DM drive module for <strong>ventilation</strong> groups<br />
One DM drive module provides a maximum of 10 A for the connection of a <strong>ventilation</strong> group.<br />
Worked sample<br />
Smoke and heat<br />
extraction systems<br />
Power requirement Drive module 10 A Switch <strong>power</strong> supplies Power modules<br />
16 A 2 (20 A) 1 x 24 A 1 (PM)<br />
30 A 3 (30 A) 1 x 24 A + 1 x 10 A 2 (PM + PME)<br />
CM control module and SM sensor module<br />
A CM control module is required in any case, as this monitors the first fire area. For each additional fire area, another SM sensor module is required.<br />
WM weather module<br />
A WM weather module is needed for wind direction dependent activation. Weather signals for closing during <strong>ventilation</strong> can also be added to<br />
the central sensor input on the CM.<br />
Casing<br />
The casing dimension depends on the number and arrangement of modules, the number of required switch <strong>power</strong> supplies and size<br />
of the batteries.<br />
Space requirements of modules and components on the DIN rail (width)<br />
Modules<br />
j<br />
j<br />
CM control module, SM sensor module, DM drive module,<br />
WM weather module: approx. 23 mm<br />
PM <strong>power</strong> module, PME <strong>power</strong> extension module: approx. 46 mm<br />
Examples<br />
j<br />
PM, CM and DM (minimum equipment):<br />
46 + 23 + 23 = 92 mm<br />
– or –<br />
<strong>with</strong> WM:<br />
92 + 23 = 115 mm<br />
~<br />
MBZ300<br />
MBZ300<br />
~<br />
~<br />
~125 mm<br />
PS 10A<br />
~125 mm<br />
PS 24A<br />
~85 mm<br />
~175 mm<br />
Note:<br />
20<br />
If only one switch <strong>power</strong> supply <strong>with</strong> 10 A is used, its space requirement on the DIN rail is added to that of the modules.<br />
Otherwise, switch <strong>power</strong> supplies are on a separate DIN rail.<br />
<strong>GEZE</strong> SMOKE AND HEAT EXTRACTION (RWA) AND VENTILATION TECHNOLOGY