11. The manhole sides, bottom and external flume sections shall be<br />

designed to withstand a static load of 150 lb/ft per foot (68<br />

kg/305mm) of depth with less than l/4" (6mm) deflection.<br />

12. There shall be no light duty angles of flanges protruding beyond the<br />

flume or manhole that can be damaged by shear or load forces.<br />

13. Inlet and Outlet Pipes: The FRP manhole and flume shall be provided<br />

with _____ inch / millimeter O.D. pipe stubs for connection to<br />

______ inch / millimeter O.D. incoming and outgoing (concrete /<br />

clay / fiberglass / cast iron / PVC) pipe. Flume end adapters shall<br />

allow a smooth flow transition from pipe flow to flume flow.<br />

a. Two neoprene boots with stainless steel clamping bands shall<br />

be supplied and sized to connect inlet and outlet pipe stubs<br />

to the pipeline.<br />

b. Pipe stubs shall have slip flanges for connection to existing line.<br />

14. Cover<br />

a. The <strong>Packaged</strong> <strong>Metering</strong> <strong>Manhole</strong> will be furnished with a<br />

fiberglass cover equipped with heavy duty stainless steel<br />

hinges having l/2" (12mm) diameter hinge pins and<br />

stainless steel hasp for locking. The cover shall be<br />

sufficient strength to withstand 1000 lbs. (454kg) top load.<br />

The cover shall overlap the manhole and seat on a<br />

neoprene seal to prevent dirt, rain and debris from getting<br />

into the manhole.<br />

b. The <strong>Packaged</strong> <strong>Metering</strong> <strong>Manhole</strong> shall have a gastight<br />

aluminum lid for non-traffic loads mounted with a 20" / 24"<br />

(508mm / 610mm) concentric manway.<br />

c. The <strong>Packaged</strong> <strong>Metering</strong> <strong>Manhole</strong> shall have a concentric<br />

manway designed to withstand a 16,000 lb. (7257kg)<br />

vertical dynamic wheel load (H-20), plus lateral forces from<br />

earth loading, ground water and frozen soil. The manhole<br />

opening shall be a (4' (1219mm) diameter barrel use: 22-<br />

1/2" (572mm) I.D or 28" (711mm) I.D. - 5' (1524mm)<br />

diameter barrel use 22-1/2" (572mm) I.D., 28" (711mm) I.D.<br />

or 36" (914mm) I.D.) manway for use with a cast iron cover,<br />

suitable for H-20 highway loading.<br />

d. The <strong>Packaged</strong> <strong>Metering</strong> <strong>Manhole</strong> shall have aluminum hatch<br />

access ____ inch / millimeter x ____ inch / millimeter.<br />

15. Internal Ladder: The ladder rungs shall have a non-slip traction<br />

surface and internal stainless steel safety bar. The ladder shall<br />

meet or exceed OSHA General Industry Standards, Part 1910.27<br />

for "Fixed Ladders".<br />

16. Utility Tap: The manhole barrel shall be fitted with a 2" (51mm) FRP<br />

through-wall utility tap(s) having threaded connections to permit<br />

sub-grade entrance for power, sample or recording lines without<br />

damaging the watertight integrity of the manhole.<br />

17. A l/2” (12mm) thick expanded polystyrene bead board will be supplied<br />

for placement on the concrete slab under the manhole.<br />

4