www.schneider-electric.us<br />
Enclosed Starters<br />
TeSys ® D in Metal Enclosures<br />
Refer to Catalog 8502CT9901<br />
TeSys D enclosed full voltage starters are available in Type 1 and Type 12/3R enclosures through 50 hp at 460 V. The<br />
enclosed D-line accepts standard D-Line accessories and all Insta-Kits control units and control power transformer<br />
kits. Standard capacity control power transformers with built-in fuse block can be installed in the standard enclosure.<br />
For extra capacity, please refer to your local distributor or nearest Square D/Schneider Electric sales office.<br />
Table 18.69: Enclosed Full Voltage Non-reversing Starters<br />
Max. Horsepower Ratings (AC3)<br />
1 Phase 3 Phase<br />
Auxiliary Contacts Current Rating Catalog Number<br />
Catalog Number<br />
of Contactor<br />
$ Price<br />
$ Price<br />
115 230 200 V 230 V 460 V 575V N.O. N.C. Type 1 Type 12/3R<br />
0.333 1 2 2 5 7.5 1 1 9 LE1D093A62••••• 109. LE1D093A72••••• 175.<br />
0.5 2 3 3 7.5 10 1 1 12 LE1D123A62••••• 137. LE1D123A72••••• 202.<br />
1 3 5 5 10 15 1 1 18 LE1D183A62••••• 153. LE1D183A72••••• 219.<br />
2 3 5 7.5 15 20 1 1 25 LE1D253A62••••• 170. LE1D253A72••••• 235.<br />
2 5 7.5 10 20 25 1 1 32 LE1D323A62••••• 191. LE1D323A72••••• 245.<br />
3 5 10 10 30 30 1 1 40 LE1D403A62••••• 273. LE1D403A72••••• 393.<br />
3 7.5 12 15 40 40 1 1 50 LE1D503A62••••• 300. LE1D503A72••••• 420.<br />
5 10 20 20 40 50 1 1 65 LE1D653A62••••• 393. LE1D653A72••••• 514.<br />
7.5 15 30 30 60 60 1 1 80 LE1D803A62••••• 473. LE1D803A72••••• 610.<br />
Table 18.70: Enclosed Full Voltage Reversing Starters<br />
Max. Horsepower Ratings (AC3) 3 Phase<br />
Auxiliary Contacts On Each<br />
Contactor<br />
Current Rating Catalog Number<br />
Catalog Number<br />
of Contactor<br />
$ Price<br />
200V 230 V 460 V 575 V N.O. N.C. Type 1 Type 12/3R<br />
$ Price<br />
2 2 5 7.5 1 1 9 LE2D093A62••••• 305. LE2D093A72••••• 382.<br />
3 3 7.5 10 1 1 12 LE2D123A62••••• 355. LE2D123A72••••• 453.<br />
5 5 10 15 1 1 18 LE2D183A62••••• 385. LE2D183A72••••• 483.<br />
5 7.5 15 20 1 1 25 LE2D253A62••••• 415. LE2D253A72••••• 513.<br />
7.5 10 20 25 1 1 32 LE2D323A62••••• 464. LE2D323A72••••• 573.<br />
10 10 30 30 1 1 40 LE2D403A62••••• 655. LE2D403A72••••• 819.<br />
12 15 40 40 1 1 50 LE2D503A62••••• 710. LE2D503A72••••• 874.<br />
20 20 40 50 1 1 65 LE2D653A62••••• 900. LE2D653A72••••• 1030.<br />
30 30 60 60 1 1 80 LE2D803A62••••• 1248. LE2D803A72••••• 1412.<br />
Table 18.71: Catalog Number Nomenclature<br />
Catalog Number Example:<br />
Base Catalog Number<br />
Wiring Method<br />
Control Power Transformer f<br />
Contactor/Starter Coil Voltage g<br />
Coil Frequency h<br />
Overload Relay Type j<br />
Overload Relay Range i<br />
fControl Power Transformer<br />
Add price from page 18-23. Select letter for primary<br />
voltage of CPT:<br />
Voltage No Transformer used 208 240 480 600<br />
Code O a L M T X<br />
a Letter O, not zero.<br />
Note: If control transformer is used, the only options available are 24 or 120<br />
volts as the secondary of the transformer. Also, DC voltages are not<br />
available when control power transformer is used.<br />
gContactor/Starter Coil Voltage<br />
Select coil voltage from table:<br />
Voltage 24 120 208 240 480 600<br />
AC B G L U T X<br />
DC B — — — — —<br />
hCoil Frequency<br />
Select:<br />
7 = dual frequency coils (50/60 Hz.)<br />
6 = 60 Hz.<br />
D=DC<br />
Note: For 9 to 65 A contactors, only dual frequency coils are available; 80<br />
A contactors, the 24 V to 240 V coils are dual frequency only (50/60<br />
Hz.). The 480 V to 600 V coils are 60 Hz. only. See catalog for other<br />
restrictions.<br />
jOverload relay type<br />
LE1D093A62 O G 7 1 07<br />
iOverload Relay Range<br />
Select code from the below:<br />
b<br />
c<br />
Note:<br />
Code<br />
Range<br />
For use on<br />
Contactors<br />
$ Price Adder<br />
01 0.1–0.16 D09–D32b 60.<br />
02 0.16–0.25 D09–D32b 60.<br />
03 0.25–0.40 D09–D32b 60.<br />
04 0.40–0.63 D09–D32b 60.<br />
05 0.63–1.0 D09–D32b 60.<br />
06 1.0–1.6 D09–D32b 60.<br />
07 1.6–2.5 D09–D32b 60.<br />
08 2.5–4 D09–D32 60.<br />
10 4–6 D09–D32 60.<br />
12 5.5–8 D09–D32 60.<br />
13 9–13 D40, D50, D65 107.<br />
14 7–10 D09–D32 62.<br />
16 9–13 D12–D32 62.<br />
18 12–18 D40, D50, D65 107.<br />
21 12–18 D18–D32 62.<br />
16–24 D25–D32b 62.<br />
22<br />
17–25 D25–D32c 62.<br />
17–25 D80 107.<br />
25 17–25 D40, D50, D65 107.<br />
30 23-28 D25–D32c 73.<br />
32 23–32 D25–D32 73.<br />
32 23–32 D40, D50, D65 107.<br />
40 30–40 D40, D50, D65 107.<br />
50 37–50 D40, D50, D65 107.<br />
53 30–38 D80 107.<br />
55 30–40 D80 107.<br />
57 37–50 D80 107.<br />
59 48–65 D80 107.<br />
61 55–70 D65–D80 107.<br />
63 63–80 D65–D80 107.<br />
65 48–65 D40, D50, D65 107.<br />
Available for Class 10 only.<br />
Available for Class 20 only.<br />
If no overload relay is required, leave this portion of the catalog blank.<br />
Add appropriate Price Adder to the base price of the starter.<br />
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 18-48<br />
IEC CONTACTORS AND<br />
18 STARTERS<br />
Select:<br />
0 = No overload relay<br />
1 = Class 10 Trip<br />
2 = Class 20 Trip<br />
© 2009 Schneider Electric<br />