25.01.2015 Views

Download MEW E101 April 2013 (pdf, 280kb) - NSW Public Works

Download MEW E101 April 2013 (pdf, 280kb) - NSW Public Works

Download MEW E101 April 2013 (pdf, 280kb) - NSW Public Works

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Part 1 - Installation<br />

A separate MEN system for each building shall be used except where an earthing<br />

conductor is indicated to be run with the submain to that building.<br />

Metallic pipes used for other services, such as gas, water, sprinkler systems, etc., shall<br />

be considered as unavoidably in contact with metallic enclosures of electrical equipment<br />

and shall be effectively bonded to the earthing system.<br />

107.2 Earthing Conductors for Underground Cables<br />

Earthing conductors other than the copper sheathing of MIMS cables shall be copper<br />

stranded conductors sized as per AS 3000, protected by a green-yellow insulation and<br />

installed as follows:<br />

(a) Separate earthing conductors for TPI conductors in conduit.<br />

(c) Separate earthing conductors attached to the cable at 1000 intervals.<br />

(c) Earthing conductors laid up with the cable.<br />

107.3 Earth Electrodes<br />

Earth electrodes shall consist of copper, stainless steel or copper sheathed rods not less<br />

than 16 diameter driven to a depth of not less than 2400 to reach the permanent<br />

moisture level. Unless disallowed by the Supply Authority, the indicated footing in each<br />

building shall be used as an electrode in addition to the above. The earthing conductor<br />

shall be connected to the reinforcing steel of the indicated footing and the driven<br />

electrode. Each electrode shall generally be installed in an earthing pit similar to<br />

"Polycrete" PEP 22. Each pit shall have a reinforced concrete surround minimum 250<br />

wide and 200 deep complete with cable markers.<br />

108 CONDUITS, FITTINGS AND JOINTS<br />

108.1 Generally<br />

Conduits and fittings shall comply with either AS 2052 "Metallic conduits and fittings" or<br />

AS 2053 "Non Metallic conduits and fittings". Conduits smaller than 20 dia. shall not be<br />

used except for fire alarm systems where 16 dia. will be accepted.<br />

Conduits shall be in long lengths, straight, smooth and free from rags, burrs and sharp<br />

edges. Off cuts shall not be used to fabricate long lengths of conduit. Conduits shall be<br />

set wherever possible to minimise the number of joints.<br />

Bends shall be of large radius and shall be formed with approved formers. Correctly<br />

sized springs shall be used to form bends in UPVC conduits. Conduits manipulated or<br />

bent must maintain true effective diameter and shape at all parts of the bend. Conduit<br />

sets distorted or showing evidence of kinks, wrinkles, flats or having been heated will not<br />

be accepted. Wherever possible, UPVC Conduits bends should be preformed by the<br />

manufacturer.<br />

Conduits shall be colour coded in accordance with Clause 602 of <strong>MEW</strong> <strong>E101</strong>.<br />

Saddles supporting conduits shall be effectively secured to the surface on which they<br />

run. Saddles shall be a proprietary brand installed as supplied.<br />

Conduit systems, including conduits and pipes used to convey cables into buildings,<br />

shall be sealed to prevent water entry.<br />

The number of cables including earth wires that may be enclosed in any one conduit or<br />

pipe shall not exceed that recommended as a guide in AS 3000.<br />

All conduits exposed to weather shall be painted with a light coloured paint designed for<br />

the purpose.<br />

108.2 Heavy Duty UPVC Conduits to AS 2053 (HD-UPVC)<br />

Page 14<br />

<strong>MEW</strong> <strong>E101</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!