• Press and at the same time 4 s. or wait 60 s.<br />
Switch on/off the power supply to the instrument after modification to carry out changes.<br />
Restoring the default values of configuration parameters<br />
Press and at the same time 4 s . PA shows in the display.<br />
Press and use or to set 743.<br />
Press or wait 15 s until PA shows.<br />
Press and at the same time ca 4 s . dEF shows in the display.<br />
Press and use or to set 149.<br />
Press or wait 15s. The instrument will flash dEF for 4s and then return to normal operation with default values<br />
Make sure the default value of the parameter is appropriate, in particular if the probes are PTC probes.<br />
Note that also the values for probe type will change if PTC probes are installed.<br />
Signaler<br />
LED compressor<br />
If it is lit, the compressor will be turned on.<br />
Flashes at modification of working setpoint or at delay, see par C0, C1, C2 and i7<br />
LED defrost<br />
If it is lit, the defrost will be running. Flashes at delay, see par C0, C1, C2, d7 and dA<br />
LED fan<br />
If it is lit, the evaporator fan will be turned on.<br />
Flashes when delay is activated, see par F3<br />
LED alarm<br />
If it is lit, an alarm will be running.<br />
Loc<br />
Is shown in the display when the keyboard is locked, see par r3 and the section about locked keyboard.<br />
- - - - Is shown in the display when the value is not available (for example if a probe is deactivated).<br />
Alarm<br />
AL = Low temperature alarm (see A0, A1 and A2)<br />
AH = High temperature alarm (see A3, A4 and A5)<br />
ld = Door switch input alarm (only if P4=3 and i0=3) (see i0 and i1) The compressor will be stopped.<br />
IA = Multipurpose input alarm (only if P4=3 and i0=0)(see i1 and i5).<br />
If i5=4 the compressor will be stopped.<br />
lSd = Instrument locked (only if P4=3 and i0=0) (see i1, i5, i7, i8 and i9)<br />
Compressor will be stopped.<br />
COH = Overheated condenser alarm (only if P4=2) (see C6)<br />
CSd = Compressor locked (only if P4=2)(see C7) Compressor will be stopped.<br />
Pr1 = Cabinet probe error (see P0)<br />
The compressor depends on par C4 and C5.<br />
Pr2 = Condenser probe error (see P0)<br />
If P4=1 Defrost uses time set by par d3.<br />
If P4=1 and d8=2 the instrument works as if d8 has the value 0.<br />
If P4=2 the condenser alarm Will not be activated.<br />
17