20.01.2015 Views

Field TZIDC-110 Electro-Pneumatic Positioner

Field TZIDC-110 Electro-Pneumatic Positioner

Field TZIDC-110 Electro-Pneumatic Positioner

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>TZIDC</strong>-<strong>110</strong> <strong>Electro</strong>-<strong>Pneumatic</strong> <strong>Positioner</strong><br />

for PROFIBUS PA<br />

10/18-0.23 EN<br />

Operation<br />

General<br />

The intelligent microprocessor-controlled <strong>TZIDC</strong>-<strong>110</strong> positioner<br />

is designed for achieving optimal results. Its stands out for quick<br />

and precise control until reaching the set point and for high operational<br />

reliability. The activation and adjustment of parameters<br />

necessary to achieve this goal is done automatically by the Autoadjust<br />

function. If required, the settings can be changed manually.<br />

The total range of parameters includes:<br />

• Operating parameters<br />

• Adjustment parameters<br />

• Monitoring parameters<br />

• Diagnosis parameters<br />

Operating parameters<br />

The following operating parameters can be activated and<br />

adjusted:<br />

• Characteristic curve (travel = f {pos. signal})<br />

linear,<br />

equal percentage 1:25 or 1:50 or 25:1 or 50:1,<br />

or user-configurable with 20 reference points<br />

• Tolerance band<br />

When reaching the tolerance band the position is considered<br />

as having reached the setpoint. From this point on, the position<br />

is further slowly re-adjusted until the dead band is reached.<br />

The factory setting for this parameter is 0.3 %.<br />

• Dead band (sensitivity)<br />

When reaching the dead band, the position is held. The factory<br />

setting for this parameter is 0.1 %.<br />

Both the tolerance band and the dead band are automatically<br />

determined during the positioner’s self-optimization.<br />

• Travel limiting<br />

The positioning travel, i.e. the stroke or angle of rotation, can<br />

be reduced as required within the full range of 0...100%,<br />

provided that a minimum value of 20% is observed.<br />

• Shut-off function<br />

This function can be selected separately for each end position.<br />

When the respective configured limit value is exceeded, the<br />

shut-off function causes immediate travel of the actuator until<br />

reaching the set end position.<br />

• Travel time prolongation<br />

With this function the max. travel time for full travel can be increased.<br />

This time parameter can be set separately for each direction<br />

• Control in the end position<br />

Here you can define whether the pneumatic actuator shall be<br />

fully pressurized or the position shall be further controlled in the<br />

end position. This parameter can be set separately for each<br />

end position.<br />

Adjustment parameters<br />

The <strong>TZIDC</strong>-<strong>110</strong> positioner has a special function (Autoadjust) for<br />

automatic adjustment of all relevant parameters. The Autoadjust<br />

function can be started by pressing the respective push-buttons<br />

on the device’s front panel or by using the configuration program<br />

on a remote PC.<br />

The following parameters can be activated and adjusted:<br />

• Control parameters<br />

To adapt the <strong>TZIDC</strong>-<strong>110</strong> positioner to the control action of the<br />

valve, the control parameters can be adjusted individually to<br />

achieve optimal control until reaching the set point.<br />

• Valve range 0...100 %<br />

Valve end positions, start of range "0 %” and end of range<br />

"100 %".<br />

• Effective direction of the actuator<br />

Adjustment to either of the two possible directions:<br />

Air to open/spring force to close<br />

or<br />

Air to close/spring force to open<br />

• Display 0...100 %<br />

Adjusting the display (0...100 %) to the direction of action for<br />

opening or closing the valve.<br />

Monitoring parameters<br />

Various functions for permanent device monitoring are implemented<br />

in the operating program of the <strong>TZIDC</strong>-<strong>110</strong> positioner:<br />

• Internal output circuit monitoring<br />

• Monitoring to check whether or not the position is out of the<br />

adjusted range (rotation angle) for position feedback.<br />

• Monitoring for positioning time-out (adjustable time parameter)<br />

• Monitoring of the stroke and travel counter to check if the limit<br />

value is exceeded (limits can be adjusted during diagnosis)<br />

While automatic commissioning is in progress, the current state<br />

is continuously indicated on the integrated LC display. All other<br />

messages can be called up for display via the graphical user<br />

interface.<br />

Extended monitoring is possible via the fieldbus. The most<br />

important process variables like the output signal (in %), the position<br />

(in %), the deviation (in %), and troubles occurring during<br />

operation are indicated as plain text in a special line.<br />

Diagnosis parameters<br />

The diagnosis parameters of the <strong>TZIDC</strong>-<strong>110</strong> program inform the<br />

operator about the operating conditions of the valve. From this<br />

information the operator can derive which maintenance works<br />

are required, and when. Additionally, limit values can be defined<br />

for these parameters. When they are exceeded, an alarm is<br />

reported.<br />

The following values are e.g. determined:<br />

• Number of control actions performed by the valve<br />

• Total stroking distance<br />

The diagnosis parameters and limit values can be called up, set,<br />

and reset via the fieldbus, by using the special <strong>TZIDC</strong>-<strong>110</strong> configuration<br />

program.<br />

4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!