FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING & LOOSE EQUIPMENT<br />

SECTION INDEX<br />

<strong>Williams</strong>’ “High Head” Through-the-Pump 1500 Portable Foam System....J2<br />

<strong>Williams</strong>’ Pressure Reducing Valve (WPRV/3, 3P, 4 & 4P)..............................J3<br />

Tank Farm <strong>Fire</strong> Fighting Foam System...............................................................J4<br />

Jet Ratio Controllers.........................................................................................J5-J6<br />

95 gpm Liquid Eductor...........................................................................................J7<br />

Spectrum Inline Eductors......................................................................................J8<br />

Spectrum “Double Action” By-Pass Eductor ....................................................J9<br />

PKW Dry Chemical Manifold Typical Layouts................................................. J10<br />

Manifolds for Hydro-Chem Systems.............................................................. J11<br />

Typical Hose Lay For Hydro-Chem Trailer mount Systems...................... J12<br />

PRODUCTS 409-745-3232 J1<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

Product<br />

<strong>Williams</strong>’ “High Head” Through-the-Pump<br />

1500 Portable Foam System<br />

Description:<br />

The <strong>Williams</strong> High Head Through-the-Pump 1500 Portable Foam System was designed to<br />

turn any pumper into a <strong>foam</strong> producing device. This unit will proportion 3% <strong>foam</strong> solution up<br />

to 1500 GPM. It can work against hydrant pressure up to 50 PSI with only 150 PSI discharge<br />

pressure. This economical system is easy to use and is completely water driven; there are no<br />

pumps or parts to maintain. Can’t get the <strong>foam</strong> to the pump Not a problem! The WTTP was<br />

designed to proportion <strong>foam</strong> from remote locations.<br />

FEATURES:<br />

• Operates against 33% Pump Suction Pressure.<br />

(Example: Master Pressure @150 PSI, Suction Pressure @ 50 PSI)<br />

• Proportions Class “B” Foam up to 1500 GPM at 3%.<br />

• Proportions Class “B” Foam up to 750 GPM at 6%.<br />

• Positive Shut-Off on Metering Valve.<br />

• Requires no maintenance.<br />

• Portable.<br />

• Water Powered.<br />

• Remote Proportioning Capabilities.<br />

• Check Valve Prevents Water from “Back Flowing“<br />

into Concentrate Source.<br />

System Includes:<br />

• Base Unit with Jet Pump & Metering Valve.<br />

• 2.0” Clear Concentrate Pick-Up Hose.<br />

• 2.0” Valved Drum Stinger.<br />

ThunderStorm<br />

AFFF/ATC<br />

MATERIALS OF CONSTRUCTION:<br />

• Brass with Stainless Steel Trim.<br />

Notes:<br />

1. The following table is based on 150 psig operating pressure at the jet pump inlet.<br />

2. At 50 psi water pump inlet, maximum hose lay is 25 ft. of 3.0” hose.<br />

3. For drafting operations or pressure below 10 psi, use the 10 psi numbers shown.<br />

Maximum Hose Lay (ft) For Remote Proportioning Portable WATP 1500 System<br />

PUMP INLET PRESSURE<br />

Solution Rate<br />

10 PSI<br />

HOSE SIZE<br />

20 PSI<br />

HOSE SIZE<br />

30 PSI<br />

HOSE SIZE<br />

40 PSI<br />

HOSE SIZE<br />

1% 3% 6% 2.5” 3” 2.5” 3” 2.5” 3” 2.5” 3”<br />

30 12 850 1700 625 1250 400 775 200 325<br />

100 40 825 1675 600 1225 375 750 175 300<br />

400 160 80 800 1625 575 1175 350 725 150 275<br />

1000 400 200 750 1500 525 1050 325 650 125 250<br />

2000 750 375 650 1325 475 950 300 600 100 225<br />

4000 1500 750 525 1050 375 775 250 475 75 200<br />

PRODUCTS 409-745-3232 J2<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

Product:<br />

<strong>Williams</strong>’ Pressure Reducing Valve<br />

(WPRV/3, 3P, 4 & 4P)<br />

Description:<br />

Maintains constant pre-set inlet pressure for use in conjunction with the<br />

<strong>Williams</strong> “High Head” Through/Around The Pump (or comparable) <strong>foam</strong> systems.<br />

Allows any firewater pump to produce suction side <strong>foam</strong> at virtually ANY positive<br />

inlet pressure. As such, the WPRV eliminates need for operator intervention to<br />

adjust intake gate valves due to suction pressure fluctuations as a result of changes<br />

in pump discharge flow. Thus, the added burden of assuring a maximum pump intake<br />

pressure (based on pump discharge pressure) associated with traditional suction<br />

side <strong>foam</strong> systems simply goes away.<br />

Additional Applications:<br />

Got a CAFS or Balanced Pressure system The WPRV can provide reduced pump inlet pressures to allow increased engine/PTO speed to<br />

maintain higher compressor or <strong>foam</strong> pump output when operating with positive pump inlet pressures. Installed within a discharge line, the WPRV<br />

maintains a preset pressure for hand lines or ground monitors independent of higher pump discharge pressures.<br />

Features:<br />

3 Modes of Operation:<br />

1. AUTOMATIC – Controls pre-set pressure from 15-115 PSI<br />

2. OPEN – Full flow to rated capacity<br />

WPRV/3 — 500 GPM w/ 7 PSI drop<br />

WPRV/4 — 1500 GPM w/ 20 PSI drop<br />

3. CLOSED — Bubble tight shut off<br />

• NFPA 1901, 14-6 COMPLIANT — Exclusive WPRV pilot control also provides bubble tight shut off to comply with NFPA 1901, 19-3.6,<br />

TIA 99-1 preventing <strong>foam</strong> solution back flow into a potable (hydrant system) water supply<br />

• PRESSURE RATINGS — 230 PSI Max. — 20 PSI Min. (Prevents reducing hydrant system pressures below 20 PSI)<br />

• INLET/OUTLET — WPRV/3: 2.5” NST; WPRV/4: 5” Storz<br />

Options:<br />

WPRV/3 & 3P (Portable)<br />

• “In-Truck” installation with panel mount control valve, standard 2.5” (F)NST swivel inlet w/ strainer and bleeder port<br />

• 3” (F) NST inlet w/strainer/outlet<br />

• 4” Storz inlet w/strainer/outlet WPRV/4 & 4P (Portable)<br />

• “In-Truck” installation with panel mount control valve, standard 5” Storz inlet w/strainer, adjustable intake relief, bleeder<br />

port and mounting hardware<br />

• Inlet intake relief valve & bleeder (4P)<br />

• 4” Storz inlet w/strainer/outlet<br />

• 6” (F)NST swivel outlet for direct mounting to pump intakes<br />

• Inlet/outlet pressure gauges<br />

• Carrying handle<br />

• 5” LDH X 10’ Long with 5” Storz couplings (200 PSI operating pressure)<br />

Materials of Construction:<br />

• WPRV/3 & 3P – Epoxy coated cast iron w/brass and stainless steel trim<br />

• WPRV/4 & 4P – Epoxy coated & anodized aluminum w/brass and stainless steel trim<br />

PRODUCTS 409-745-3232 J3<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Tank Farm <strong>Fire</strong> Fighting Foam System<br />

Flow<br />

Rate<br />

Solution % Jet Size # of Jet<br />

lays<br />

“Old Style” 2 x 6 Gun JRCP Hose Lay Comparison<br />

2.0” Hose<br />

Lay (ft) Time (min)<br />

2.50” Hose<br />

Lay (ft) Time (min)<br />

3.0” Hose<br />

Lay (ft) Time (min)<br />

6,000 1 2 1 N/A N/A 350 1.0 750 2.8<br />

6,000 1 1.5 2 440 1.4 1,300 6.1 2,550 17.4<br />

6,000 3 2 3 N/A N/A 75 0.3 150 0.6<br />

Flow<br />

Rate<br />

Solution % Jet Size # of Jet<br />

lays<br />

Ambassador JRCP Hose Lay Comparison<br />

2.0” Hose<br />

Lay (ft) Time (min)<br />

2.50” Hose<br />

Lay (ft) Time (min)<br />

3.0” Hose<br />

Lay (ft) Time (min)<br />

6,000 1 2 1 N/A N/A 350 1.0 750 2.7<br />

6,000 1 1.5 2 434 1.3 1,250 6.0 2,550 17.2<br />

6,000 3 2 3 N/A N/A 150 0.5 300 1.2<br />

PRODUCTS 409-745-3232 J4<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

Product:<br />

Jet Ratio Controllers (Jet Pumps)<br />

Description:<br />

Utilizing a small amount of water, this high efficiency venturi-type<br />

device moves <strong>foam</strong> concentrate from a remote storage location to a<br />

matched Hydro-Foam nozzle. This all-hydraulic system dramatically<br />

simplifies and improves the logistics of moving the high quantities of <strong>foam</strong><br />

concentrate required to extinguish a large flammable liquid fire. Foam<br />

concentrate is delivered from the Jet Ratio Controller to a matched<br />

Hydro-Foam nozzle via fire hose. Depending on nozzle and hose size, as well as the percentage of <strong>foam</strong> mixed (1% or 3%), the distance<br />

between the <strong>foam</strong> supply and Hydro-Foam nozzle can be up to 2,500 feet.<br />

Jet Ratio Controllers are supplied in conjunction with matched Hydro-Foam nozzles. Foam concentrate inlet on matched nozzle can<br />

be provided with 8 ft. of reinforced clear plastic hose with PVC shut-off valve, and/or metering valve “stinger”. This configuration allows <strong>foam</strong><br />

concentrate to be drawn directly from a <strong>foam</strong> concentrate drum and then delivered efficiently to the nozzle via fire hose.<br />

Jet Ratio Controllers are provided with connections at three ports, designated as “inlet,” “discharge” and “suction.” Inlet (female swivel)<br />

and discharge (rigid male) has National Hose thread (NST, NH) connections with NPT (M) connection for the concentrate inlet port. Foam<br />

concentrate inlet is furnished with standard drum kit, which consists of flexible suction hose, rigid PVC “Stinger” pipe and shutoff valve. Jet<br />

Ratio Controller body is all brass construction. “H” series jet ratio controllers are available, on special order, for elevated nozzles, or other<br />

high back pressure applications.<br />

Typical Schematic<br />

ThunderStorm ®<br />

AFFF/ATC<br />

PRODUCTS 409-745-3232 J5<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

1.5”<br />

INLET<br />

TYPICAL SCHEMATIC<br />

ThunderStorm ®<br />

AFFF/ATC<br />

MODEL 3% Flow Match 1% DISCHARGE “A” SUCTION “B” LENGTH “C”<br />

1.5JP24 750 GPM 2000 gpm 1.5” 1.5” 12.375”<br />

1.5JP30 1000 GPM 2500 gpm 1.5” 1.5” 12.375”<br />

2.0JP60 2000 GPM 5000 gpm 2.5” 2” 15.5”<br />

NOTE: 6% APPLICATIONS AVAILABLE UPON REQUEST<br />

PRODUCTS 409-745-3232 J6<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose<br />

Equipment<br />

Product:<br />

95 gpm Liquid Eductor<br />

Description:<br />

The Elkhart 242-95 Eductor is a device used for educting a liquid concentrate<br />

solution into the water stream of 1-1/2” coupled fire hose lines.<br />

The Eductor is constructed of Armor-Lyte composite material with<br />

stainless steel components for resilience and durability. Armor-Lyte is<br />

impervious to the corrosion caused by high concentrate detergents, salt water and most chemicals.<br />

Each eductor comes equipped with a 1-1/2” “F” NH female swivel connector input, a 1-1/2” “M” NH male outlet and a 3/4” male Garden<br />

Hose Thread inlet for the concentrate pick-up hose.<br />

The 242-95 Eductor is factory calibrated for pump flow rates of 95gpm (356 lt/m). The Eductor comes complete with three different checkvalves<br />

for three different concentrate eduction rates. When attached, the Black checkvalve will educt at a 0.5% rate, the Purple checkvalve will<br />

educt at a 1% rate and the Green checkvalve is for educting at a 3% rate.<br />

To switch checkvalves on the eductor unit, gently grasp the checkvalve body with pliers or vise grips and unscrew. Carefully screw alternate<br />

checkvalve into eductor body, thread to “hand-tight”. There is no need to over tighten.<br />

The 242-95 Eductor can be used as either an “End-of-the-Line” or as a “Pump Mounted” System. The eductor is designed for a nominal<br />

operating pressure of between 75 and 150 psi. If <strong>proportioning</strong> 3%, the 242-95s are restricted to a maximum hose length of 150 feet between<br />

the eductor and nozzle. However, at ½% and 1% solution rates, the maximum hose lay with 1.50”ID fire hose goes to 200 feet when used with<br />

a 95+gpm nozzle.<br />

The Eductor comes complete with<br />

three different checkvalves for three different<br />

concentrate eduction rates.<br />

*Armor-Lyte is a registered trademark of<br />

<strong>Williams</strong> <strong>Fire</strong> and Hazard Control, Inc ® 120108<br />

PRODUCTS 409-745-3232 J7<br />

EMERGENCY 409-727-2347<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

Product:<br />

Spectrum Inline Eductors<br />

Description:<br />

Spectrum Inline Foam Eductors provide the simplest and most economical<br />

method of introducing a controlled flow of <strong>foam</strong> concentrate into<br />

a pressurized water stream. As opposed to “Hydro-Foam Technology”,<br />

(which is used in conjunction with master stream nozzles) these “Venturi-<br />

Type” <strong>foam</strong> proportioners are designed to be used in conjunction with a<br />

matched constant flow end-of-line device (nozzle), where adequate water<br />

pressure is available. Inline <strong>foam</strong> eductors are capable of operating at inlet<br />

pressures as low as 70 psi, but in most cases adequate residual fire fighting<br />

pressure at the nozzle requires that the eductor inlet pressure be at least 100 psi, or greater.<br />

Spectrum Inline Eductors are rated to flow 60, 95, or 125 gpm @ 150 psi inlet. Nominal flow rates at other inlet pressures are listed<br />

below. Eductor outlet pressure is approximately 65% of inlet pressure. Eductor components, including body, venturi jet and metering orifice<br />

are constructed of corrosion-resistant brass.<br />

Standard water inlet - NH (F) swivel. Foam solution discharge - NH (M). Complete with clear pvc concentrate pick-up hose with slotted<br />

brass “stinger”; 1% or 3% fixed orifice; ball check valve.<br />

RIGID<br />

Model<br />

Nominal<br />

Nominal<br />

Nominal<br />

Proportioning<br />

Flow<br />

@100 PSI<br />

Flow<br />

@125 PSI<br />

Flow<br />

@150 PSI<br />

1.5” -60 gpm 49 gpm 55 gpm 60 gpm 1% or 3%<br />

1.5” -95 gpm 78 gpm 87 gpm 95 gpm 1% or 3%<br />

1.5” -125 gpm 102 gpm 114 gpm 125 gpm 1% or 3%<br />

PRODUCTS 409-745-3232 J8<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Foam Proportioning & Loose Equipment<br />

Product:<br />

Spectrum “Double Action” By-Pass Eductor<br />

Description:<br />

The Spectrum “Double Action” By-Pass Foam Eductor provides the versatility<br />

of a full-flow water by-pass <strong>foam</strong> proportioner in conjunction with the simplicity<br />

and reduced weight of a standard, single waterway inline eductor. This specialty<br />

by-pass type <strong>foam</strong> venturi transforms any 1.5” handline into a <strong>foam</strong> <strong>proportioning</strong><br />

system. Three flow rates are available: 60 gpm; 95 gpm; 125 gpm. Flows are based<br />

on 200 psi inlet pressure. The eductor will proportion <strong>foam</strong> at lower inlet pressures,<br />

provided that discharge pressure is not excessive. Positive shut-off metering allows <strong>foam</strong> <strong>proportioning</strong> to be adjusted and set from 0.5%<br />

to 3%. Body is constructed of durable 6061 - T6 (black) anodized aluminum.<br />

In operation, <strong>foam</strong> is produced by simply installing the system in the hose line, emersing the concentrate pickup tube into an adequate supply<br />

of ThunderStorm ® AFFF <strong>foam</strong> concentrate and adjusting the eductor to the “<strong>foam</strong>” position. When <strong>foam</strong> application is no longer needed,<br />

there is no need to remove the eductor for application of water only. This conversion is easily accomplished by simply rotating the <strong>foam</strong> control<br />

sleeve to the “water” setting. The result is an enlarged waterway which allows for water only application.<br />

Other Features Include:<br />

• Positive Shutoff Metering Valve.<br />

• Integral Concentrate Ball Check Valve.<br />

• Clear Plastic Concentrate Pick Up Hose with Rigid “Stinger”.<br />

• Lightweight, Compact Design (4 lbs., nominal).<br />

Double<br />

Action<br />

Eductor<br />

Nominal Flow<br />

@200 PSi<br />

K-Factor Inlet Discharge Proportioning<br />

Range<br />

60 gpm 60 gpm 4.25 1.5 NH (F) Swivel 1.5” NH (M) 0.5%-6%<br />

95 gpm 95 gpm 6.72 1.5 NH (F) Swivel 1.5” NH (M) 0.5%-6%<br />

125 gpm 125 gpm 8.84 1.5 NH (F) Swivel 1.5” NH (M) 0.5%-6%<br />

PRODUCTS 409-745-3232 J9<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

“PKW” Dry Chemical Delivery Manifold — Typical Layouts<br />

PRODUCTS 409-745-3232 J10<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Hydro-Chem Technology<br />

Manifolds for Hydro-Chem Systems<br />

Dry Chemical Manifiold - 4 Inlets<br />

Dry Chemical Manifiold - 6 Inlets<br />

PRODUCTS 409-745-3232 J11<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM


FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

FOAM PROPORTIONING / LOOSE EQUIPMENT<br />

Hydro-Chem Technology<br />

Typical Hose Lay For Hydro-Chem Trailer mount Systems<br />

1000 GPM Hose Layout<br />

Patriot II Hose Layout<br />

PRODUCTS 409-745-3232 J12<br />

EMERGENCY 409-727-2347<br />

120108<br />

WWW.WILLIAMSFIRE.COM