Specification
Specification
Specification
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Specification</strong> - Outdoor Units<br />
System<br />
12<br />
2012 SAMSUNG<br />
System Air Conditioner<br />
DVM PLUS IV HP / HR COMPACT MODULE<br />
DVM PLUS IV HP RD220HHXGB RD240HHXGB RD260HHXGB RD280HHXGB RD300HHXGB<br />
Model Name<br />
DVM PLUS IV HR RD220HRXGB RD240HRXGB RD260HRXGB RD280HRXGB RD300HRXGB<br />
Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50<br />
Mode - HP / HR HP / HR HP / HR HP / HR HP / HR<br />
Performance<br />
Power<br />
HP HP 22 24 26 28 30<br />
Capacity<br />
(Nominal)<br />
Cooling<br />
Heating<br />
kW 61.6 67.2 72.8 78.4 84<br />
Btu/h 210,200 229,300 248,400 267,500 286,600<br />
kW 69.3 75.6 81.9 88.2 94.5<br />
Btu/h 236,500 258,000 279,500 301,000 322,400<br />
Power Input<br />
Cooling<br />
16.24 18.4 19.3 21.2 24.9<br />
kW<br />
(Nominal)<br />
Heating 15.39 17 18.15 19.8 21.4<br />
Current Input<br />
Cooling<br />
33 40 40.9 42 51.3<br />
A<br />
(Nominal)<br />
Heating 31.1 36.8 37.8 45.6 45.1<br />
Circuit Breaker (MCCB+ELB / ELCB) A 75 75 75 75 100<br />
Nominal Cooling - 3.79 3.65 3.77 3.7 3.37<br />
COP<br />
Nominal Heating - 4.5 4.45 4.51 4.45 4.42<br />
Fan Air Flow Rate CMM (173) x 1 + (210) x 1 (210) x 2 (210) x 1 + (226) x 1 (210) x 1 + (250) x 1 (210) x 1 + (270) x 1<br />
Piping<br />
Connections<br />
Liquid Pipe , mm 15.88 15.88 19.05 19.05 19.05<br />
Gas Pipe , mm 28.58 28.58 31.75 31.75 31.75<br />
Discharge Gas Pipe (DVM PLUS IV HR) , mm 25.40 25.40 28.58 28.58 28.58<br />
Oil Equalizing Pipe , mm 6.35 6.35 6.35 6.35 6.35<br />
Installation<br />
Max. Length m 200 200 200 200 200<br />
Limitation<br />
Max. Height m 110 (40)* 110 (40)* 110 (40)* 110 (40)* 110 (40)*<br />
Type - R410A R410A R410A R410A R410A<br />
Refrigerant<br />
Factory Charging kg 10 10 12 12 13.5<br />
Sound Sound Pressure dB(A) 61 61 61 61 62<br />
External<br />
Dimension<br />
Operating<br />
Temp. Range<br />
Net Weight<br />
DVM PLUS IV HP<br />
(237) x 1 + (240) x 1 (240) x 2 (240) x 1 + (280) x 1 (240) x 1 + (329) x 1 (240) x 1 + (340) x 1<br />
kg<br />
DVM PLUS IV HR (243) x 2 (243) x 2 (243) x 1 + (293) x 1 (243) x 1 + (338) x 1 (243) x 1 + (349) x 1<br />
Shipping Weight<br />
DVM PLUS IV HP<br />
(253) x 1 + (256) x 1 (256) x 2 (256) x 1 + (301) x 1 (256) x 1 + (350) x 1 (256) x 1 + (361) x 1<br />
kg<br />
DVM PLUS IV HR (259) x 2 (259) x 2 (259) x 1 + (314) x 1 (259) x 1 + (359) x 1 (259) x 1 + (369) x 1<br />
Net Dimensions (WxHxD) mm (880 x 1695 x 765) x 2 (880 x 1695 x 765) x 2 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 1 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 1 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 1<br />
Shipping Dimensions (WxHxD) mm (948 x 1912 x 832) x 2 (948 x 1912 x 832) x 2 (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 1 (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 1 (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 1<br />
Cooling °C -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48<br />
Heating °C -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24<br />
DVM PLUS IV HP / HR COMPACT MODULE<br />
DVM PLUS IV HP RD320HHXGB RD340HHXGB RD360HHXGB RD380HHXGB RD400HHXGB<br />
Model Name<br />
DVM PLUS IV HR RD320HRXGB RD340HRXGB RD360HRXGB RD380HRXGB RD400HRXGB<br />
Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50<br />
Mode - HP / HR HP / HR HP / HR HP / HR HP / HR<br />
Performance<br />
Power<br />
HP HP 32 34 36 38 40<br />
Capacity<br />
(Nominal)<br />
Cooling<br />
Heating<br />
kW 89.6 95.2 100.8 106.4 112<br />
Btu/h 305,700 324,800 343,900 363,100 382,200<br />
kW 100.8 107.1 113.4 119.7 126<br />
Btu/h 343,900 365,400 386,900 408,400 429,900<br />
Power Input<br />
Cooling<br />
26.2 27.1 29 32.7 34<br />
kW<br />
(Nominal)<br />
Heating 23 24.15 25.8 27.4 29<br />
Current Input<br />
Cooling<br />
52.8 53.7 54.8 64.1 65.6<br />
A<br />
(Nominal)<br />
Heating 47.5 48.5 56.3 55.8 58.2<br />
Circuit Breaker (MCCB+ELB / ELCB) A 100 100 100 100 100<br />
Nominal Cooling - 3.42 3.51 3.48 3.25 3.29<br />
COP<br />
Nominal Heating - 4.38 4.43 4.4 4.37 4.34<br />
Fan Air Flow Rate CMM (210) x 1 + (275) x 1 (226) x 1 + (275) x 1 (250) x 1 + (275) x 1 (270) x 1 + (275) x 1 (275) x 2<br />
Piping<br />
Connections<br />
Liquid Pipe , mm 19.05 19.05 19.05 19.05 19.05<br />
Gas Pipe , mm 31.75 31.75 38.1 38.1 38.1<br />
Discharge Gas Pipe (DVM PLUS IV HR) , mm 28.58 28.58 31.75 31.75 31.75<br />
Oil Equalizing Pipe , mm 6.35 6.35 6.35 6.35 6.35<br />
Installation<br />
Max. Length m 200 200 200 200 200<br />
Limitation<br />
Max. Height m 110 (40)* 110 (40)* 110 (40)* 110 (40)* 110 (40)*<br />
Type - R410A R410A R410A R410A R410A<br />
Refrigerant<br />
Factory Charging kg 13.5 15.5 15.5 17 17<br />
Sound Sound Pressure dB(A) 63 63 64 64 64<br />
External<br />
Dimension<br />
Operating<br />
Temp. Range<br />
Net Weight<br />
DVM PLUS IV HP<br />
(240) x 1 + (349) x 1 (280) x 1 + (349) x 1 (329) x 1 + (349) x 1 (340) x 1 + (349) x 1 (349) x 2<br />
kg<br />
DVM PLUS IV HR (243) x 1 + (355) x 1 (293) x 1 + (355) x 1 (338) x 1 + (355) x 1 (349) x 1 + (355) x 1 (355) x 2<br />
Shipping Weight<br />
DVM PLUS IV HP<br />
(256) x 1 + (370) x 1 (301) x 1 + (370) x 1 (350) x 1 + (370) x 1 (361) x 1 + (370) x 1 (370) x 2<br />
kg<br />
DVM PLUS IV HR (259) x 1 + (376) x 1 (314) x 1 + (376) x 1 (359) x 1 + (376) x 1 (369) x 1 + (376) x 1 (376) x 2<br />
Net Dimensions (WxHxD) mm (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 1 (1295 x 1695 x 765) x 2 (1295 x 1695 x 765) x 2 (1295 x 1695 x 765) x 2 (1295 x 1695 x 765) x 2<br />
Shipping Dimensions (WxHxD) mm (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 1 (1363 x 1912 x 832) x 2 (1363 x 1912 x 832) x 2 (1363 x 1912 x 832) x 2 (1363 x 1912 x 832) x 2<br />
Cooling °C -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48<br />
Heating °C -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24<br />
* Product <strong>Specification</strong>s in the Publication can be changed without a prior notice. Because there is always an ongoing improvement on our product.<br />
* If you wish to install an outdoor unit module with a capacity of over 60 HP, then please contact your local Samsung Dealer.<br />
* The maximum height of installation limitation for piping connections is only allowable when using PDM kits.<br />
System<br />
13<br />
2012 SAMSUNG<br />
System Air Conditioner