Part 2 - Switchboards and Associated Equipment<br />
• Disconnection of all live parts that can be unintentionally touched after<br />
the door has been opened. (Meet clause 7.4.2.2.3 b) of AS/NZS<br />
3439.1:2002.)<br />
• Shielding all live parts in such a manner that they cannot be<br />
unintentionally touched when the door is opened or the cover is<br />
removed. (Meet clause 7.4.2.2.3 c) of AS/NZS 3439.1:2002.)<br />
For Common Control Compartments:<br />
• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />
clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.)<br />
• Shielding all live parts in such a manner that they cannot be<br />
unintentionally touched when the door is opened or the cover is<br />
removed. (Meet clause 7.4.2.2.3 c) of AS/NZS 3439.1:2002.)<br />
For Distribution Compartments with one main protective device plus a<br />
number of subcircuit protective devices:<br />
• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />
clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.) for the compartment door<br />
and for the escutcheon.<br />
202.1.7 Custom-built Assembly Type “DTPLUS”<br />
The following details shall apply to Custom-built Assemblies Type “DTPLUS”:<br />
(a) A Type “DTPLUS” assembly shall be a stationary “cubicle-type assembly” or<br />
‘multi-cubicle-type assembly” as defined in AS/NZS 3439.1:2002.<br />
(b) A Type “DTPLUS” assembly shall comply with AS/NZS 3439.1:2002 as defined by<br />
the following requirements:<br />
(i) Form of separation shall be Form 4b.<br />
(ii) The degree of protection after installation in accordance with the<br />
manufacturer’s instructions shall be IP51 for indoor installation and IP56 for<br />
outdoor installation.<br />
(iii) Assemblies shall be front access with top and/or bottom cable entry.<br />
(iv) Assemblies shall be floor mounted.<br />
(v) For outdoor switchboards containing busbars, pollution degree 3 shall apply<br />
at locations further than 1km in a direct line from the coast or at altitudes<br />
below 1000 metres. Otherwise, pollution degree 4 shall apply.<br />
For indoor switchboards, pollution degree 3 shall apply.<br />
(vi) The following safety measures against direct contact shall apply:<br />
For Main Incoming Supply Compartments, Motor Starter Compartments and<br />
Distribution Feeder Compartments with one feeder in the Distribution Feeder<br />
Compartment:<br />
• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />
clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.)<br />
• Disconnection of all live parts that can be unintentionally touched after<br />
the door has been opened. (Meet clause 7.4.2.2.3 b) of AS/NZS<br />
3439.1:2002.)<br />
• Shielding all live parts in such a manner that they cannot be<br />
unintentionally touched when the door is opened or the cover is<br />
removed. (Meet clause 7.4.2.2.3 c) of AS/NZS 3439.1:2002.)<br />
Page 32<br />
<strong>MEW</strong> <strong>E101</strong>