<strong>GEZE</strong> RWA control unit systems<br />

<strong>GEZE</strong> EMERGENCY POWER Supply UNITS<br />

<strong>GEZE</strong> RWA<br />

DM drive module for <strong>ventilation</strong> groups<br />

One DM drive module provides a maximum of 10 A for the connection of a <strong>ventilation</strong> group.<br />

Worked sample<br />

Smoke and heat<br />

extraction systems<br />

Power requirement Drive module 10 A Switch <strong>power</strong> supplies Power modules<br />

16 A 2 (20 A) 1 x 24 A 1 (PM)<br />

30 A 3 (30 A) 1 x 24 A + 1 x 10 A 2 (PM + PME)<br />

CM control module and SM sensor module<br />

A CM control module is required in any case, as this monitors the first fire area. For each additional fire area, another SM sensor module is required.<br />

WM weather module<br />

A WM weather module is needed for wind direction dependent activation. Weather signals for closing during <strong>ventilation</strong> can also be added to<br />

the central sensor input on the CM.<br />

Casing<br />

The casing dimension depends on the number and arrangement of modules, the number of required switch <strong>power</strong> supplies and size<br />

of the batteries.<br />

Space requirements of modules and components on the DIN rail (width)<br />

Modules<br />

j<br />

j<br />

CM control module, SM sensor module, DM drive module,<br />

WM weather module: approx. 23 mm<br />

PM <strong>power</strong> module, PME <strong>power</strong> extension module: approx. 46 mm<br />

Examples<br />

j<br />

PM, CM and DM (minimum equipment):<br />

46 + 23 + 23 = 92 mm<br />

– or –<br />

<strong>with</strong> WM:<br />

92 + 23 = 115 mm<br />

~<br />

MBZ300<br />

MBZ300<br />

~<br />

~<br />

~125 mm<br />

PS 10A<br />

~125 mm<br />

PS 24A<br />

~85 mm<br />

~175 mm<br />

Note:<br />

20<br />

If only one switch <strong>power</strong> supply <strong>with</strong> 10 A is used, its space requirement on the DIN rail is added to that of the modules.<br />

Otherwise, switch <strong>power</strong> supplies are on a separate DIN rail.<br />

<strong>GEZE</strong> SMOKE AND HEAT EXTRACTION (RWA) AND VENTILATION TECHNOLOGY