<strong>GEZE</strong> RWA control unit systems<br />
<strong>GEZE</strong> EMERGENCY POWER Supply UNITS<br />
<strong>GEZE</strong> THZ compact staircase control unit<br />
<strong>GEZE</strong> RWA<br />
Smoke and heat<br />
extraction systems<br />
The RWA complete solution for staircases<br />
RWA emergency <strong>power</strong> supply units enable the coordinated actuation and release of fresh and exhaust air openings equipped <strong>with</strong><br />
electrically operated drives. With the new THZ emergency <strong>power</strong> supply unit, <strong>GEZE</strong> is presenting a compact solution for reliable<br />
smoke dissipation in staircases. The new control unit permits connection of a complete smoke dissipation solution comprising at least<br />
two drives, one fresh air and one exhaust air opening. The THZ is great value for money thanks to its high performance capacity and<br />
installation advantages.<br />
<strong>GEZE</strong> THZ<br />
PRODUCT FEATURES<br />
CONNECTION POSSIBILITIES<br />
TECHNICAL DATA<br />
• 3.4 A output current<br />
• 3 signal contacts for which parameters can be set: alarm/ fault/ window open<br />
• Weather station, lockable, <strong>with</strong>out additional board<br />
• Reset possible via external contact<br />
• Mains voltage 230 V AC 50 Hz<br />
• Output voltage 24 V ±15%<br />
• Emergency <strong>power</strong> supply min. 72 hours through 2 x 12 V batteries<br />
• Ambient temperature -5°C to +40°C<br />
• Can be used for RWA and daily <strong>ventilation</strong><br />
• Individual component replacement possible (board, <strong>power</strong> pack and battery)<br />
• Cable monitoring on alarm and drive lines<br />
• Adjustable reaction to mains failure (OPEN, CLOSED or no reaction)<br />
• Illuminated LED display for operating, fault and maintenance signal<br />
• Enclosure rating IP 30<br />
THZ<br />
• Up to 10 RM1003 smoke detectors or WM1005 heat differential detectors<br />
• Up to 8 RWA buttons FT4-24 V DC<br />
• For three vent switches (LTA 24 AZ) <strong>with</strong> LED (or any number <strong>with</strong>out LED connected)<br />
• Simple connection to fire alarm central unit through fire alarm central unit input (e.g. fire alarm<br />
central unit in dead man‘s function)<br />
• Wind/rain detector can be connected <strong>with</strong>out additional module<br />
• Parameters can be set for 3 potential-free signal contacts<br />
THZ<br />
Dimensions (W x H x D)<br />
193 x 285 x 89 mm<br />
Number of vent assemblies 1<br />
Output current<br />
max. 3.4 A<br />
RWA buttons<br />
max. 8 x per line<br />
Smoke detectors<br />
max. 10 x per line<br />
Heat differential detectors<br />
max. 10 x per line<br />
Signal inputs available<br />
• Rain/wind control and external fire alarm system (potential-free)<br />
• 2 signal inputs for which parameters can be set<br />
Signal outputs available<br />
3 signal contacts for which parameters can be set<br />
Power data transformer/battery 100 VA / 2.1-2.3 Ah<br />
Connection cross-section/mains 2.5 mm 2<br />
Terminal cross-section motor line 2.5 mm²<br />
8<br />