21.01.2015 Views

VAV box reheat is active, damper is open to maximum ... - BetterBricks

VAV box reheat is active, damper is open to maximum ... - BetterBricks

VAV box reheat is active, damper is open to maximum ... - BetterBricks

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

If the <strong>damper</strong> position <strong>is</strong> constant when you would expect variation, then the mo<strong>to</strong>r opera<strong>to</strong>r or DDC-<strong>box</strong><br />

controller (including the pressure transducer and its tubing) may be the problem.<br />

If the <strong>damper</strong> position <strong>is</strong> constant, the duct static pressure <strong>is</strong> not sat<strong>is</strong>fied, and the AHU VSD <strong>is</strong> at 100%,<br />

then the system capacity <strong>is</strong> inadequate, or there may be a large duct leak somewhere in the system.<br />

(Contrac<strong>to</strong>rs have been known <strong>to</strong> remove terminal units and leave the medium-pressure ducting wide<br />

<strong>open</strong> for added ventilation during renovation projects.)<br />

If the AHU SP <strong>is</strong> being maintained and the VSD <strong>is</strong> cycling as needed <strong>to</strong> maintain the setpoint, there may<br />

be a closed fire <strong>damper</strong> upstream of the <strong>VAV</strong> <strong>box</strong>. Inspect any other <strong>VAV</strong> <strong>box</strong>es being fed by the same<br />

branch duct (downstream of the last fire <strong>damper</strong>) <strong>to</strong> see if they exhibit similar problems.<br />

Example of Normal Operation<br />

If your graph looks similar <strong>to</strong> the one below then your system <strong>is</strong> operating as it should and the problem <strong>is</strong><br />

resolved. The <strong>damper</strong> <strong>is</strong> at minimum position while <strong>reheat</strong> <strong>is</strong> <strong>active</strong>. When the thermostat calls for cooling,<br />

the <strong>reheat</strong> goes <strong>to</strong> zero and the <strong>damper</strong> <strong>open</strong>s as needed <strong>to</strong> sat<strong>is</strong>fy the space requirements. Note that the<br />

fan static pressure <strong>is</strong> maintained throughout the day.<br />

Normal <strong>VAV</strong>-<strong>box</strong> operation<br />

Examples of Abnormal Operation<br />

<strong>VAV</strong> <strong>box</strong>es are no<strong>to</strong>rious for having many different modes of failure. Below are two examples of what a<br />

trend log of abnormal operation might look like, but your own trend-log graph will probably have its own<br />

unique features.<br />

If your graph looks similar <strong>to</strong> one below then your system <strong>is</strong> not operating as it should and the problem <strong>is</strong><br />

unresolved. The <strong>reheat</strong> <strong>is</strong> energized at 50% once the <strong>damper</strong> r<strong>is</strong>es above minimum setpoint. Airflow from<br />

the AHU <strong>to</strong> the pressure-sensor location <strong>is</strong> not a problem since it can maintain static pressure. Inspect the<br />

static pressure at the <strong>VAV</strong> <strong>box</strong> locally <strong>to</strong> make sure it has adequate pressure. There may be a partially<br />

Produced by <strong>BetterBricks</strong>, the commercial initiative of the Northwest Energy Efficiency Alliance<br />

BOpTlsMstrPrb22.doc • 3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!