<strong>Specification</strong> - Outdoor Units<br />

System<br />

• High Efficiency<br />

• Large Capacity<br />

• Advanced and Reliable Protection<br />

• Easy Installation & Maintenance<br />

• Eco-friendly<br />

• Comfortable Operation<br />

• Premium Quality Control Heat Recovery<br />

DVM PLUS IV HP / HR COMPACT MODULE<br />

DVM PLUS IV HP RD080HHXGB RD100HHXGB<br />

Model Name<br />

DVM PLUS IV HR RD080HRXGB RD100HRXGB<br />

Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50<br />

Mode - HP / HR HP / HR<br />

Performance<br />

Power<br />

HP HP 8 10<br />

Capacity<br />

(Nominal)<br />

Cooling<br />

Heating<br />

kW 22.4 28.0<br />

Btu/h 76,400 95,500<br />

kW 25.2 31.5<br />

Btu/h 86,000 107,500<br />

Power Input<br />

Cooling<br />

5.20 7.04<br />

kW<br />

(Nominal)<br />

Heating 5.46 6.89<br />

Current Input<br />

Cooling<br />

8.80 13.00<br />

A<br />

(Nominal)<br />

Heating 11.40 12.70<br />

Circuit Breaker (MCCB+ELB / ELCB) A 30 30<br />

Nominal Cooling - 4.31 3.98<br />

COP<br />

Nominal Heating - 4.62 4.57<br />

Fan Air Flow Rate CMM 173 173<br />

Piping<br />

Connections<br />

Liquid Pipe , mm 9.52 9.52<br />

Gas Pipe , mm 19.05 22.23<br />

Discharge Gas Pipe (DVM PLUS IV HR) , mm 15.88 19.05<br />

Oil Equalizing Pipe , mm - -<br />

Installation<br />

Max. Length m 200 200<br />

Limitation<br />

Max. Height m 110 (40)* 110 (40)*<br />

Type - R410A R410A<br />

Refrigerant<br />

Factory Charging kg 5.0 5.0<br />

Sound Sound Pressure dB(A) 57 58<br />

External<br />

Dimension<br />

Operating<br />

Temp. Range<br />

Net Weight<br />

DVM PLUS IV HP<br />

237 237<br />

kg<br />

DVM PLUS IV HR 243 243<br />

Shipping Weight<br />

DVM PLUS IV HP<br />

253 253<br />

kg<br />

DVM PLUS IV HR 259 259<br />

Net Dimensions (WxHxD) mm 880 x 1695 x 765 880 x 1695 x 765<br />

Shipping Dimensions (WxHxD) mm 948 x 1912 x 832 948 x 1912 x 832<br />

Cooling °C -5 ~ 48 -5 ~ 48<br />

Heating °C -20 ~ 24 -20 ~ 24<br />

System<br />

10<br />

2012 SAMSUNG<br />

System Air Conditioner<br />

DVM PLUS IV HP / HR COMPACT MODULE<br />

DVM PLUS IV HP RD120HHXGB RD140HHXGB RD160HHXGB RD180HHXGB RD200HHXGB<br />

Model Name<br />

DVM PLUS IV HR RD120HRXGB RD140HRXGB RD160HRXGB RD180HRXGB RD200HRXGB<br />

Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50<br />

Mode - HP / HR HP / HR HP / HR HP / HR HP / HR<br />

Performance<br />

Power<br />

HP HP 12 14 16 18 20<br />

Capacity<br />

(Nominal)<br />

Cooling<br />

Heating<br />

kW 33.6 39.2 44.8 50.4 56.0<br />

Btu/h 114,600 133,800 152,900 172,000 191,100<br />

kW 37.8 44.1 50.4 56.7 63.0<br />

Btu/h 129,000 150,500 172,000 193,500 215,000<br />

Power Input<br />

Cooling<br />

9.20 10.10 12.00 15.70 17.00<br />

kW<br />

(Nominal)<br />

Heating 8.50 9.65 11.30 12.90 14.50<br />

Current Input<br />

Cooling<br />

20.00 20.90 22.00 31.30 32.80<br />

A<br />

(Nominal)<br />

Heating 18.40 19.40 27.20 26.70 29.10<br />

Circuit Breaker (MCCB+ELB / ELCB) A 40 40 50 60 60<br />

Nominal Cooling - 3.65 3.88 3.73 3.21 3.29<br />

COP<br />

Nominal Heating - 4.45 4.57 4.46 4.40 4.34<br />

Fan Air Flow Rate CMM 210 226 250 270 275<br />

Piping<br />

Connections<br />

Liquid Pipe , mm 12.70 12.70 12.70 15.88 15.88<br />

Gas Pipe , mm 25.40 25.40 28.58 28.58 28.58<br />

Discharge Gas Pipe (DVM PLUS IV HR) , mm 22.23 22.23 25.40 25.40 25.40<br />

Oil Equalizing Pipe , mm - - - - -<br />

Installation<br />

Max. Length m 200 200 200 200 200<br />

Limitation<br />

Max. Height m 110 (40)* 110 (40)* 110 (40)* 110 (40)* 110 (40)*<br />

Type - R410A R410A R410A R410A R410A<br />

Refrigerant<br />

Factory Charging kg 5.0 7.0 7.0 8.5 8.5<br />

Sound Sound Pressure dB(A) 58 58 60 60 61<br />

External<br />

Dimension<br />

Operating<br />

Temp. Range<br />

Net Weight<br />

DVM PLUS IV HP<br />

240 280 329 340 349<br />

kg<br />

DVM PLUS IV HR 243 293 338 349 355<br />

Shipping Weight<br />

DVM PLUS IV HP<br />

256 301 350 361 370<br />

kg<br />

DVM PLUS IV HR 259 314 359 369 376<br />

Net Dimensions (WxHxD) mm 880 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765 1295 x 1695 x 765<br />

Shipping Dimensions (WxHxD) mm 948 x 1912 x 832 1363 x 1912 x 832 1363 x 1912 x 832 1363 x 1912 x 832 1363 x 1912 x 832<br />

Cooling °C -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48<br />

Heating °C -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24<br />

* Product <strong>Specification</strong>s in the Publication can be changed without a prior notice. Because there is always an ongoing improvement on our product.<br />

* If you wish to install an outdoor unit module with a capacity of over 60 HP, then please contact your local Samsung Dealer.<br />

* The maximum height of installation limitation for piping connections is only allowable when using PDM kits.<br />

11<br />

2012 SAMSUNG<br />

System Air Conditioner