INSTALLATION INSTRUCTIONS DUCTED CCC<br />

4. AIR DISTRIBUTION SYSTEM<br />

SIZING & DESIGN<br />

The Installer of this air conditioner/heat pump system must design the air distribution system for their particular application. Several<br />

requirements for this system MUST be met for the air conditioner/heat pump to operate properly. These requirements are as<br />

follows:<br />

A. The duct material must meet or exceed any agency or RVIA Standard that may be in existence at the time the RV is produced.<br />

B. All discharge air ducts must be properly insulated to prevent condensation from forming on their surfaces or adjacent surfaces<br />

during operation of the air conditioner/heat pump. This insulation must be R-7 minimum.<br />

C. Ducts and their joints must be sealed to prevent condensation from forming on adjacent surfaces during operation of the air<br />

conditioner/heat pump.<br />

D. Return air openings must have 40 square inches minimum free area including the filter.<br />

E. Return air to the air conditioner/heat pump must be filtered to prevent dirt accumulation on air conditioner/heat pump cooling<br />

surface.<br />

! CAUTION<br />

It is the responsibility of the installer to insure<br />

the ductwork will not collapse or bend<br />

during and after the installation. <strong>Dometic</strong><br />

Corporation will not be liable for roof structural<br />

or ceiling damage due to improperly insulated,<br />

sealed or collapsed ductwork.<br />

AIR DISTRIBUTION<br />

DUCT SIZING & DESIGN CHART<br />

Return <strong>Air</strong> Cover Model 3105007.XXX 3308120.XXX<br />

3105935.XXX<br />

Genesis <strong>Air</strong> Filtration System<br />

Roof Cavity Depth 2.0 In. Min. - 5-1/2 In. Max. 2.0 In. Min. - 5-1/2 In. Max.<br />

Duct Cross Sectional Area 21.0 Sq. In. Min. 32.0 Sq. In. Min.<br />

Duct Size<br />

Depth 1-1/2 In. Min. - 2-1/2 In. Max. 2.0 In. Min. - 2-1/2 In. Max.<br />

Width 7.0 In. Min. - 10.0 In. Max. 8.0 In. Min. - 10.0 In. Max.<br />

Total Duct Length 15.0 Ft. Min. - 40.0 Ft. Max. 15.0 Ft. Min. - 40.0 Ft. Max.<br />

Duct Length (short run) 1/3 Total Duct Length 1/3 Total Duct Length<br />

Register Requirements<br />

Number Required Per Run 4 Min. 4 Min.<br />

Register Free <strong>Air</strong> Area 14.0 Sq. In. 14.0 Sq. In.<br />

Distance From Duct End 5.0 In. Min. - 8.0 In. Max. 5.0 In. Min. - 8.0 In. Max.<br />

Distance From Elbow 15.0 In. 15.0 In.<br />

Total System Static <strong>Air</strong> Pressure 0.55 - 0.90 In. W.C. 579 Series 0.55 - 0.90 In. W.C. 579 Series<br />

Blower at High Speed, 0.40 - 1.10 In. W.C. 590, 591, 595 Series 0.40 - 1.10 In. W.C. 590, 591, 595 Series<br />

Filter & Grill In Place 0.12 - 0.65 In. W.C. 600, 630 Series 0.12 - 0.65 In. W.C. 600, 630 Series<br />

Note: Duct sizes listed are inside dimensions.<br />

6