<strong>Residential</strong> <strong>Multipurpose</strong> <strong>Fire</strong> <strong>Sprinkler</strong> <strong>Systems</strong><br />

<strong>Multipurpose</strong> fire sprinkler systems shall be installed in one and two family residences per the following:<br />

I. General<br />

1. Contractors shall demonstrate compliance with State <strong>Sprinkler</strong> license requirements for NFPA 13D systems.<br />

Note: Homeowners are exempt from State licensing installation requirements. However, the designer <strong>of</strong> the<br />

system and plans are required to be a licensed pr<strong>of</strong>essional.<br />

2. The system shall meet all manufactures requirements for installation.<br />

3. <strong>Fire</strong> sprinkler plans will be reviewed and approved by East Pierce <strong>Fire</strong> and Rescue.<br />

4. System monitoring is not required on one and two family homes (See II g).<br />

5. Developments with model home(s) will have the initial review performed on the models only. Inspection will be<br />

required as below on all units.<br />

6. <strong>Sprinkler</strong> drops shall be limited to 36” maximum.<br />

7. Water treatment/filtration systems shall have an automatic bypass as required by NFPA 13D.<br />

8. <strong>Sprinkler</strong> systems shall be designed to IRC Appendix R or NFPA 13D.<br />

9. <strong>Sprinkler</strong>s shall be separated from heat sources (fireplace, wood stove, oven, kitchen range top, et cetera) as<br />

required by the sprinkler manufacturer's installation instructions. Distances shall be measured in a straight line from<br />

the nearest edge <strong>of</strong> the heat source to the nearest edge <strong>of</strong> the sprinkler<br />

10. <strong>Sprinkler</strong> piping shall comply with all requirements for cold water distribution piping. The sprinkler piping shall<br />

connect to and be a part <strong>of</strong> the cold water distribution piping system.<br />

11. Nonmetallic pipe and tubing, such as CPVC and PEX, shall be listed for use in residential fire sprinkler systems.<br />

12. Piping shall be protected from freezing. Where sprinklers are required in areas that are subject to freezing, dryside-wall<br />

or dry-pendent sprinklers extending from a nonfreezing area into a freezing area shall be installed.<br />

13. The area <strong>of</strong> coverage <strong>of</strong> a single sprinkler shall not exceed 400 square feet and shall be based on the sprinkler<br />

listing and the sprinkler manufacturer's installation instructions.<br />

C:\JH\2011\Handouts 1 rev. 2/14/11


14. <strong>Sprinkler</strong> discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the<br />

obstructed area. <strong>Sprinkler</strong> separation from obstructions shall comply with the minimum distances specified in the<br />

sprinkler manufacturer's instructions.<br />

15. Pendent sprinklers within 3 feet <strong>of</strong> the center <strong>of</strong> a ceiling fan, surface-mounted ceiling luminaire or similar object<br />

shall be considered to be obstructed, and additional sprinklers shall be installed.<br />

16. Sidewall sprinklers within 5 feet <strong>of</strong> the center <strong>of</strong> a ceiling fan, surface-mounted ceiling luminaire or similar object<br />

shall be considered to be obstructed, and additional sprinklers shall be installed.<br />

17. A means to drain the sprinkler system shall be provided on the system side <strong>of</strong> the water distribution shut<strong>of</strong>f valve.<br />

18. <strong>Sprinkler</strong>s shall be installed to protect all areas <strong>of</strong> a dwelling unit.<br />

Exceptions:<br />

a. Attics, crawl spaces and normally unoccupied concealed spaces that do not contain fuel-fired appliances do not<br />

require sprinklers. In attics, crawl spaces and normally unoccupied concealed spaces that contain fuel-fired<br />

equipment, a sprinkler shall be installed above the equipment; however, sprinklers shall not be required in the<br />

remainder <strong>of</strong> the space.<br />

b. Clothes closets, linen closets and pantries not exceeding 24 square feet in area, with the smallest dimension not<br />

greater than 3 feet and having wall and ceiling surfaces <strong>of</strong> gypsum board.<br />

c. Bathrooms not more than 55 square feet in area.<br />

d. Carports; exterior porches; unheated entry areas, such as mud rooms, that are adjacent to an exterior door; and<br />

similar areas.<br />

e. Garages without warm ceilings (room above) need only have one sprinkler covering the garage/house door.<br />

II. Plan submittal.<br />

1. Provide floor plan scaled drawing (1/4” = 1’) showing all <strong>of</strong> the following:<br />

a. Size/type <strong>of</strong> sprinkler heads.<br />

b. Location/coverage <strong>of</strong> sprinkler heads.<br />

c. Size/type <strong>of</strong> sprinkler piping.<br />

d. Complete isometric diagram <strong>of</strong> water piping system including sprinkler heads.<br />

e. Drainage fixture units <strong>of</strong> all fixtures including sprinkler heads.<br />

f. Type and location <strong>of</strong> all valves check valves, shut<strong>of</strong>f valves, et cetera.<br />

Note: Backflow prevention devices are not required on this type <strong>of</strong> system. Stand alone systems are<br />

not allowed per BLMC 13.04.110 M #1<br />

g. Exterior bell or horn and strobe on address side and audibility on the inside (smoke alarms).<br />

h. Size/type <strong>of</strong> sprinkler heads.<br />

i. Two family units require a separate meter for each unit (Each sprinkler system shall not serve more than one<br />

dwelling). No exceptions.<br />

C:\JH\2011\Handouts 2 rev. 2/14/11


j. All products used for the fire sprinkler system shall be new and listed as required by NFPA 13D and WAC 51-<br />

51-60105<br />

k. The fire sprinkler system shall be installed per NFPA 13 D and WAC. 51-51-60105<br />

l. Minimum <strong>of</strong> 1” meter and 1 ½” service line to the building is required (see exception to #3 in common<br />

questions below).<br />

III. Rough Inspection.<br />

1. All system components shall be in place at the time <strong>of</strong> rough pipe inspection.<br />

2. Tenting insulation is required for all fire sprinkler piping that is installed in the attic space.<br />

3. Bucket test will be required for the two most remote heads flowing at the same time.<br />

Note: No part <strong>of</strong> the system shall be covered until it has been inspected and approved.<br />

IV. Final Inspection.<br />

1. The system shall be in service at the time <strong>of</strong> final inspection.<br />

2. All heads and escutcheons shall be in place.<br />

3. On completion <strong>of</strong> the final, all handles shall be removed or locked in place.<br />

Exception: Monitored systems.<br />

4. A warning sign, with minimum ¼” letters, shall be affixed adjacent to the main shut<strong>of</strong>f valve and shall state the<br />

following:<br />

“Warning: The water system for this home supplies fire sprinklers that require certain flows and<br />

pressures to fight a fire. Devices that restrict the flow or decrease the pressure or automatically shut <strong>of</strong>f<br />

the water to the fire sprinkler system, such as water s<strong>of</strong>teners, filtration systems, and automatic shut<strong>of</strong>f<br />

valves, shall not be added to this system without review <strong>of</strong> the fire sprinkler system by a fire protection<br />

specialist.”<br />

DO NOT REMOVE THIS SIGN<br />

V. Common Questions for <strong>Residential</strong> <strong>Sprinkler</strong> <strong>Systems</strong>.<br />

Note: If you have a question you believe would benefit others, and would like it added to this list please email them to<br />

the Building Official Jerry E Hight at hightj@ci.bonney-lake.wa.us.<br />

1. Are we required to have the residential sprinkler system monitored<br />

No. Instead, we require a bell or horn and strobe on address side <strong>of</strong> your home (see item II g above). The reason is<br />

to make sure if the system activates and you are not home, someone will see, or hear the alarm and alert<br />

authorities.<br />

2. Are we required to install a backflow device on the residential sprinkler system<br />

No. The reason is that you are installing a complete flow through system. Therefore, the domestic water used for<br />

your home also flows through the sprinkler system.<br />

3. What is the meter size that we are required to install for a residential sprinkler system<br />

C:\JH\2011\Handouts 3 rev. 2/14/11


A minimum <strong>of</strong> one inch (1”) meter (or larger depending on fire flow demands) is required and a one and one half<br />

inch (1 ½”) service line is required from the meter to the home. [The one inch meter cost (SDC fee) has been<br />

reduced to the same cost as a five eights (5/8”) or a three quarter inch (3/4”) meter. The reason the city did this<br />

was to provide the water needed and to provide a price reduction ($10k) to allow the installation <strong>of</strong> a residential<br />

sprinkler system.]<br />

Exception:<br />

A. Existing 5/8” meters [installed prior to July 12, 2010] may be used if the sprinkler system is designed<br />

for a 5/8” meter. Please note the system can not have a pump and tank design as it would involve a<br />

prohibited backflow preventer. When the fire flow test occurs after installation, it will be based on two<br />

sprinkler heads operating at the same time. However, if after installation the flow test does not pass, then<br />

a 1” or larger meter will need to be installed.<br />

B. A pump and tank system may be allowed with prior approval if all <strong>of</strong> the following condition are met:<br />

1. The water system is provided from a well on private property.<br />

2. The tank must be a self contained nonsiphonable refillable tank.<br />

3. The tank must be designed for a minimum <strong>of</strong> ten (10) minutes <strong>of</strong> fire flow based on hydraulic<br />

calculations for two heads.<br />

4. The system must be designed to IRC Appendix R or NFPA 13D<br />

4. If my existing meter is too small, will I have to replace it with a larger meter If so who pays for it<br />

Meter set installation or replacement is the responsibility <strong>of</strong> the permitee. Prior to any work the permitee is to<br />

contact the Community Development Engineer for inspection and approval. Once the meter set has been installed<br />

and approved, contact the Public Works Department to request installation <strong>of</strong> the water meter. Details for the<br />

meter set are available online through the <strong>City</strong> <strong>of</strong> <strong>Bonney</strong> <strong>Lake</strong> website at http://www.ci.bonney-lake.wa.us/<br />

Note: All meters and meter sets provided and installed on water service connections shall be and remain<br />

the property <strong>of</strong> the city and shall be removed only by the city.<br />

5. If I share a main supply (1” tap <strong>of</strong>f <strong>of</strong> the street main) with my neighbor (two meters being supplied by one 1”<br />

water main tap) will it be sufficient to supply both houses<br />

No. Depending on the flow requirements to your house you may need to install a new water main tap and a new<br />

service line to the meter splitters. All new building supply lines from the water meter to the house have to be a<br />

minimum <strong>of</strong> one and one-half inch (1 ½”).<br />

6. Does a new town house or duplex require multiple water meters<br />

Yes. Each duplex and townhouse style building unit will have a separate water meter and service for each living<br />

unit. There shall be only one water meter installed for each building housing multiple residential units.<br />

7. Can there be dead ends in the residential sprinkler system piping<br />

Dead ends are limited to 36”. Your dead ends should be limited because you are installing a “loop system”. We<br />

typically do not allow any dead ends unless they are unavoidable. <strong>Sprinkler</strong> systems need to meet the cities’<br />

potable water requirements. The reason is to have the water circulate through all <strong>of</strong> the piping so there isn’t any<br />

water contamination. You are drinking the same water that flows through your domestic water system and<br />

sprinkler system.<br />

8. Can we use the smoke detectors in the home as a form <strong>of</strong> notification <strong>of</strong> fire sprinkler system activation<br />

C:\JH\2011\Handouts 4 rev. 2/14/11


Yes. This is in addition to the exterior bell or horn and strobe (see II g above).<br />

9. Do all the sprinkler heads go <strong>of</strong>f if there was a fire in my home<br />

Typically no. Most fires are contained by only using one or two heads to control the fire. The sprinkler heads are<br />

designed to respond quickly. In doing so, the water usage is reduced to the area <strong>of</strong> the fire.<br />

10. I’m in the city but receiving water from Valley Water District. What is my standard for water service for fire<br />

flow<br />

Valley Water District implements the minimum provisions <strong>of</strong> the <strong>Bonney</strong> <strong>Lake</strong> Development Policies and Public<br />

Works Design Standards while operating within the city limits. Although these standards are minimum you may<br />

want to contact Valley Water District for provisions that they may apply to your project that may be above and<br />

beyond the city’s standards.<br />

11. If I remodel my house or have an addition installed will I have to install fire sprinklers<br />

Yes. If your remodel and or addition exceeds 50% <strong>of</strong> the market value <strong>of</strong> your house prior to any work being done<br />

you will have to add fire sprinklers. This is defined as a “Substantial Remodel”. You will be required to install a<br />

1” meter and 1 ½” building service line between the meter and the house for the new sprinkler system as required<br />

for a new home.<br />

If you have any questions please contact:<br />

Barry M Barquest<br />

Assistant Chief-<strong>Fire</strong> Marshal<br />

Certified Health and Safety Officer<br />

East Pierce <strong>Fire</strong> and Rescue<br />

18421 Sumner -Buckley HWY E Suite F<br />

<strong>Bonney</strong> <strong>Lake</strong>, WA. 98391<br />

bbarquest@eastpiercefire.org<br />

253-863-1800<br />

C:\JH\2011\Handouts 5 rev. 2/14/11