VAV box reheat is active, damper is open to maximum ... - BetterBricks
VAV box reheat is active, damper is open to maximum ... - BetterBricks
VAV box reheat is active, damper is open to maximum ... - BetterBricks
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
If the <strong>damper</strong> position <strong>is</strong> constant when you would expect variation, then the mo<strong>to</strong>r opera<strong>to</strong>r or DDC-<strong>box</strong><br />
controller (including the pressure transducer and its tubing) may be the problem.<br />
If the <strong>damper</strong> position <strong>is</strong> constant, the duct static pressure <strong>is</strong> not sat<strong>is</strong>fied, and the AHU VSD <strong>is</strong> at 100%,<br />
then the system capacity <strong>is</strong> inadequate, or there may be a large duct leak somewhere in the system.<br />
(Contrac<strong>to</strong>rs have been known <strong>to</strong> remove terminal units and leave the medium-pressure ducting wide<br />
<strong>open</strong> for added ventilation during renovation projects.)<br />
If the AHU SP <strong>is</strong> being maintained and the VSD <strong>is</strong> cycling as needed <strong>to</strong> maintain the setpoint, there may<br />
be a closed fire <strong>damper</strong> upstream of the <strong>VAV</strong> <strong>box</strong>. Inspect any other <strong>VAV</strong> <strong>box</strong>es being fed by the same<br />
branch duct (downstream of the last fire <strong>damper</strong>) <strong>to</strong> see if they exhibit similar problems.<br />
Example of Normal Operation<br />
If your graph looks similar <strong>to</strong> the one below then your system <strong>is</strong> operating as it should and the problem <strong>is</strong><br />
resolved. The <strong>damper</strong> <strong>is</strong> at minimum position while <strong>reheat</strong> <strong>is</strong> <strong>active</strong>. When the thermostat calls for cooling,<br />
the <strong>reheat</strong> goes <strong>to</strong> zero and the <strong>damper</strong> <strong>open</strong>s as needed <strong>to</strong> sat<strong>is</strong>fy the space requirements. Note that the<br />
fan static pressure <strong>is</strong> maintained throughout the day.<br />
Normal <strong>VAV</strong>-<strong>box</strong> operation<br />
Examples of Abnormal Operation<br />
<strong>VAV</strong> <strong>box</strong>es are no<strong>to</strong>rious for having many different modes of failure. Below are two examples of what a<br />
trend log of abnormal operation might look like, but your own trend-log graph will probably have its own<br />
unique features.<br />
If your graph looks similar <strong>to</strong> one below then your system <strong>is</strong> not operating as it should and the problem <strong>is</strong><br />
unresolved. The <strong>reheat</strong> <strong>is</strong> energized at 50% once the <strong>damper</strong> r<strong>is</strong>es above minimum setpoint. Airflow from<br />
the AHU <strong>to</strong> the pressure-sensor location <strong>is</strong> not a problem since it can maintain static pressure. Inspect the<br />
static pressure at the <strong>VAV</strong> <strong>box</strong> locally <strong>to</strong> make sure it has adequate pressure. There may be a partially<br />
Produced by <strong>BetterBricks</strong>, the commercial initiative of the Northwest Energy Efficiency Alliance<br />
BOpTlsMstrPrb22.doc • 3