement<br />
Frame leakage detection<br />
Frame-earth current<br />
threshold relay<br />
IPT<br />
Optional Interphase coil<br />
for connection with coupled<br />
rectifier transformers<br />
Side view of rectifier+AIS cubicle (right side)<br />
Technical data<br />
Symbol<br />
Unit<br />
Rated service current I Ne [A] up to 1600 A<br />
Rated Power P [W] upt to 1200 kW<br />
Rated voltage U Ne [VDC] 900<br />
Rated insultation voltage U nm [VDC] 1800<br />
Nominal voltage U n [VDC] 600/750<br />
Power frequency withstand voltage U a [kV] 6.9 kV, 50 Hz, 1min.<br />
Output signal<br />
6 or 12 pulses<br />
Connection scheme<br />
1 or 2 Graetz bridges in parallel<br />
Protection degree (basic)<br />
IP20<br />
Ambient temperature range [VDC] -5 °C ... +40 °C<br />
Typical weight [kg] 950<br />
Dimensions (WxDxH) [mm] 1600x1400x2200<br />
Cooling<br />
Natural Air
Standards<br />
The <strong>SECUB</strong>-2 has been successfully type tested at IPH laboratory in Berlin.<br />
According to standards:<br />
• IEC 61992-2:2006<br />
• EN 50123-2:2003<br />
Approved type test reports available.<br />
Main features related to <strong>SECUB</strong>-2 breaker cubicle<br />
Rated voltage (Une)<br />
Rated insulation voltage<br />
Rated service current (Ine)<br />
Rated making & breaking capacity (Înss/Inss)<br />
Rated track time constant (Tnc)<br />
Duty classes<br />
900VDC<br />
1800VDC<br />
2600A<br />
100/150kA<br />
31.5ms<br />
f, e, d<br />
SG820794BEN_B00-05.13<br />
Sécheron SA<br />
Rue du Pré-Bouvier 25<br />
1217 Meyrin - Geneva<br />
CH-Switzerland<br />
Tel: +41 (0)22 739 41 11<br />
Fax: +41 (0)22 739 48 11<br />
substations@secheron.com<br />
www.secheron.com<br />
This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product,<br />
whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances,<br />
of the product’s maintenance conditions and requirements. Séche ron reserves all rights, especially those arising from our “General Delivery Conditions”.<br />
Copyright© 2007 Sécheron SA