CONTA-<strong>ELECTRONICS</strong><br />

Potentiometric converter units CML<br />

CML-POT-UI<br />

· Mount on TS 35<br />

· Compact design, width: 6.2mm<br />

· Screw-clamp connection<br />

· Conversion of potentiometer signals into standard<br />

analog signals<br />

· Suitable for 1 k to 20 k Ω potentiometer<br />

· Output: 0 to 10 V, 0 to 20 mA, or 4 to 20 mA<br />

· Output signal is adjustable via DIP switch<br />

· OFFSET and SPAN setting is always accessible<br />

Circuit diagram<br />

Type<br />

Cat. no./Qty. p.pck.<br />

Size (L x W x H) with TS 35 x 7.5<br />

Weight<br />

General information<br />

DIN-VDE specifications<br />

Electro-magnetic compatibility<br />

Protection class<br />

Operating temperature<br />

Connection type<br />

Insulation stripping length<br />

Conductor cross-section<br />

Screw-clamp / tension-spring connection<br />

Conversion error<br />

Temperature coefficient<br />

Frequency limit (- 3dB)<br />

Power supply<br />

Input data<br />

Potentiometer<br />

Minimal use of potentiometer<br />

for OFFSET/SPAN adjustment<br />

Remarks:<br />

Output data<br />

Voltage of output signal<br />

Max. voltage of output signal<br />

Load resistance<br />

Current of outputs (adjustable via DIP switch)<br />

Max. output current<br />

Load resistance<br />

Offset<br />

Remarks:<br />

CML-POT-UI<br />

15641.2/1<br />

93.1 x 6.2 x 102.5 mm<br />

66 g<br />

DIN EN 50178:1987; DIN VDE 0110 pollution degree 2, overvoltage category III<br />

CE compliant<br />

IP 20<br />

-20 to +55°C<br />

Screw-clamp/tension-spring connection<br />

12mm/8mm<br />

0.2-2.5mm 2<br />

AWG 22-14<br />

< 0.2% of end value<br />

< 0.02%/K<br />

10 Hz<br />

24 V DC -15% +10%/40 mA<br />

0 to 1 kΩ to 0 to 20 kΩ<br />

60%<br />

first adjust offset, then span<br />

0 to 10 V (default)<br />

approx. 11 V<br />

> 1 kΩ<br />

0 to 20 or 4 to 20 mA (default is 4 to 20 mA)<br />

approx. 22 mA<br />

< 500 Ω<br />

< 10 mV/20 mA<br />

when the current and voltage outputs are used simultaneously, the load resistance must be<br />

> 10 kΩ on the voltage output.<br />