<strong>NEBB</strong> S & V PROCEDURAL STANDARDS SECTION 4<br />
STANDARDS FOR INSTRUMENTATION<br />
AND CALIBRATION<br />
4.2 RANGE AND ACCURACY<br />
Calibration requirements for each instrument are specified in table 4-1 <strong>and</strong> shall be met.<br />
4.3 CALIBRATION<br />
Annual Calibration – ALL S&V instrumentation shall be maintained with a current annual calibration<br />
certificate, traceable to the National Institute of St<strong>and</strong>ards <strong>and</strong> Technology (NIST), or<br />
equivalent organizations in other countries, <strong>and</strong> to the ANSI specifications listed in Table 4.1 or<br />
manufacturers specifications, whichever is more stringent.<br />
Field Calibration (<strong>Sound</strong>) – All sound instrumentation shall be field calibrated with an acoustic<br />
calibrator meeting the minimum requirements set forth in Table 4.1, at the beginning <strong>and</strong> the<br />
end of each day of use. Field calibration levels, times, <strong>and</strong> dates shall be documented in test<br />
reports.<br />
Field Calibration (<strong>Vibration</strong>) – All vibration instrumentation shall be field calibrated per manufacturer’s<br />
recommendations, <strong>and</strong>/or with a vibration calibrator meeting the minimum requirements set<br />
forth in Table 4.1. Calibration shall be performed before <strong>and</strong> after each instrument use. Field<br />
calibration levels, times, <strong>and</strong> dates shall be documented in test reports.<br />
Firms with multiple sets of instrumentation shall comply with either of the following conditions as a<br />
minimum requirement for <strong>NEBB</strong> certification:<br />
a) Calibrate all instrumentation used by the firm on S&V projects in accordance with Table 4-1.<br />
b) Maintain a complete set of calibrated instrumentation used for comparison with regularly used<br />
instrumentation. Periodic checking of regularly used instrumentation against the calibrated set<br />
shall be performed. Acceptance criteria for the results of the comparisons are the<br />
responsibility of the <strong>NEBB</strong> Qualified S&V Supervisor.<br />
Supervisors must underst<strong>and</strong> the importance of using accurate instrumentation in the field,<br />
<strong>and</strong> shall be prepared to have witnesses verify their work with the Firm’s calibrated set of<br />
instrumentation. Results of the data verification shall validate the accuracy of the<br />
instrumentation used to perform the work.<br />