<strong>Power</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />

Contents<br />

<strong>Tmax</strong> Technical Data .................................................................... 4-2<br />

Distribution & Generator Protection <strong>Tmax</strong>...................................... 4-10<br />

<strong>Isomax</strong> Technical Data .................................................................. 4-16<br />

Distribution & Generator Protection <strong>Isomax</strong>.................................... 4-20<br />

<strong>Tmax</strong> Accessories.......................................................................... 4-30<br />

<strong>Isomax</strong> Accessories ...................................................................... 4-34<br />

Motor Protection <strong>Tmax</strong>.................................................................. 4-48<br />

Motor Protection <strong>Isomax</strong>................................................................ 4-51<br />

Current Limiting MCCB’s .............................................................. 4-58<br />

<strong>Emax</strong> Technical Data .................................................................... 4-60<br />

<strong>Emax</strong> Air Ciruit <strong>Breakers</strong>................................................................ 4-66<br />

<strong>Emax</strong> Accessories.......................................................................... 4-83<br />

ABB LIMITED<br />

4/1


<strong>Tmax</strong> Electrical Specifications<br />

B C N<br />

Performance level Iu [A] 160 160 160<br />

Poles No. 3/4 3/4 3/4 3/4<br />

Description T1<br />

Rated service voltage<br />

Ue<br />

Rated ultimate short circuit breaking capacity<br />

Icu<br />

Rated short circuit service breaking capacity<br />

Ics<br />

Rated short circuit making capacity<br />

Icm<br />

Isolation behavior<br />

Releases Thermomagnetic TMD (adj.)<br />

TMF (fixed) - - -<br />

PR221 DS-I - - -<br />

1) MF up to R 12.5 A<br />

2) In the plug-in version, the maximum setting is derated by 10% at 40°C<br />

3) F-FC Cu-FC CuAI-EF-ES-R-FC Cu AI 240mm 2<br />

(AC) 50-60Hz [V] 690 690 690<br />

(DC) [V] 500 500 500<br />

Rated impulse withstand voltage Uimp [kV] 8 8 8<br />

Rated insulation voltage Ui [V] 800 800 800<br />

Voltage test at industrial frequency for 1 min. [V] 3000 3000 3000<br />

(AC) 50-60Hz 220/230 V [kA] 25 40 50<br />

(AC) 50-60Hz 380/415 V [kA] 16 25 36<br />

(AC) 50-60Hz 440 V [kA] 10 15 22<br />

(AC) 50-60Hz 500 V [kA] 8 10 15<br />

(AC) 50-60Hz 690 V [kA] 3 4 6<br />

(DC) 250 V 2 poles in series [kA] 16 25 36<br />

(DC) 250 V 3 poles in series [kA] 20 30 40<br />

(DC) 500 V 3 poles in series [kA] 16 25 36<br />

(AC) 50-60Hz 220/230 V [kA] 100% 75% 75%<br />

(AC) 50-60Hz 380/415 V [kA] 100% 75% 50% (19kA)<br />

(AC) 50-60Hz 440 V [kA] 100% 75% 50%<br />

(AC) 50-60Hz 500 V [kA] 100% 75% 50%<br />

(AC) 50-60Hz 690 V [kA] 100% 75% 50%<br />

(AC) 50-60Hz 220/230 V [kA] 52.5 84 105<br />

(AC) 50-60Hz 380/415 V [kA] 32 52.5 75.6<br />

(AC) 50-60Hz 440 V [kA] 17 30 46.2<br />

(AC) 50-60Hz 500 V [kA] 13.6 17 30<br />

(AC) 50-60Hz 690 V [kA] 4.3 5.9 9.2<br />

Breaking time [ms] 7 6 5<br />

Utilisation category A A A<br />

Reference Standards IEC 60947-2 IEC 60947-2 IEC 60947-2<br />

magnetic only MA - - -<br />

microprocessor based PR221 DS-LS - - -<br />

Versions F F F<br />

Terminals F - P FC Cu-EF-FC CuAI 95mm 2<br />

Fixing on DIN rail DIN EN 50022<br />

Mechanical life [No. Operations] 25000 25000 25000<br />

[No. Hourly Operations] 240 240 240<br />

Electrical life at 415 V [No. Operations] 8000 8000 8000<br />

[No. Hourly Operations] 120 120 120<br />

Basic dimensions, fixed version 3 poles L [mm] 76 76 76<br />

4 poles L [mm] 102 102 102<br />

H [mm] 130 130 130<br />

P [mm] 70 70 70<br />

Weight fixed version 3/4 Poles [kg] 0.9 / 1.2 0.9 / 1.2 0.9 / 1.2<br />

plug-in version 3/4 Poles [kg] - - -<br />

ABB LIMITED 4/2


T2<br />

T3<br />

N S H L N S<br />

160 160 160 160 160 160<br />

3/4 3/4 3/4 3/4 3/4 3/4<br />

690 690 690 690 690 690<br />

500 500 500 500 500 500<br />

8 8 8 8 8 8<br />

800 800 800 800 800 800<br />

3000 3000 3000 3000 3000 3000<br />

65 85 100 120 50 85<br />

36 50 70 85 36 50<br />

30 45 55 75 25 40<br />

25 30 36 50 20 30<br />

6 7 8 10 5 8<br />

36 50 70 85 36 50<br />

40 55 85 100 40 55<br />

36 50 70 85 36 50<br />

100% 100% 100% 100% 75% 50%<br />

100% 100% 100% 75%(70kA) 75% 50% (27kA)<br />

100% 100% 100% 75% 75% 50%<br />

100% 100% 100% 75% 75% 50%<br />

100% 100% 100% 75% 75% 50%<br />

143 187 220 264 105 187<br />

75.6 105 154 187 75.6 105<br />

63 94.5 121 165 52.5 84<br />

52.5 63 75.6 105 40 63<br />

9.2 11.9 13.6 17 7.7 13.6<br />

3 3 3 3 7 6<br />

A A A A A A<br />

IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2<br />

- - - - - -<br />

1) 1) 1) 1)<br />

- -<br />

- -<br />

F-P 2) F-P 2) F-P 2) F-P 2) F-P 2) F-P 2)<br />

2<br />

F-FC Cu-FC CuAI-EF-ES-R-FC CuAI 185mm<br />

3) 3)<br />

DIN EN 50022 DIN EN 50022<br />

25000 25000 25000 25000 25000 25000<br />

240 240 240 240 120 120<br />

8000 8000 8000 8000 8000 8000<br />

120 120 120 120 120 120<br />

90 90 90 90 105 105<br />

120 120 120 120 140 140<br />

130 130 130 130 150 150<br />

70 70 70 70 70 70<br />

1.1 / 1.5 1.1 / 1.5 1.1 / 1.5 1.1 / 1.5 2.1 / 3 2.1 / 3<br />

1.5 / 1.9 1.5 / 1.9 1.5 / 1.9 1.5 / 1.9 2.7 / 3.7 2.7 / 3.7<br />

ABB LIMITED 4/3


<strong>Isomax</strong> Electrical Specifications<br />

Description S3 S4<br />

N H L N<br />

Performance level Iu [A] 160-250 160-250 160-250 160-250<br />

Poles No. 3/4 3/4 3/4 3/4<br />

Rated service voltage<br />

Ue<br />

(AC) 50-60Hz [V] 690 690 690 690<br />

(DC) [V] 750 750 750 -<br />

Rated impulse withstand voltage Uimp [kV] 8 8 8 8<br />

Rated insulation voltage Ui [V] 800 800 800 800<br />

Voltage test at industrial frequency for 1 min. [V] 3000 3000 3000 3000<br />

Rated ultimate short circuit breaking capacity<br />

Icu<br />

(AC) 50-60Hz 220/230 V [kA] 65 100 170 65<br />

(AC) 50-60Hz 380/415 V [kA] 35 65 85 35<br />

(AC) 50-60Hz 440 V [kA] 30 50 65 30<br />

(AC) 50-60Hz 500 V [kA] 25 40 50 25<br />

(AC) 50-60Hz 690 V [kA] 14 18 50 18<br />

(DC) 250 V 2 poles in series [kA] 35 65 85 -<br />

(DC) 250 V 3 poles in series [kA] 35 50 65 -<br />

(DC) 750 V 3 poles in series [kA] 20 35 50 -<br />

Rated short circuit service breaking capacity Ics [%Icu] 100% 75% 75% 100%<br />

Rated short circuit making capacity (415 V) [kA] 74 143 187 74<br />

Opening Time (415 V at Icu) [ms] 8 7 6 8<br />

Rated short time withstand current for 1 s, Icw [kA] - - - -<br />

Utilisation category (EN 60947-2) A A A A<br />

Isolation behavior<br />

IEC 60947-2, EN 60947-2<br />

Releases Thermomagnetic T adjustable, M fixed 3 Ith - -<br />

T adjustable, M fixed 5 Ith -<br />

T adjustable, M fixed 10 Ith -<br />

T adjustable, M adjustable - - - -<br />

magnetic only M fixed -<br />

microprocessor based PR211/P (I-LI) - - -<br />

PR212/P (LSI-LSIG - - -<br />

Versions F-P-W F-P-W<br />

Terminals Fixed F-EF-ES-FC<br />

FC CuAI-RC-R<br />

Plug-in<br />

EF-FC-R<br />

Withdrawable<br />

EF-FC-R<br />

Fixing on DIN rail DIN EN 50023<br />

Mechanical life [No. Operations] 25000 25000 25000 20000<br />

[No. Hourly Operations] 120 120 120 120<br />

Electrical life at 415 V [No. Operations] 10000 (160A) -8000 (250A)<br />

[No. Hourly Operations] 120 120 120 120<br />

Basic dimensions, fixed 3/4 poles L [mm] 105/140 105/140 105/140 105/140<br />

D [mm] 103.5 103.5 103.5 103.5 103.5<br />

H [mm] 170 170 170 254 254<br />

Weight fixed version 3/4 Poles [kg] 2.6/3.5 2.6/3.5 2.6/3.5 4/5.3<br />

plug-in version 3/4 Poles [kg] 3.1/4.1 3.1/4.1 3.1/4.1 4.5/5.9<br />

withdrawable 3/4 Poles [kg] 3.5/4.5 3.5/4.5 3.5/4.5 4.9/6.3<br />

ABB LIMITED 4/4


S4 S5 S6 S7<br />

H L N H L N S H L S H L<br />

160-250 160-250 400-630 400-630 400-630 630-800 630-800 630-800 630-800 1250-1600 1250-1600 1250-1600<br />

3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4<br />

690 690 690 690 690 690 690 690 690 690 690 690<br />

- - 750 750 750 750 750 750 750 - - -<br />

8 8 8 8 8 8 8 8 8 8 8 8<br />

800 800 800 800 800 800 800 800 800 800 800 800<br />

3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000<br />

100 200 65 100 200 65 85 100 200 85 100 200<br />

65 100 35 65 100 35 50 65 100 50 65 100<br />

50 80 30 50 80 30 45 50 80 40 55 80<br />

40 65 25 40 65 25 35 40 65 35 45 70<br />

22 30 20 25 30 20 22 25 30 20 25 35<br />

- - 35 65 100 35 50 65 100 - - -<br />

- - 35 50 65 20 35 50 65 - - -<br />

- - 20 35 50 16 20 35 50 - - -<br />

100% 75% 100% 100% 75% 100% 100% 100% 75% 100% 75% 50%<br />

143 220 74 143 220 74 105 143 220 105 143 220<br />

7 6 8 7 6 10 9 8 7 22 22 22<br />

- - 5 (400A) 7.6 (630A) - 10 (800A) 15 (1250A) - 20 (1600A)<br />

A A B (400A) - A (630A) B B B B B B B<br />

- - - - - - - - - - - -<br />

- - - - - - - - - - - -<br />

- - - - - - - - - - - -<br />

- - - - -<br />

- - - - - - - - - - - -<br />

F-P-W F-P(400)-W F-W F-W<br />

F-EF-ES-FC F-EF(400A)-ES-FC F-EF-ES-FC-CuAI F-EF-ES-FC CuAI(1250A)<br />

FC CuAI-RC-R FC CuAI(400A)-RC-(400A)-R RC-R HR-VR<br />

EF-FC-R EF-FC-R - -<br />

EF-FC-R EF(400A)-ES-FC(400A) EF-HR-VR EF-HR-VR<br />

DIN EN 50023 DIN EN 50023<br />

20000 20000 20000 20000 20000 20000 20000 20000 20000 10000 10000 10000<br />

120 120 120 120 120 120 120 120 120 120 120 120<br />

10000(160A) - 8000(250A) 7000 (400A) - 5000 (800A) 7000 (630A) - 5000 (800A) 7000 (1250A) - 5000 (1600A)<br />

120 120 60 60 60 60 60 60 60 20 20 20<br />

105/140 105/140 140/184 140/184 140/184 210/280 210/280 210/280 210/280 210/280 210/280 210/280<br />

103.5 103.5 103.5 103.5 103.5 103.5 103.5 103.5 138.5 138.5 138.5<br />

254 254 254 254 268 268 268 268 406 406 406<br />

4/5.3 4/5.3 5/7 5/7 5/7 9.5/12 9.5/12 9.5/12 9.5/12 17/22 17/22 17/22<br />

4.5/5.9 4.5/5.9 6.1/8.4 6.1/8.4 6.1/8.4 - - - - - - -<br />

4.9/6.3 4.9/6.3 6.4/8.7 6.4/8.7 6.4/8.7 12.1/15.1 12.1/15.1 12.1/15.1 12.1/15.1 21.8/29.2 21.8/29.2 21.8/29.2<br />

ABB LIMITED 4/5


<strong>Tmax</strong> Construction Characteristics<br />

Modularity of the series<br />

3<br />

7<br />

1<br />

2<br />

9<br />

14<br />

13<br />

ABB LIMITED 4/6


Starting from the fixed version circuit-breaker, all the other versions<br />

used for various requirements are obtained by means of<br />

mounting conversion kits.<br />

12<br />

The following are available:<br />

1<br />

2<br />

3<br />

Kit for converting a fixed circuit-breaker into the moving<br />

part of a plug-in<br />

<strong>Circuit</strong>-breaker fixed parts for plug-in circuit-breakers<br />

Conversion kit for the connection terminals<br />

Various accessories are also available:<br />

4<br />

Shunt opening releases<br />

5<br />

Undervoltage releases<br />

8<br />

6<br />

6<br />

Auxiliary contacts<br />

7<br />

Position contacts<br />

5<br />

8<br />

9<br />

10<br />

11<br />

12<br />

Advanced contacts on rotary handle<br />

Front and rear connection terminals<br />

Bracket for rear fixing on DIN EN 50022 rail<br />

Front interlocking plate<br />

Solenoid operating mechanism<br />

4<br />

13<br />

14<br />

Rotary handle operating mechanism - direct on circuitbreaker<br />

and transmitted on compartment door<br />

Three-pole and four-pole residual current releases<br />

ABB LIMITED 4/7


<strong>Tmax</strong> Electronic Releases<br />

Protection functions<br />

of the PR221DS-LS release<br />

Protection Function Trip threshold Trip Curves<br />

A B C<br />

L<br />

CANNOT BE<br />

EXCLUDED<br />

Against overload with inverse<br />

long delay trip and trip characteristic<br />

according to a definite<br />

time curve (I 2 t = constant)<br />

i1 = 0.40 - 0.44 - 0.48 - 0.52 -<br />

0.56 - 0.60 - 0.64 - 0.68<br />

0.72 - 0.76 - 0.80 - 0.84<br />

0.88 - 0.92 - 0.96 - 1 x In<br />

Release between 1.05...1.30 x I1<br />

(IEC 60947-2)<br />

at 6 x I1<br />

t1 = 3s<br />

(Tolerence<br />

at 6 x I1<br />

t1 = 6s<br />

± 10% up to 2 x In;<br />

± 20% over 2 xIn)<br />

S<br />

CAN BE<br />

EXCLUDED<br />

Against a short-circuit with<br />

inverse short delay and trip<br />

characteristic with definite time<br />

(I 2 t = constant)<br />

i1 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5<br />

- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 -<br />

9 - 10 x In<br />

Tolerence<br />

± 10% up to 2 x In<br />

± 20% over 2 x In<br />

at 8 x In at 8 x In<br />

t2 = 0.1s t2 = 0.25s<br />

(Tolerence ± 20%)<br />

I<br />

CAN BE<br />

EXCLUDED<br />

Against short-circuit with instantaneous<br />

adjustable trip (can be<br />

selected as an alternative to<br />

protection function S)<br />

I3 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5<br />

- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 -<br />

9 - 10 x In<br />

Tolerence ± 20%<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/8


<strong>Tmax</strong> Thermomagnetic Releases<br />

Thermomagnetic releases<br />

The <strong>Tmax</strong> T1, T2 and T3 circuit-breakers can be fitted with thermomagnetic releases and are<br />

used to protect alternating and direct current networks with an application range from 1A to<br />

250A. They allow protection against overloads with a thermal device (with adjustable threshold)<br />

made using the bimetal technique, and protection against short-circuit with a magnetic device<br />

(with fixed threshold).<br />

The four-pole circuit-breakers are always supplied with the neutral protected by the release<br />

and protection of the neutral at 100% of the phase setting for settings up to 100A. For higher<br />

settings, the version with protection of the neutral at 50% of the phase setting is available.<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/9


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T2N (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2N 36kA 100%<br />

Protection types available<br />

Type<br />

Electronic<br />

Settings<br />

L<br />

PR221DS/LS 0.4 -1x In 1-10x In<br />

S<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70 - 100% 10x Ith<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR221DS/LS<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

T2N160R1.6 1.6A 50940 50962 - -<br />

T2N160R2 2A 50941 50963 - -<br />

T2N160R2.5 2.5A 50942 50964 - -<br />

T2N160R3.2 3.2A 50943 50965 - -<br />

T2N160R4 4A 50944 50966 - -<br />

T2N160R5 5A 50945 50967 - -<br />

T2N160R6.3 6.3A 50946 50968 - -<br />

T2N160R8 8A 50947 50969 - -<br />

T2N160R10 10A 50948 50970 51123 51128<br />

T2N160R12.5 12.5A 50949 50971 - -<br />

36kA T2N160R16 16A 50950 50972 - -<br />

T2N160R20 20A 50951 50973 - -<br />

T2N160R25 25A 50952 50974 51124 51129<br />

T2N160R32 32A 50953 50975 - -<br />

T2N160R40 40A 50954 50976 - -<br />

T2N160R50 50A 50955 50977 - -<br />

T2N160R63 63A 50956 50978 51125 51130<br />

T2N160R80 80A 50957 50979 - -<br />

T2N160R100 100A 50958 50980 51126 51131<br />

T2N160R125 125A 50959 51115 - -<br />

T2N160R160 160A 50960 51116 51127 51613<br />

Plug-in <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below Plug-in<br />

1SDA0<br />

R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/11


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T2S (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2S 50kA 100%<br />

Protection types available<br />

Type<br />

Electronic<br />

Settings<br />

L<br />

PR221DS/LS 0.4 -1x In 1-10x In<br />

S<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70 - 100% 10x Ith*<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR221DS/LS<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

50kA T2S160R1.6 1.6A 50984 51006 - -<br />

T2S160R2 2A 50985 51007 - -<br />

T2S160R2.5 2.5A 50986 51008 - -<br />

T2S160R3.2 3.2A 50987 51009 - -<br />

T2S160R4 4A 50988 51010 - -<br />

T2S160R5 5A 50989 51011 - -<br />

T2S160R6.3 6.3A 50990 51012 - -<br />

T2S160R8 8A 50991 51013 - -<br />

T2S160R10 10A 50992 51014 51133 51138<br />

T2S160R12.5 12.5A 50993 51015 - -<br />

T2S160R16 16A 50994 51016 - -<br />

T2S160R20 20A 50995 51017 - -<br />

T2S160R25 25A 50996 51018 51134 51139<br />

T2S160R32 32A 50997 51019 - -<br />

T2S160R40 40A 50998 51020 - -<br />

T2S160R50 50A 50999 51021 - -<br />

T2S160R63 63A 51000 51022 51135 51140<br />

T2S160R80 80A 51001 51023 - -<br />

T2S160R100 100A 51002 51024 51136 51141<br />

T2S160R125 125A 51003 51117 - -<br />

T2S160R160 160A 51004 51118 51137 51614<br />

Plug-in <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

1SDA0<br />

Plug-in<br />

R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/12


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T2H (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2H 70kA 100%<br />

Protection types available<br />

Type<br />

Electronic<br />

Settings<br />

L<br />

PR221DS/LS 0.4 -1x In 1-10x In<br />

S<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70 - 100% 10x Ith<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR221DS/LS<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

T2H160R1.6 1.6A 51028 51050 - -<br />

T2H160R2 2A 51029 51051 - -<br />

T2H160R2.5 2.5A 51030 51052 - -<br />

T2H160R3.2 3.2A 51031 51053 - -<br />

T2H160R4 4A 51032 51054 - -<br />

T2H160R5 5A 51033 51055 - -<br />

T2H160R6.3 6.3A 51034 51056 - -<br />

T2H160R8 8A 51035 51057 - -<br />

T2H160R10 10A 51036 51058 51143 51148<br />

70kA T2H160R12.5 12.5A 51037 51059 - -<br />

T2H160R16 16A 51038 51060 - -<br />

T2H160R20 20A 51039 51061 - -<br />

T2H160R25 25A 51040 51062 51144 51149<br />

T2H160R32 32A 51041 51063 - -<br />

T2H160R40 40A 51042 51064 - -<br />

T2H160R50 50A 51043 51065 - -<br />

T2H160R63 63A 51044 51066 51145 51150<br />

T2H160R80 80A 51045 51067 - -<br />

T2H160R100 100A 51046 51068 51146 51151<br />

T2H160R125 125A 51047 51119 - -<br />

T2H160R160 160A 51048 51120 51147 51615<br />

Plug-in <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

1SDA0<br />

Plug-in<br />

R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/13


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T1... (160A)<br />

Ratings @ 415V (230V for 1 pole)<br />

Icu Ics Icw<br />

(1sec)<br />

T1B (1Pole) 25kA 75%<br />

T1B (3 & 4 Pole) 16kA 100%<br />

T1C 25kA 75%<br />

T1N 36kA 50%<br />

T1D - - 2kA<br />

Protection types available<br />

Type<br />

Settings<br />

Ith<br />

Standard Distribution (1 pole) 100% 10x Ith*<br />

Standard Distribution (3&4 pole)70-100%<br />

Im<br />

10x Ith*<br />

* Subject to a Minimum value of 500A<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front cable terminals for copper cables - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic<br />

Ith 1SDA0 R1<br />

1 Pole 3 Pole 4 Pole<br />

T1B160R16 16A 52616 50870 50881<br />

T1B160R20 20A 52617 50871 50882<br />

T1B160R25 25A 52618 50872 50883<br />

T1B160R32 32A 52619 50873 50884<br />

T1B160R40 40A 52620 50874 50885<br />

16kA (25A for T1B160R50 50A 52621 50875 50886<br />

1 pole) T1B160R63 63A 52622 50876 50887<br />

T1B160R80 80A 52623 50877 50888<br />

T1B160R100 100A 52624 50878 50889<br />

T1B160R125 125A 52625 50879 50890<br />

T1B160R160 160A 52626 50880 50936<br />

T1C160R25 25A - 50894 50905<br />

T1C160R32 32A - 50895 50906<br />

T1C160R40 40A - 50896 50907<br />

T1C160R50 50A - 50897 50908<br />

25kA T1C160R63 63A - 50898 50909<br />

T1C160R80 80A - 50899 50910<br />

T1C160R100 100A - 50900 50911<br />

T1C160R125 125A - 50901 50912<br />

T1C160R160 160A - 50902 50937<br />

T1N160R32 32A - 50917 50928<br />

T1N160R40 40A - 50918 50929<br />

T1N160R50 50A - 50919 50930<br />

36kA T1N160R63 63A - 50920 50931<br />

T1N160R80 80A - 50921 50932<br />

T1N160R100 100A - 50922 50933<br />

T1N160R125 125A - 50923 50934<br />

T1N160R160 160A - 50924 50938<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/10


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T2 (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2L 85kA 75%<br />

Protection types available<br />

Type<br />

Electronic<br />

Settings<br />

L<br />

PR221DS/LS 0.4 -1x In 1-10x In<br />

S<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70 - 100% 10x Ith<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagetic PR221DS/LS<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

T2L160R1.6 1.6A 51072 51094 - -<br />

T2L160R2 2A 51073 51095 - -<br />

T2L160R2.5 2.5A 51074 51096 - -<br />

T2L160R3.2 3.2A 51075 51097 - -<br />

T2L160R4 4A 51076 51098 - -<br />

T2L160R5 5A 51077 51099 - -<br />

T2L160R6.3 6.3A 51078 51100 - -<br />

T2L160R8 8A 51079 51101 - -<br />

T2L160R10 10A 51080 51102 51153 51158<br />

85kA T2L160R12.5 12.5A 51081 51103 - -<br />

Plug-in <strong>Circuit</strong> breakers<br />

T2L160R16 16A 51082 51104 - -<br />

T2L160R20 20A 51083 51105 - -<br />

T2L160R25 25A 51084 51106 51154 51159<br />

T2L160R32 32A 51085 51107 - -<br />

T2L160R40 40A 51086 51108 - -<br />

T2L160R50 50A 51087 51109 - -<br />

T2L160R63 63A 51088 51110 51155 51160<br />

T2L160R80 80A 51089 51111 - -<br />

T2L160R100 100A 51090 51112 51156 51161<br />

T2L160R125 125A 51091 51121 - -<br />

T2L160R160 160A 51092 51122 51157 51162<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

Plug-in<br />

1SDA0 R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/14


Distribution and Generator Protection MCCBs<br />

<strong>Tmax</strong> T3 (250A)<br />

Ratings @ 415V<br />

Icu Ics Icw<br />

(1sec)<br />

T3N 36kA 75%<br />

T3S 50kA 50%<br />

T3D - - 3.6kA<br />

Protection types available<br />

Type<br />

Settings<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70-100% 10x Ith*<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole<br />

T3N250R63 63A 51241 51252<br />

T3N250R80 80A 51242 51253<br />

T3N250R100 100A 51243 51254<br />

36kA T3N250R125 125A 51244 51303<br />

T3N250R160 160A 51245 51304<br />

T3N250R200 200A 51246 51305<br />

T3N250R250 250A 51247 51306<br />

T3S250R63 63A 51263 51274<br />

T3S250R80 80A 51264 51275<br />

T3S250R100 100A 51265 51276<br />

50kA T3S250R125 125A 51266 51307<br />

T3S250R160 160A 51267 51308<br />

T3S250R200 200A 51268 51309<br />

T3S250R250 250A 51269 51310<br />

Fixed Pattern Switch Disconnector<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front cable terminals for copper cables - for other terminals see<br />

accessories section pagexx<br />

lcw (1 sec) Model Current (A) 1SDA0 R1<br />

Iu 3 Pole 4 Pole<br />

3.6kA T3D250 250A 51327 51328<br />

Plug-in <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

1SDA0<br />

Plug-in<br />

R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/15


<strong>Isomax</strong> Construction Characteristics<br />

Modularity of the series<br />

1<br />

Rotary handle<br />

9<br />

Shunt trip<br />

2<br />

Locking device<br />

10<br />

Aux contact<br />

3<br />

Motor operator<br />

11<br />

Rear stud terminal<br />

4<br />

Thermal Magnetic Release<br />

12<br />

Cable clamp aluminium<br />

27<br />

5<br />

Standard escutcheon<br />

13<br />

Cable clamp copper<br />

6<br />

Data plate<br />

14<br />

Extended bar terminals<br />

7<br />

DINescutcheon<br />

15<br />

Conversion kit from fixed to moving<br />

22<br />

8<br />

UVR<br />

16<br />

Position carriage switch<br />

8<br />

9<br />

7<br />

5<br />

1<br />

6<br />

10<br />

2<br />

4<br />

22<br />

3<br />

27<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/16


17<br />

18<br />

14<br />

19<br />

13<br />

12<br />

11<br />

24<br />

23<br />

16<br />

25<br />

15<br />

20<br />

26<br />

21<br />

22<br />

Long terminal shrouds<br />

17<br />

Fixed portion terminal shrouds<br />

23<br />

Plug-in tulip contacts<br />

18<br />

Rear cable connections<br />

24<br />

Shunt trip + UVR female socket<br />

19<br />

Rear bolt connections<br />

25<br />

Aux connections plug-in / drawout<br />

20<br />

Door closing racking device<br />

26<br />

Female sockets for fixed breaker<br />

21<br />

Carriage locking device<br />

27<br />

Short terminal shrouds<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/17


<strong>Isomax</strong> Electronic Releases<br />

PR211/P<br />

PR212/P<br />

In<br />

In<br />

S4 100<br />

160<br />

250<br />

S5 320<br />

400<br />

L<br />

I1 (0.4 ... 1xIn)<br />

t1 = 3 ... 18s<br />

S4 100<br />

160<br />

250<br />

S5 320<br />

400<br />

L<br />

I1 (0.4 ... 1xIn)<br />

t1 = 3 ... 18s<br />

S<br />

I2 (1 ... 10 OFF x In)<br />

t2 = 0.05 ... 0.5s<br />

S6 630<br />

800<br />

S7 1000<br />

1250<br />

1600<br />

I<br />

I3 (1.5 ... 12 x In)<br />

S6 630<br />

800<br />

S7 1000<br />

1250<br />

1600<br />

I<br />

I3 (1.5 ... 12 OFF x In)<br />

G<br />

I4 (0.2 ... 1 OFF x In)<br />

t4 = 0.01 ... 0.8s<br />

L<br />

Against overload with inverse long time delay and trip characteristic<br />

according to a time dependent curve (I 2 t = constant)<br />

CANNOT BE<br />

EXCLUDED<br />

S<br />

CAN BE<br />

EXCLUDED<br />

I<br />

CAN BE<br />

EXCLUDED<br />

G<br />

CAN BE<br />

EXCLUDED<br />

Against short-circuit with inverse short time delay and trip<br />

characteristic with dependent time (I 2 t = constant) independent<br />

Against short-circuit with adjustable instantaneous trip<br />

Against earth fault with short inverse time delay and trip characteristic<br />

according to a dependent time curve (I 2 t = constant)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/18


<strong>Isomax</strong> Thermomagnetic Releases<br />

The thermomagnetic releases which equip the <strong>SACE</strong>S3 circuit-breakers have the thermal element with<br />

threshold adjustable from 0.7 ÷ 1 x In. The regulated current value which is obtained by using the appropriate<br />

selector must be intended as the rated value at 40ºC. The magnetic element has fixed trip threshold,<br />

with trip values which may vary according to the phase setting.<br />

The thermomagnetic releases which equip <strong>SACE</strong> S5 and S6 circuit-breakers have the thermal element with<br />

threshold adjustable from 0.7 ÷ 1 x In. The regulated current value which is obtained by using the approproate<br />

selector must be intended as the rated value at 40ºC. The magnetic element can be adjusted from<br />

5 ÷ 10 x In. The table gives the maximum magnetic trip values (10 x In) for protection of the phases (L1 -<br />

L2 - L3) and of the neutral.<br />

S3<br />

S5/6<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/19


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S3 (250A)<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

S3N 35kA 100%<br />

S3H 65kA 75%<br />

S3L 85kA 75%<br />

S3D - - 6.5kA<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Standard Low Threshold Generator<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

S3N160R32 32A 13346 13371 13359 13383 - -<br />

S3N160R50 50A 13348 13373 13361 13385 - -<br />

S3N160R80 80A 13350 13375 13363 13387 - -<br />

35kA S3N160R100 100A 13352 13377 13365 13389 48539 48549<br />

S3N160R125 125A 13354 13379 13367 13391 48540 48550<br />

S3N160R160 160A 13356 13381 13369 13393 48541 48551<br />

S3N250R200 200A 13491 13499 13495 13503 48545 48555<br />

S3N250R250 250A 13493 13501 13497 13505 48546 48556<br />

S3H160R32 32A 13395 13419 13407 13431 - -<br />

S3H160R50 50A 13397 13421 13409 13433 - -<br />

S3H160R80 80A 13399 13423 13411 13435 - -<br />

65kA S3H160R100 100A 13401 13425 13413 13437 48542 48552<br />

S3H160R125 125A 13403 13427 13415 13439 48543 48553<br />

S3H160R160 160A 13405 13429 13417 13441 48544 48554<br />

S3H250R200 200A 13507 13515 13511 13519 48547 48557<br />

S3H250R250 250A 13509 13517 13513 13521 48548 48558<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/20


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S3 (250A)<br />

Protection types available<br />

Type<br />

Standard Distribution<br />

Settings<br />

Ith<br />

Im<br />

70-100% 10xIth<br />

Low Threshold Thermomagnetic 70-100% 5xIth<br />

Generator Thermomagnetic<br />

70-100% 3xIth<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Standard Low Threshold<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

S3L160R32 32A 13443 13467 13455 13479<br />

S3L160R50 50A 13445 13469 13457 13481<br />

S3L160R80 80A 13447 13471 13459 13483<br />

85kA S3L160R100 100A 13449 13473 13461 13485<br />

S3L160R125 125A 13451 13475 13463 13487<br />

S3L160R160 160A 13453 13477 13465 13489<br />

S3L250R200 200A 13523 13531 13527 13535<br />

S3L250R250 250A 13525 13533 13529 13537<br />

Fixed Pattern Switch Disconnector<br />

lcw (1 sec) Model Current (A) 1SDA0 R1<br />

Iu 3 Pole 4 Pole<br />

S3D100 100A 20906 20907<br />

6.5kA S3D100 160A 20908 20909<br />

S3D250 250A 20910 20911<br />

Plug-in / Withdrawable <strong>Circuit</strong> breakers / Disconnectors<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

Plug-in<br />

Withdrawable<br />

1SDA0 R1 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

Conversion Kit 13608 13609 13610 13611<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals 13543 13550 13559 13568<br />

Extended Front bar Terminals 13539 13548 13555 13564<br />

Threaded Rear Terminals 13547 13554 13563 13572<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/21


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S4 (250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S4N 35kA 100%<br />

S4H 65kA 100%<br />

S4L 100kA 75%<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection PR211 PR212<br />

In 1SDA0 R1 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 15550 15838 - -<br />

35kA S4N160R100 100A LSI - - 15553 15841<br />

LSIG - - 15558 15846<br />

LI 15551 15839 - -<br />

35kA S4N160R160 160A LSI - - 15554 15842<br />

LSIG - - 15559 15847<br />

LI 17319 17385 - -<br />

35kA S4N250R250 250A LSI - - 17320 17386<br />

LSIG - - 17323 17389<br />

LI 16144 16426 - -<br />

65kA S4H160R100 100A LSI - - 16146 16428<br />

LSIG - - 16152 16434<br />

LI 16145 16427 - -<br />

65kA S4H160R100 160A LSI - - 16147 16429<br />

LSIG - - 16153 16435<br />

LI 17451 17517 - -<br />

65kA S4H250R250 250A LSI - - 17452 17518<br />

LSIG - - 17455 17521<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/22


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S4 (250A)<br />

Protection types available<br />

Electronic (ac only)<br />

Type<br />

Settings<br />

L S I G<br />

PR211/LI 0.4-1x In - 1.5-12x In -<br />

PR212/LSI 0.4-1x In 1-10x In 1.5-12x In<br />

PR212/LSIG 0.4-1x In 1-10xIn 1.5-12x In 0.2-1x In<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection PR211 PR212<br />

In 1SDA0 R1 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 16732 17014 - -<br />

100kA S4L160R100 100A LSI - - 16734 17016<br />

LSIG - - 16740 17022<br />

LI 16733 17015 - -<br />

100kA S4L160R160 160A LSI - - 16735 17017<br />

LSIG - - 16741 17023<br />

LI 17583 17649 - -<br />

100kA S4L250R250 250A LSI - - 17584 17650<br />

Plug-in / Withdrawable <strong>Circuit</strong> breakers / Disconnectors<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

LSIG - - 17587 17653<br />

Plug-in<br />

Withdrawable<br />

1SDA0 R1 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

Conversion Kit 13608 13609 13610 13611<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals 13616 13625 13634 13643<br />

Extended Front bar Terminals 13612 13621 13630 13639<br />

Threaded Rear Terminals 13620 13629 13638 13647<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/23


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S5 (630A)<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)*<br />

S5N 35kA 100% 5kA<br />

S5H 65kA 100% 5kA<br />

S5L 100kA 75% 5kA<br />

*400A only<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection Thermomagnetic PR211 PR212<br />

Ith 1SDA0 R1<br />

35kA S5N400R320 320A<br />

35kA S5N400R400 400A<br />

35kA S5N630R500 500A<br />

35kA S5N630R630 630A<br />

65kA S5H400R320 320A<br />

65kA S5H400R400 400A<br />

65kA S5H630R500 500A<br />

65kA S5H630R630 630A<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

T/Mag 38438 38440 - - - -<br />

LI - - 17716 17848 - -<br />

LSI - - - - 17718 17850<br />

LSIG - - - - 17724 17856<br />

T/Mag 38439 38441 - - - -<br />

LI - - 17717 17849 - -<br />

LSI - - - - 17719 17851<br />

LSIG - - - - 17725 17857<br />

T/Mag 38678 38683 - - - -<br />

LI - - - - - -<br />

LSI - - - - - -<br />

LSIG - - - - - -<br />

T/Mag - - - - - -<br />

LI - - 38675 38680 - -<br />

LSI - - - - 38676 38681<br />

LSIG - - - - 38677 38682<br />

T/Mag 38522 38524 - - - -<br />

LI - - 17992 18124 - -<br />

LSI - - - - 17994 18126<br />

LSIG - - - - 18000 18132<br />

T/Mag 38523 38525 - - - -<br />

LI - - 17993 18125 - -<br />

LSI - - - - 17995 18127<br />

LSIG - - - - 18001 18133<br />

T/Mag 38708 38713 - - - -<br />

LI - - - - - -<br />

LSI - - - - - -<br />

LSIG - - - - - -<br />

T/Mag - - - - - -<br />

LI - - 38705 38710 - -<br />

LSI - - - - 38706 38711<br />

LSIG - - - - 38707 38712<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/24


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S5 (630A)<br />

Protection types available<br />

Electronic L S I G<br />

Type<br />

Settings<br />

PR211/LI 0.4-1x In - 1.5-12x In -<br />

PR212/LSI 0.4-1x In 1-10x In 1.5-12x In -<br />

PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70-100% 5-10x Ith<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection Thermomagnetic PR211 PR212<br />

Ith 1SDA0 R1<br />

100kA S5L400R320 320A<br />

100kA S5L400R400 400A<br />

100kA S5L630R500 500A<br />

100kA S5L630R630 630A<br />

Plug-in / Withdrawable <strong>Circuit</strong> breakers / Disconnectors<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

T/Mag 38606 38608 - - - -<br />

LI - - 18256 18388 - -<br />

LSI - - - - 18258 18390<br />

LSIG - - - - 18264 18396<br />

T/Mag 38607 38609 - - - -<br />

LI - - 18257 18389 - -<br />

LSI - - - - 18259 18391<br />

LSIG - - - - 18265 18397<br />

T/Mag 38740 38745 - - - -<br />

LI - - - - - -<br />

LSI - - - - - -<br />

LSIG - - - - - -<br />

T/Mag - - - - - -<br />

LI - - 38737 38742 - -<br />

LSI - - - - 38738 38743<br />

LSIG - - - - 38739 38744<br />

400A 400A 630A<br />

plug-in withdrawable withdrawable<br />

1SDA0<br />

R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

Conversion Kit 13716 13717 13718 13719 38778 38779<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals (400A) 13724 13733 13742 13751 - -<br />

Extended Front bar Terminals 13720 13729 13738 13747 - -<br />

Spreaded Ext Front bar Terminals - - - - 38761 38762<br />

Threaded Rear Terminals 13728 13737 13746 13755 38763 38970<br />

Vertical Flat bar Terminals - - - - 38971 38972<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/25


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S6 (800A)<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

S6D - - 15kA<br />

S6N 35kA 100% 7.6kA (630A) 10kA (800A)<br />

S6S 50kA 100% 7.6kA (630A) 10kA (800A)<br />

S6H 65kA 100% 7.6kA (630A) 10kA (800A)<br />

S6L100kA 75% 7.6kA (630A) 10kA (800A)<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR211 PR212<br />

Ith 1SDA0 R1<br />

35kA S6N630R630 630A<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

T/Mag 38787 38788 - - - -<br />

LI - - 18519 18573 - -<br />

LSI - - - - 18520 18574<br />

LSIG - - - - 18523 18577<br />

T/Mag 38871 38872 - - - -<br />

35kA S6N800R800 800A LI - - 18951 19005 - -<br />

50kA S6S630R630 630A<br />

50kA S6S800R800 800A<br />

65kA S6H630R630 630A<br />

65kA S6H800R800 800A<br />

LSI - - - - 18952 19006<br />

LSIG - - - - 18955 19009<br />

T/Mag 38799 38800 - - - -<br />

LI - - 18627 18681 - -<br />

LSI - - - - 18628 18682<br />

LSIG - - - - 18631 18685<br />

T/Mag 38883 38884 - - - -<br />

LI - - 19059 19113 - -<br />

LSI - - - - 19060 19114<br />

LSIG - - - - 19063 19117<br />

T/Mag 38823 38824 - - - -<br />

LI - - 18735 18789 - -<br />

LSI - - - - 18736 18790<br />

LSIG - - - - 18739 18793<br />

T/Mag 38907 38908 - - - -<br />

LI - - 19167 19221 - -<br />

LSI - - - - 19168 19222<br />

LSIG - - - - 19171 19225<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/26


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S6 (800A)<br />

Protection types available<br />

Electronic L S I G<br />

Type<br />

Settings<br />

PR211/LI 0.4-1x In - 1.5-12x In -<br />

PR212/LSI 0.4-1x In 1-10x In 1.5-12x In -<br />

PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70-100% 5-10x Ith<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR211 PR212<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

T/Mag 38847 38848 - - - -<br />

100kA S6L630R630 630A<br />

LI - - 18843 18897 - -<br />

LSI - - - - 18844 18898<br />

LSIG - - - - 18847 18901<br />

T/Mag 38931 38932 - - - -<br />

100kA S6L800R800 800A<br />

LI - - 19275 19329 - -<br />

LSI - - - - 19276 19330<br />

LSIG - - - - 19279 19333<br />

Fixed Pattern Switch Disconnector<br />

lcw (1 sec) Model Current (A)<br />

Iu 1SDA0 R1<br />

3 Pole 4 Pole<br />

S6D400 400A 20545 20581<br />

15kA S6D630 630A 20674 20699<br />

Withdrawable <strong>Circuit</strong> breakers<br />

S6D800 800A 20724 20749<br />

To convert fixed pattern device to withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator<br />

Padlock Device<br />

Rotary Handle<br />

c). Remember to use accessories suitable for withdrawable pattern devices<br />

1SDA0<br />

Withdrawable 3 Pole 4 Pole<br />

Conversion Kit 13962 13963<br />

Fixed portion (Base)<br />

Extended Front bar Terminals 13964 13973<br />

Horizontal Flat bar Terminals 13968 13977<br />

Vertical Flat bar Terminals 13972 13981<br />

R1<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/27


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S7 (1250A)<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

S7S 50kA 100% 15kA (1250A) 20kA (1600A)<br />

S7H 65kA 75% 15kA (1250A) 20kA (1600A)<br />

S7L 100ka 50% 15kA (1250A) 20kA (1600A)<br />

S7D - - 25kA<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection PR211 PR212<br />

In 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 19384 19492 - -<br />

50kA S7S1250R1000 1000A LSI - - 19386 19494<br />

LSIG - - 19392 19500<br />

LI 19385 19493 - -<br />

50kA S7S1250R1250 1250A LSI - - 19387 19495<br />

LSIG - - 19393 19501<br />

LI 20031 20073 - -<br />

50kA S7S1600R1600 1600A LSI - - 20032 20074<br />

LSIG - - 20035 20077<br />

LI 19600 19708 - -<br />

65kA S7H1250R1000 1000A LSI - - 19602 19710<br />

LSIG - - 19608 19716<br />

LI 19601 19709 - -<br />

65kA S7H1250R1250 1250A LSI - - 19603 19711<br />

LSIG - - 19609 19717<br />

LI 20115 20157 - -<br />

65kA S7H1600R1600 1600A LSI - - 20116 20158<br />

LSIG - - 20119 20161<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/28


Distribution and Generator Protection MCCBs<br />

<strong>Isomax</strong> S7 (1250A)<br />

Protection types available<br />

Electronic L S I G<br />

Type<br />

Settings<br />

PR211/LI 0.4-1x In 1.5-12x In<br />

PR212/LSI 0.4-1x In 1-10xIn 1.5-12x In<br />

PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Protection PR211 PR212<br />

In 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 19816 19924 - -<br />

100kA S7L1250R1000 1000A LSI - - 19818 19926<br />

LSIG - - 19824 19932<br />

LI 19817 19925 - -<br />

100kA S7L1250R1250 1250A LSI - - 19819 19927<br />

LSIG - - 19825 19933<br />

LI 20199 20241 - -<br />

100kA S7L1600R1600 1600A LSI - - 20200 20242<br />

LSIG - - 20203 20245<br />

Fixed Pattern Switch Disconnector<br />

lcw (1 sec) Model Current (A)<br />

Iu 1SDA0 R1<br />

3 Pole 4 Pole<br />

S7D1000 1000A 20774 20799<br />

25kA S7D1250 1250A 20824 20849<br />

Withdrawable <strong>Circuit</strong> breakers<br />

S7D1600 1600A 20874 20890<br />

To convert fixed pattern device to withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator<br />

Padlock Device<br />

Rotary Handle<br />

c). Remember to use accessories suitable for withdrawable pattern devices<br />

1SDA0<br />

Withdrawable 3 Pole 4 Pole<br />

Conversion Kit 23299 14087<br />

Fixed portion (Base)<br />

Extended Front bar Terminals 48951 14097<br />

Horizontal Flat bar Terminals 14092 14101<br />

Vertical Flat bar Terminals 14096 14105<br />

R1<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/29


Accessories <strong>Tmax</strong> T1, T2 and T3<br />

1). Electrical Accessories<br />

a). Shunt Opening Releases ( cabled version)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

12V DC 53001<br />

24…30 AC 51339 24…30V DC 51339<br />

48…60V AC 51340 48…60V DC 51340<br />

110…127V AC 51341 110…125V DC 51341<br />

220…240V AC 51342 220…250V DC 51342<br />

380…440V AC 51343<br />

480…500V AC 51344<br />

b). Undervoltage Release (UVR) (cabled Version)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

24…30V AC 51351 24…30V DC 51351<br />

48V AC 51352 48V DC 51352<br />

60V AC 52335 60V DC 52335<br />

110…127V AC 51353 110…127V DC 51353<br />

220…240V AC 51354 220…250V DC 51354<br />

380…440V AC 51355<br />

480…500V AC 51356<br />

c). Time lag device for UVR (UVD)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

24V AC 51357 24V DC 51357<br />

48V AC 51358 48V DC 51358<br />

60V AC 51359 60V DC 51359<br />

110…125V AC 51360 110…125V DC 51360<br />

220…250V AC 51361 220…250V DC 51361<br />

a) b) c)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/30


Accessories <strong>Tmax</strong> T1, T2 and T3<br />

1). Electrical Accessories cont....<br />

d). Solenoid operator (inc padlock device)<br />

Voltage 1SDA0 R1 1SDA0 R1<br />

Front Fitting Side by Side<br />

48…60V DC 51376 51379<br />

110…250V AC 51377 51380<br />

e). Auxiliary Contacts (cabled version)<br />

ON/OFF Tripped Release Breaker Protection 1SDA0 R1<br />

(c/o) Position (c/o) Tripped (c/o) Type<br />

1 1 Thermomagnetic 51370<br />

1 1 1 Electronic 53704<br />

3 1 Thermomagnetic 51371<br />

f). Residual - current releases<br />

RC221 and RC222 addon blocks<br />

<strong>Breakers</strong> must be fitted with Front cable terminals for copper cables on lower terminals<br />

( Terminal kit supplied with RCD addon kit for T2 and T3)<br />

1SDA0 R1 1SDA0 R1<br />

Breaker Type RC221 RC222<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

T1 51398 51401 51400 51402<br />

T2 51403 51405 51404 51406<br />

T3 51407 51409 51408 51410<br />

d)<br />

e)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/31


Accessories <strong>Tmax</strong> T1, T2 and T3<br />

2). Mechanical Accessories<br />

a). Direct Mounted Rotary Handles (RHD)<br />

For Fixed/Plug-in devices - Grey/White<br />

For Fixed/Plug-in devices - Red/Yellow<br />

1SDA051381R1<br />

1SDA051382R1<br />

b). Door Mounted Rotary Handles (complete with transmission rod Lmax = 300mm) (RHE)<br />

• Adjustable depth<br />

• Padlockable<br />

• Complete with Door Interlock ( defeatable)<br />

For Fixed/Plug-in devices - Grey/White<br />

For Fixed/Plug-in devices - Red/Yellow<br />

500mm transmission rod<br />

Optional Keylock<br />

IP54 Gasket<br />

1SDA051383R1<br />

1SDA051384R1<br />

1SDA051386R1<br />

1SDA051389R1<br />

1SDA051392R1<br />

c). Padlock Lever lock (PLL)<br />

Padlock in OPEN Position<br />

Padlock in OPEN/CLOSED<br />

1SDA051393R1<br />

1SDA051394R1<br />

d). Mechanical Interlock across Two/ Three circuit breakers (MIF)<br />

Between 2 circuit breakers<br />

Between 3 <strong>Circuit</strong> <strong>Breakers</strong><br />

1SDA051396R1<br />

1SDA052165R1<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/32


Accessories <strong>Tmax</strong> T1, T2 and T3<br />

2). Mechanical Accessories Cont....<br />

e). Terminals for fixed pattern MCCBs and Plug-in Bases<br />

1SDA0 R1<br />

Terminal Type T1 T2 T3<br />

6 pieces 8 pieces 6 pieces 8 pieces 6 pieces 8 pieces<br />

Extended Front (EF) 51440 51441 51464 51465 51488 51489<br />

Spreaded Extended (ES) - - 51468 51469 51492 51493<br />

Rear Terminals (R) - - 51472 51473 51496 51497<br />

Copper Front Cable terminals (FC Cu): Std Std 51452 51453 51480 51481<br />

Cu/Al Front Cable terminals (FC CuAl):<br />

1x95mm 2 External 51444 51445 - - - -<br />

1x95mm 2 Internal - - 51456 51457 - -<br />

1x185mm 2 External - - 51460 51461 - -<br />

1x185mm 2 Internal - - - - 51484 51485<br />

140…240mm 2 External - - - - 51942 51943<br />

f). Terminal covers<br />

1SDA0 R1<br />

MCCB No of poles High Low<br />

T1<br />

3 poles 51415 51421<br />

4 poles 51416 51422<br />

T2<br />

3 poles 51417 51423<br />

4 poles 51418 51424<br />

T3<br />

3 poles 51419 51425<br />

4 poles 51420 51426<br />

g). Separating Partitions (PB)<br />

Height Qty 1SDA0 R1<br />

100mm 4 51427<br />

100mm 6 51428<br />

200mm 4 51429<br />

200mm 6 51430<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/33


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

1). Electrical Accessories<br />

a). Shunt Trip<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

12V DC 23403<br />

24V AC 13781 24V DC 13781<br />

48V AC 13782 48V DC 13782<br />

60V AC 23405 60…72V DC 23405<br />

110…120V AC 13783 110…125V DC 13783<br />

220…240V AC 13785 220…250V DC 13785<br />

380…400V AC 13786<br />

480V AC 37512<br />

Wiring Connector: Fixed pattern devices 13865<br />

Wiring Connector: Plug-in/Withdrawable devices 13866<br />

b). Undervoltage Release (UVR)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

24V AC 13842 24V DC 13833<br />

48V AC 13843 48V DC 13835<br />

60V AC 23346 60V DC 13836<br />

110…127V AC 13844 110…125V DC 13838<br />

220…250V AC 13846 220…250V DC 13839<br />

380…440V AC 13847<br />

480V AC 37513<br />

Wiring Connector: Fixed pattern devices 13865<br />

Wiring Connector: Plug-in/Withdrawable devices 13866<br />

c). UVR + Time Lag Device 1SDA0 R1<br />

UVR + Delay: S3/S5 Input voltage 110…220V AC only 13840<br />

UVR + Delay: S6/S7 Input voltage 110…220V AC only 14186<br />

Wiring Connector: Fixed pattern devices 13865<br />

Wiring Connector: Plug-in/Withdrawable devices 13866<br />

a) b) c)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/34


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

d). Direct acting Motor operator (inc padlock device)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

110…127V AC 13875 24V DC 13873<br />

220…240V AC 13876 48…60V DC 13874<br />

380V AC 13877 110…125V DC 13875<br />

440V AC 14545 220...250V DC 13876<br />

e). Auxiliary Contacts<br />

ON/OFF (c/o) Tripped position (c/o) Signal type 1SDA0 R1<br />

1 1 Analogue (>24V) 13575<br />

1 1 Digital (24V) 13856<br />

2 0 Digital (


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

1). Electrical Accessories cont....<br />

f). Protection Release Trip Signal<br />

X3/X4 Connector<br />

Pattern Protection Type 1SDA0 R1<br />

PR211/LI 13702<br />

Fixed pattern PR212/LSI 13704<br />

PR212/LSIG 13704<br />

PR211/LI 13703<br />

Plug-in/Withdrawable PR212/LSI 13705<br />

PR212/LSIG 13705<br />

g). External Neutral Current Transformer<br />

MCCB Current Rating 1SDA0 R1<br />

100A 37114<br />

S4 160A 37115<br />

250A 37117<br />

320A 37118<br />

S5 400A 37119<br />

630A 37120<br />

Connector for Neutral CT<br />

Pattern Protection Type 1SDA0 R1<br />

PR211/LI 13702<br />

Fixed pattern PR212/LSI 13704<br />

PR212/LSIG 13704<br />

PR211/LI 13703<br />

Plug-in/Withdrawable PR212/LSI 13705<br />

PR212/LSIG 13705<br />

h). Residual-current release RC211 and RC212<br />

Type Vertical Mount Side/side Mount<br />

1SDA0 R1<br />

RC211-S3 20289 20288<br />

RC212-S3 20291 20290<br />

RC211 and RC212 add on blocks for S3 breaker<br />

Fitting by our workshop is recommended<br />

4 pole circuit breaker/switch disconnector required<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/36


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

2). Mechanical Accessories<br />

a). Direct Mounted Rotary Handles<br />

1SDA0<br />

For Fixed/Plug-in devices - Grey/White 13867<br />

For Fixed/Plug-in devices - Red/Yellow 13870<br />

For Withdrawable devices - Grey/White 13868<br />

R1<br />

b). Door Mounted Rotary Handles ( complete with transmission rod L max = 300mm)<br />

Adjustable depth, Padlockable, complete with Door Interlock ( defeatable) 1SDA0 R1<br />

For Fixed/Plug-in devices - Grey/White 13869<br />

For Fixed/Plug-in devices - Red/Yellow 13871<br />

For Withdrawable devices - Grey/White 50714<br />

500mm transmission rod 25427<br />

Optional Keylock 13881<br />

IP54 Gasket 13891<br />

c). Front Flange<br />

Padlockable 1SDA0 R1<br />

Fixed/ Plug-in devices 13889<br />

Withdrawable devices 13890<br />

Optional Keylock 13881<br />

d). Mechanical Interlock across two circuit breakers<br />

MCCB Horizontal Vertical<br />

1SDA0 R1<br />

S3 23330 23331<br />

S4 13690 13691<br />

S5 43453 43454<br />

S3X 50524 -<br />

S4X 50525 -<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/37


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

2). Mechanical Accessories Cont....<br />

e). Terminal for Fixed Pattern MCCBs<br />

Terminal kits consist of 6 or 8 pieces<br />

kits of 3 or 4 pieces are available - consult technical catalogue for order references<br />

Terminal Type Max 1SDA0 R1<br />

Current S3 S4 S5<br />

Extended Front (EF)<br />

6 pcs 8 pcs 6 pcs 8 pcs 6 pcs 8 pcs<br />

250A 13596 13597 13596 13597 - -<br />

400A - - - - 13706 13707<br />

Spreaded Extended (ES) 46515 46516 46515 46516 47549 47550<br />

250A 13606 13607 13606 13607 - -<br />

Threaded rear stud (R) 400A - - - - 13714 13715<br />

630A - - - - 38968 38775<br />

250A 13598 13599 13598 13599 - -<br />

Copper Front Cable terminals (FC Cu) 400A - - - - 13708 13709<br />

630A - - - - 38767 38768<br />

Cu/Al Front Cable terminals (FC CuAl) :<br />

1x95mm 2 160A 13602 13603 13602 13602 - -<br />

1x150mm 2 250A 20293 20294 20293 20294 - -<br />

2x120mm 2 400A - - - - 23295 23296<br />

1x240mm 2 400A - - - - 13710 13711<br />

Cu/Al Rear cable terminals (RC CuAl)<br />

1x120mm 2 250A 13604 13605 13604 13605 - -<br />

1x240mm 2 400A - - - - 13712 13713<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/38


Accessories <strong>Isomax</strong> S3, S4 and S5<br />

2). Mechanical Accessories Cont....<br />

f). Terminals for Plug-in and Withdrawable Bases<br />

Terminal kits consist of 6 or 8 pieces<br />

Terminal Type Max Current 1SDA0 R1<br />

S3 S4 S5<br />

6 pcs 8 pcs 6 pcs 8 pcs 6 pcs 8 pcs<br />

250A 13650 13651 13650 13651 - -<br />

Extended Front (EF) 400A - - - - 13759 13760<br />

630A - - - - 38780 38781<br />

250A 13654 13655 13654 13655 - -<br />

Threaded rear stud (R) 400A - - - - 13763 13764<br />

630A - - - - 38969 38782<br />

Cu/Al Front Cable terminals (FC CuAl) :<br />

250A 13652 13653 13652 13653 - -<br />

400A - - - - 13760 13762<br />

Vertical Flat Bar terminals (VR) 630A - - - - 38763 38784<br />

g). Terminal Covers<br />

Types available<br />

High:<br />

Low:<br />

FP High:<br />

For fixed pattern devices<br />

For Fixed pattern devices and for Moving parts of Plug-in and Withdrawable devices<br />

For Plug-in and Withdrawable Bases<br />

1SDA0 R1<br />

MCCB No of poles High Low FP High<br />

S3<br />

3 poles 13695 13693 13697<br />

4 poles 13696 13694 13698<br />

S4<br />

3 poles 13695 13693 13697<br />

4 poles 13696 13694 13698<br />

S5<br />

3 poles 13897 13895 13899<br />

4 poles 13898 13896 13900<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/39


Accessories <strong>Isomax</strong> S6 and S7<br />

1). Electrical Accessories<br />

a). Shunt Trip<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

12V DC 23404<br />

24V AC 14136 24V DC 14136<br />

48V AC 14137 48V DC 14137<br />

60V AC 23406 60…72V DC 23406<br />

110…120V AC 14138 110…125V DC 14138<br />

220…240V AC 14140 220…250V DC 14140<br />

380…400V AC 14141<br />

480V AC 37512<br />

Shunt trip Wiring Connector<br />

Fixed pattern devices<br />

Plug-in/Withdrawable<br />

S6 13865<br />

S7 14209<br />

S6 13866<br />

S7 14210<br />

b). Undervoltage Release (UVR)<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

24V AC 14188 24V DC 14179<br />

48V AC 14189 48V DC 14181<br />

60V AC 23347 60V DC 14182<br />

110…127V AC 14190 110…125V DC 14184<br />

220…250V AC 14192 220…250V DC 14185<br />

380…440V AC 14193<br />

480V AC 37515<br />

UVR Wiring Connector<br />

Fixed pattern devices<br />

Plug-in/Withdrawable<br />

S6 13865<br />

S7 14209<br />

S6 13866<br />

S7 14210<br />

a) b)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/40


Distribution and Generator Protection MCCBs<br />

Accessories <strong>Isomax</strong> S6 and S7<br />

1). Electrical Accessories cont...<br />

c). UVR + Time Lag Device<br />

1SDA0 R1<br />

UVR + Delay: Input voltage 110…220V AC only 14186<br />

Wiring Connector:<br />

Fixed pattern devices<br />

Plug-in/Withdrawable<br />

S6 13865<br />

S7 14209<br />

S6 13866<br />

S7 14210<br />

d). Stored Energy Motor operator<br />

AC Voltage 1SDA0 R1 DC Voltage 1SDA0 R1<br />

S6 S7 S6 S7<br />

24V DC 14029 14214<br />

48V DC 14030 14215<br />

60V DC 23348 23350<br />

110…127V AC 14031 14216 110…125V DC 14031 14216<br />

220…250V AC 14032 14217 220…250V DC 14032 14217<br />

380V AC 14033 14218<br />

Motor Op Wiring Connector<br />

Fixed pattern devices<br />

Plug-in/Withdrawable<br />

S6 13857<br />

S7 14203<br />

S6 13858<br />

S7 14204<br />

Optional Keylock<br />

Lock against manual and electrical operation S6/S7 13885<br />

c)<br />

d)<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/41


Distribution and Generator Protection MCCBs<br />

Accessories <strong>Isomax</strong> S6 and S7<br />

1). Electrical Accessories cont....<br />

e). Auxiliary Contacts<br />

On/Off Tripped pos On/Off Tripped position Signal type<br />

(c/o) (c/o) (1no & 1nc) (no) 1SDA0 R1<br />

1 1 Analogue (>24V) 23332<br />

1 1 Digital (24V) 23366<br />

2 0 Digital (24V) 48956<br />

1 1 Digital (


Distribution and Generator Protection MCCBs<br />

Accessories <strong>Isomax</strong> S6 and S7<br />

1). Electrical Accessories Cont....<br />

g). External Neutral Current Transformer<br />

MCCB Current Rating 1SDA0 R1<br />

S6<br />

630A 25777<br />

800A 25778<br />

1000A 25779<br />

S7 1250A 25780<br />

1600A 25781<br />

X3/X4 Connector<br />

Pattern Protection Type 1SDA0 R1<br />

PR211/LI 13702<br />

Fixed pattern PR212/LSI 13704<br />

PR212/LSIG 13704<br />

PR211/LI 13703<br />

Plug-in/Withdrawable PR212/LSI 13705<br />

PR212/LSIG 13705<br />

2). Mechanical Accessories<br />

a). Direct Mounted Rotary Handles<br />

1SDA0 R1<br />

TypeColour S6 S7<br />

For Fixed/Plug-in devices<br />

Grey/White 14026 14211<br />

Red/Yellow 14027 14212<br />

For Withdrawable devices - Grey/White Grey/White 46568 46570<br />

b). Door Mounted Rotary Handles ( complete with transmission rod L max = 500mm)<br />

Adjustable depth padlockable, complete with door interlock ( defeatable) 1SDA0 R1<br />

Type Colour S6 S7<br />

For Fixed/Plug-in devices<br />

Grey/White 14028 14213<br />

Red/Yellow 46569 46572<br />

For Withdrawable devices - Grey/White Grey/White 50715 50716<br />

Optional Keylock 13881<br />

IP54 Gasket 13891<br />

c). Front Flange<br />

1SDA0 R1<br />

Padlockable S6 S7<br />

Fixed/ Plug-in devices 14035 14227<br />

Withdrawable devices 14036 14228<br />

Optional Keylock 13881<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/43


Accessories <strong>Isomax</strong> S6 and S7<br />

2). Mechanical Accessories Cont....<br />

d). Mechanical Interlock across two circuit breakers<br />

MCCB Horizontal Vertical<br />

1SDA0 R1<br />

S6 14024 14025<br />

S7 14205 14206<br />

e). Terminals for fixed pattern MCCBs<br />

Terminal kits consist of 6 or 8 pieces<br />

kits of 3 or 4 pieces are available - consult technical catalogue for order references<br />

Terminal Type<br />

S6<br />

Max Current<br />

1SDA0 R1<br />

S7<br />

6 pcs 8 pcs 6 pcs 8 pcs<br />

630A 13920 13921 - -<br />

Extended Front (EF) 800A 13954 13955 - -<br />

1600A - - 14079 14080<br />

Spreaded Extended (ES) 1600A - - 50690 50691<br />

Threaded rear stud (R) 800A 13960 13961 - -<br />

Cu/Al Front Cable terminals (FC CuAl)<br />

2x240mm 2 630A 13922 13923 - -<br />

3x185mm 2 800A 13956 13957 - -<br />

4x240mm 2 1250A - - 14081 14082<br />

Cu/Al Rear cable terminals (RC CuAl)<br />

2x150mm 2 630A 13924 13925 - -<br />

3x240mm 2 800A 13958 13959 - -<br />

Horizontal/Vertical Flat Bar terms (HR/VR)<br />

1600A - - 14083 14084<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/44


<strong>SACE</strong> <strong>Isomax</strong> S circuit-breakers for<br />

motor protection (protection against short-circuit)<br />

Three-phase asynchronous motor starting, switching and protection are essential operations for its correct use. The traditional system<br />

used for this purpose has three different devices: a circuit-breaker for protection against short-circuit, a thermal relay for protection<br />

against overload and lack of or unbalanced phase, and a counter for the motor operations. Everything must necessarily take into account<br />

the problems which arise on start-up.<br />

In particular, these different factors must be taken into account when selecting these devices, such as:<br />

- the motor power<br />

- the starting diagram<br />

- the type of motor: with cage rotor or with wound rotor<br />

- the fault current at the point of motor installation in the network<br />

ABB <strong>SACE</strong>proposes a wide range of circuit-breakers, which by implementing the protection against short-circuit exclusively, are suitable<br />

for use inside protected starters of traditional type.<br />

The new <strong>SACE</strong> T2 with fixed magnetic protection is an extremely compact circuit-breaker, which stands out for its exceptional performances<br />

in terms of breaking capacity and limitation of the specific let-through energy.<br />

It can be used in a vast range of start-ups, from 0.37kW to 37kW and from 400V-50kA up to 690V-50kA. <strong>SACE</strong> S3 N/H/L 160/250 circuit<br />

breakers and the S3X 125/200 current-limiting circuit-breaker are fitted with a magnetic only release adjustable from 4 to 12 time the rated<br />

service current. They cover coordinations from 37 to 132kW and allow optimal motor protection thanks to their great flexibility due to the<br />

wide setting range of the magnetic threshold.<br />

Finally, <strong>SACE</strong>S4 160/250, S5 400/630, S6 630/800, and S7 1250/1600, with different capacity levels, like the current-limiting S4X and<br />

S6X, can be fitted with the PR211/P (I) electronic microprocessor-based release. Above all, they are used for protection of high power<br />

motors and, thanks to adjustment of the protection against short-circuit from 1.5 to 12 times, allow the optimumtrip value to be selected<br />

for any motor type.<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/46


www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/47


Motor Protection MCCBs<br />

<strong>Tmax</strong> T2N (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2N 36kA 100%<br />

T2S 50kA 100%<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

In MF MA PR221DS/I<br />

3 Pole 3 Pole 3 Pole 4 Pole<br />

T2N160R1 1A 53110 - - -<br />

T2N160R1.6 1.6A 53111 - - -<br />

T2N160R2 2A 53112 - - -<br />

T2N160R2.5 2.5A 53113 - - -<br />

T2N160R3.2 3.2A 53114 - - -<br />

T2N160R4 4A 53115 - - -<br />

T2N160R5 5A 53116 - - -<br />

T2N160R6.5 6.5A 53117 - - -<br />

T2N160R8.5 8.5A 53118 - - -<br />

36kA T2N160R10 10A - - 51163 51169<br />

T2N160R11 11A 53119 - -<br />

T2N160R12.5 12.5A 53120 - - -<br />

T2N160R20 20A - 51207 - -<br />

T2N160R25 25A - - 51164 51170<br />

T2N160R32 32A - 51208 - -<br />

T2N160R52 52A - 51209 - -<br />

T2N160R63 63A - - 51165 51171<br />

T2N160R80 80A - 51210 - -<br />

T2N160R100 100A - 51211 51166 51172<br />

T2N160R160 160A - - 51168 51617<br />

for accessories see page x/xx<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/48


Motor Protection MCCBs<br />

<strong>Tmax</strong> T2S (160A)<br />

Protection types available<br />

Type<br />

Settings<br />

Electronic L S<br />

PR221DS/I<br />

Magnetic Only<br />

Fixed Magnetic (MF)<br />

Adjustable Magnetic (MA)<br />

1 - 10x In<br />

Im<br />

13x In<br />

6…12x In<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

In MF MA PR221DS/I<br />

3 Pole 3 Pole 3 Pole 4 Pole<br />

T2S160R1 1A 53121 - - -<br />

T2S160R1.6 1.6A 53122 - - -<br />

T2S160R2 2A 53123 - - -<br />

T2S160R2.5 2.5A 53124 - - -<br />

T2S160R3.2 3.2A 53125 - - -<br />

T2S160R4 4A 53126 - - -<br />

T2S160R5 5A 53127 - - -<br />

T2S160R6.5 6.5A 53128 - - -<br />

50kA T2S160R8.5 8.5A 53129 - - -<br />

T2S160R10 10A - - 51174 51179<br />

T2S160R11 11A 53130 - - -<br />

T2S160R12.5 12.5A 53131 - - -<br />

T2S160R20 20A - 51216 - -<br />

T2S160R25 25A - - 51175 51180<br />

T2S160R32 32A - 51217 - -<br />

T2S160R52 52A - 51218 - -<br />

T2S160R63 63A - - 51176 51181<br />

T2S160R80 80A - 51219 - -<br />

T2S160R100 100A - 51220 51177 51182<br />

T2S160R160 160A - - 51178 51618<br />

for accessories see page x/xx<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/49


Motor Protection MCCBs<br />

<strong>Tmax</strong> T3 (250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T3N 36kA 75%<br />

T3S 50kA 50%<br />

Protection types available<br />

Type<br />

Magnetic Only<br />

Adjustable Magnetic (MA)<br />

Settings<br />

6…12x In<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals see<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

Ith MA 3 Pole<br />

36kA<br />

T3N250R100 100A 51315<br />

T3N250R125 125A 51316<br />

T3N250R160 160A 51317<br />

T3N250R200 200A 51318<br />

50kA<br />

T3S250R100 100A 51320<br />

T3S250R125 125A 51321<br />

T3S250R160 160A 51322<br />

T3S250R200 200A 51323<br />

Plug-in <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

1SDA0 R1<br />

Plug-in 3 Pole 4 Pole<br />

Conversion Kit 51413 51414<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51331 51332<br />

**for other terminals see accessories section pagexx<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/50


Accessories <strong>Isomax</strong> S6 and S7<br />

2). Mechanical Accessories Cont....<br />

f). Terminals for Plug-in and Withdrawable Bases<br />

Terminal kits consist of 6 or 8 pieces<br />

Terminal Type Max Current 1SDA0 R1<br />

S6<br />

S7<br />

6 pieces 8 pieces 6 pieces 8 pieces<br />

Extended Front (EF)<br />

800A 13984 13985 - -<br />

1600A - - 14108 14109<br />

Horizontal Flat Bar (HR)<br />

800A 13986 13987 - -<br />

1600A - - 14110 14111<br />

Vertical Flat Bar terminals (VR)<br />

800A 13988 13989 - -<br />

1600A - - 14112 14113<br />

g). Terminal Covers<br />

Types available<br />

High:<br />

Low:<br />

FP High:<br />

For fixed pattern devices<br />

For Fixed pattern devices and for Moving parts of Plug-in and<br />

Withdrawable devices<br />

For Plug-in and Withdrawable Bases<br />

1SDA0 R1<br />

MCCB No of poles High Low FP High<br />

S6<br />

3 poles 14040 14038 -<br />

4 poles 14041 14039 -<br />

S7<br />

3 poles - 23324 -<br />

4 poles - 23325 -<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/45


Motor Protection MCCBs<br />

<strong>Isomax</strong> S3N, H, L (250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S3N 35kA 100%<br />

S3H 65kA 75%<br />

S3L 85kA 75%<br />

All breakers are Magnetic Only with adjustable<br />

settings AVAILABLE IN 3 POLE ONLY<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

I m<br />

3 Pole<br />

S3N160RM3 12…36A 47782<br />

S3N160RM5 20…60A 47783<br />

S3N160RM10 40…120A 47784<br />

S3N160RM25 100…300A 47785<br />

S3N160RM50 200…600A 47786<br />

35kA S3N160RM100 400…1200A 47787<br />

S3N160RM125 500…1500A 47788<br />

S3N160RM160 640…1600A 47789<br />

S3N250RM160 640…1920A 48651<br />

S3N250RM200 800…2400A 48654<br />

65kA<br />

S3H160RM50 200…600A 45185<br />

S3H160RM100 400…1200A 45186<br />

S3H160RM125 500…1500A 45187<br />

S3H160RM160 640…1600A 45188<br />

S3H250RM160 640…1920A 48657<br />

S3H250RM200 800…2400A 48658<br />

85kA<br />

S3L160RM50 200…600A 50544<br />

S3L160RM100 400…1200A 50545<br />

S3L160RM125 500…1500A 50546<br />

S3L160RM160 640…1600A 50547<br />

S3L250RM160 640…1920A 50548<br />

S3L250RM200 800…2400A 50549<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/51


Motor Protection MCCBs<br />

<strong>Isomax</strong> S3X (250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S3X 200kA 100%<br />

All breakers are Magnetic Only with adjustable<br />

settings AVAILABLE IN 3 POLE ONLY<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

I m<br />

3 Pole<br />

S3X125RM25 100…300A 45387<br />

S3X125RM50 200…600A 45388<br />

S3X125RM100 400…1200A 45389<br />

200kA S3X125RM125 500…1500A 45390<br />

S3X200RM125 500…1500A 46135<br />

S3X200RM160 640…1920A 48659<br />

S3X200RM200 800…2400A 48660<br />

Plug-in and Withdrawable <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator<br />

Padlock Device<br />

Rotary Handle<br />

b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices<br />

Plug-in<br />

Withdrawable<br />

1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole<br />

Conversion Kit 46519 46520 46521 46522<br />

Fixed<br />

Front Copper Cable Terminals 13543 13550 13559 13568<br />

Extended Front bar Terminals 13539 13548 13555 13564<br />

Threaded Rear Terminals 13547 13554 13563 13572<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/52


Motor Protection MCCBs<br />

<strong>Isomax</strong> S4N, H, L, X (250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S4N 35kA 100%<br />

S4H 65kA 100%<br />

S4L 100kA 75%<br />

S4X 200kA 100%<br />

Protection types available<br />

Electronic (ac only)<br />

Type<br />

Settings<br />

L R I U<br />

PR212/I - - 1.5 - 12x In -<br />

PR212/LR 0.4 - 1x In 3 - 10x In 6 - 12x In ON/OFF<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

Ith PR211/I PR212/LRIU<br />

35kA<br />

3 Pole 4 Pole 3 Pole Only<br />

S4N160R100 100A 15548 15836 50139<br />

S4N160R160 160A 15549 15837 50140<br />

S4N250R200 200A - - 50141<br />

S4N250R250 250A 17318 17384 -<br />

65kA<br />

S4H160R100 100A 16142 16424 45049<br />

S4H160R160 160A 16143 16425 45050<br />

S4H250R200 200A - - 48662<br />

S4H250R250 250A 17450 17516 -<br />

100kA<br />

S4L160R100 100A 16730 17012 50550<br />

S4L160R160 160A 16731 17013 50551<br />

S4L250R200 200A - - 50552<br />

S4L250R250 250A 17582 17648 -<br />

S4X250R100 100A - - 46590<br />

200kA S4X250R160 160A - - 46591<br />

S4X250R200 200A - - 48661<br />

Plug-in and Withdrawable <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator, Padlock Device, Rotary Handle<br />

b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices<br />

Plug-in<br />

Withdrawable<br />

S4N/H/L S4X S4N/H/L S4X<br />

3 Pole 4 Pole 3Pole 3 Pole 4 Pole 3Pole<br />

Conversion Kit 13608 13609 46511 13610 13611 46521<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals - 13543 13550 13634 13643 -<br />

Extended Front bar Terminals - 13612 13621 13630 13639 -<br />

Threaded Rear Terminals - 13547 13554 13638 13647 -<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/53


Motor Protection MCCBs<br />

<strong>Isomax</strong> S5 (630A)<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

S5N 35kA 100% 5kA<br />

S5H 65kA 100% 5kA<br />

S5L 100kA 75% 5kA<br />

Protection types available<br />

Electronic (ac only)<br />

Type<br />

Settings<br />

L R I U<br />

PR211/I 0.4-1x In 1.5-12x In<br />

PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

Ith PR211/I PR212/LRIU<br />

3 Pole 4 Pole 3 Pole Only<br />

S5N400R320 320A 17714 17846 50142<br />

35kA S5N400R400 400A 17715 17847 -<br />

S5N630R630 630A 38674 38679 -<br />

S5H400R320 320A 17990 18122 45051<br />

65kA S5H400R400 400A 17991 18123 -<br />

S5H630R630 630A 38704 38709 -<br />

S5L400R320 320A 18254 18386 50553<br />

100kA S5L400R400 400A 18255 18387 -<br />

S5L630R630 630A 38736 38741 -<br />

Plug-in and Withdrawable <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to plug-in or withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a). Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator, padlock device, rotary handle<br />

b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices<br />

400A<br />

630A<br />

1SDA0 R1 1SDA0 R1<br />

Plug-in Withdrawable Withdrawable<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

Conversion Kit 13716 13717 13718 13719 38778 38779<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals (400A) 13724 13733 13742 13751 - -<br />

Extended Front bar Terminals 13720 13729 13738 13747 - -<br />

Spreaded Ext Front bar Terminals - - - - 38761 38762<br />

Threaded Rear Terminals 13728 13737 13746 13755 38763 38970<br />

Vertical Flat bar Terminals - - - - 38971 38972<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/54


Motor Protection MCCBs<br />

<strong>Isomax</strong> S6 (800A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S6N 35kA 100%<br />

S6S 50kA 100%<br />

S6H 65kA 100%<br />

S6L 100kA 75%<br />

S6X 200kA 100%<br />

Protection types available<br />

Electronic (ac only)<br />

Type<br />

PR211/I<br />

Settings<br />

L R I U<br />

1.5-12x In<br />

PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

Ith PR211/I PR212/LRIU<br />

3 Pole 4 Pole 3 Pole Only<br />

S6N630R630 630A 18518 18572 -<br />

35kA S6N800R630 630A - - 50143<br />

S6N800R800 800A 18950 19004 -<br />

50kA<br />

S6S630R630 630A 18626 18680 -<br />

S6S800R800 250A 19058 19112 -<br />

S6H630R630 630A 18734 18788 -<br />

65kA S6H800R630 630A - - 45052<br />

S6H800R800 800A 19166 19220 -<br />

S6L630R630 630A 38736 38741 -<br />

100kA S6L800R630 630A - - 50554<br />

S6L800R800 800A 19274 19328 -<br />

200kA<br />

S6X400R320 320A 47595 47601 47780<br />

S6X400R400 400A 46534 46538 -<br />

S6X630R400 400A - - 47781<br />

S6X630R630 630A 46560 46564 48663<br />

Withdrawable <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator, Padlock Device, Rotary Handle<br />

c). Remember to use accessories suitable for withdrawable pattern devices<br />

S6N/S/H/L<br />

1SDA0<br />

R1<br />

S6X<br />

3 Pole 4 Pole 3 Pole<br />

Conversion Kit 13962 13963 47619<br />

Fixed portion (Base)<br />

Extended Front bar Terminals 13964 13973 13964<br />

Horizontal Flat bar Terminals 13968 13977 13968<br />

Vertical Flat bar Terminals 14096 14105 14096<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/55


Motor Protection MCCBs<br />

<strong>Isomax</strong> S7 (1250A)<br />

Ratings @ 415V<br />

Icu Ics<br />

S7S 50kA 100%<br />

S7H 65kA 100%<br />

S7L 100kA 75%<br />

Protection types available<br />

Electronic (ac only)<br />

Type<br />

PR211/I<br />

Settings<br />

L R I U<br />

1.5-12x In<br />

PR212/LRIU 0.4-1x In 3-10x In 6-12x In ON/OFF<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) 1SDA0 R1<br />

Ith PR211/I PR212/LRIU<br />

50kA<br />

3 Pole 4 Pole 3 Pole Only<br />

S7S1250R1000 1000A 19382 19490 50144<br />

S7S1250R1250 1250A 19383 19491 -<br />

65kA<br />

S7H1250R1000 1000A 19598 19706 45053<br />

S7H1250R1250 1250A 19599 19707 -<br />

100kA<br />

S7L1250R1000 1000A 19814 19922 -<br />

S7L1250R1250 1250A 19815 19923 -<br />

Withdrawable <strong>Circuit</strong> breakers<br />

To convert fixed pattern device to withdrawable pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Suitable Fixed portion (Base) from part numbers below<br />

Special Notes:<br />

a).Withdrawable devices must be fitted with a front plate accessory such as:<br />

Motor operator, Padlock Device, Rotary Handle<br />

c). Remember to use accessories suitable for withdrawable pattern devices<br />

Withdrawable<br />

1SDA0 R1<br />

3 Pole 4 Pole<br />

Conversion Kit 23299 14087<br />

Fixed portion (Base)<br />

Extended Front bar Terminals 48951 14097<br />

Horizontal Flat bar Terminals 14092 14105<br />

Vertical Flat bar Terminals 14096 14101<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/56


Current Limiting MCCBs<br />

<strong>Tmax</strong> T2, <strong>Isomax</strong> S3X, S4X, S6X<br />

Applications<br />

These current-limiting circuit-breakers are suitable for installation in all types of civil, industrial and service sector installations,<br />

as well as for electrical installations on board ships, in mines or on oil rigs, as well as, generally speaking, in any installations<br />

where high power generators and transformers make it possible for very high short-circuit currents of up to 200kA at<br />

380/415 V~, 180 kA at 440 V~ and 75 kA at 690 V~ to occur.<br />

The circuit-breakers can be positioned downstream of the power supply either to provide general protection (installations,<br />

multi-user systems and electrical lines) or for protecting electrical equipment (motors, generators, transformers and capacitors).<br />

They can also be fitted in systems where back-up protection is required that allows the use of circuit-breakers downstream<br />

which have a lower breaking capacity than the prospective short-circuit current in the point of installation.<br />

The breaking capacities of the <strong>SACE</strong> current-limiting circuit-breakers are higher than the best values achieved by other units<br />

of this type.<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/57


Current Limiting MCCBs<br />

<strong>Tmax</strong> T2 (160A)<br />

Ratings @ 415V<br />

Icu Ics<br />

T2L 85kA 75%<br />

Protection types available<br />

Type<br />

Settings<br />

Electronic L S<br />

PR221DS/LS 0.4 - 1x I n 1 - 10x I n<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70-100% 10x Ith*<br />

Low Threshold Thermomagnetic 70-100%<br />

10x Ith<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Standard Low Threshold PR221DS/LS<br />

Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

T2L160R1.6 1.6A - - 51072 51094 - -<br />

T2L160R2 2A - - 51073 51095 - -<br />

T2L160R2.5 2.5A - - 51074 51096 - -<br />

T2L160R3.2 3.2A - - 51075 51097 - -<br />

T2L160R4 4A - - 51076 51098 - -<br />

T2L160R5 5A - - 51077 51099 - -<br />

T2L160R6.3 6.3A - - 51078 51100 - -<br />

T2L160R8 8A - - 51079 51101 - -<br />

T2L160R10 10A - - 51080 51102 51153 51158<br />

T2L160R12.5 12.5A - - 51081 51103 - -<br />

85kA T2L160R16 16A 51082 51104 - - - -<br />

Plug-in <strong>Circuit</strong> breakers<br />

T2L160R20 20A 51083 51105 - - - -<br />

T2L160R25 25A 51084 51106 - - 51154 51159<br />

T2L160R32 32A 51085 51107 - - - -<br />

T2L160R40 40A 51086 51108 - - - -<br />

T2L160R50 50A 51087 51109 - - - -<br />

T2L160R63 63A 51088 51110 - - 51155 51160<br />

T2L160R80 80A 51089 51111 - - - -<br />

T2L160R100 100A 51090 51112 - - 51156 51161<br />

T2L160R125 125A 51091 51121 - - - -<br />

T2L160R160 160A 51092 51122 - - 51157 51162<br />

To convert fixed pattern device to plug-in pattern:-<br />

1). Select correct Fixed Pattern Device from part numbers above<br />

2). Select Conversion Kit from part numbers below<br />

3). Add Fixed portion (Base) from part numbers below<br />

1SDA0<br />

Plug-in<br />

R1<br />

3 Pole 4 Pole<br />

Conversion Kit 51411 51412<br />

Fixed portion (Base)<br />

Front Copper Cable Terminals** 51329 51330<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/58


Current Limiting MCCBs<br />

<strong>Isomax</strong> S3X, S4X, S6X<br />

Ratings @ 415V<br />

Icu Ics<br />

S3X 200kA 100%<br />

S4X 200kA 100%<br />

S6X 200kA 100%<br />

Protection types available<br />

Type<br />

Settings<br />

Electronic L S I G<br />

PR211/LI 0.4-1x In 1.5-12x In<br />

PR212/LSI 0.4-1x In 1-10x In 1.5 - 12x In<br />

PR212/LSIG 0.4-1x In 1-10x In 1.5-12x In 0.2-1x In<br />

Thermomagnetic Ith Im<br />

Standard Distribution 70-100% 5-10x Ith<br />

Fixed Pattern <strong>Circuit</strong> Breaker<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Supplied as standard with front bar terminals for busbar - for other terminals &<br />

accessories section pagexx<br />

Icu (415V) Model Current (A) Thermomagnetic PR211 PR212<br />

In/Ith Protection 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

S3X125R32 32A T/Mag 45197 45207 - - - -<br />

S3X125R50 50A T/Mag 45199 45209 - - - -<br />

S3X125R80 80A T/Mag 45201 45211 - - - -<br />

S3X S3X125R100 100A T/Mag 45203 45213 - - - -<br />

S3X125R125 125A T/Mag 45205 45215 - - - -<br />

S3X200R125 125A T/Mag 46039 46045 - - - -<br />

S3X200R160 160A T/Mag 46041 46047 - - - -<br />

S3X200R200 200A T/Mag 46043 46049 - - - -<br />

LI - - 46584 46594 - -<br />

S4X S4X250R100 100A LSI - - - - 46586 46596<br />

LSIG - - - - 46588 46598<br />

LI - - 46585 46595 - -<br />

S4X S4X250R160 160A LSI - - - - 46587 46597<br />

LSIG - - - - 46589 46599<br />

LI - - 46525 46529 - -<br />

S4X S4X250R250 250A LSI - - - - 46526 46530<br />

LSIG - - - - 46527 46531<br />

LI - - 47596 47602 - -<br />

S6X S6X400R320 320A LSI - - - - 47597 47603<br />

LSIG - - - - 47598 47604<br />

LI - - 46535 46539 - -<br />

S6X S6X400R400 400A LSI - - - - 46536 46540<br />

LSIG - - - - 46537 46541<br />

LI - - 46561 46565 - -<br />

S6X S6X630R630 630A LSI - - - - 46562 46566<br />

LSIG - - - - 46563 46567<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/59


<strong>Emax</strong> Air <strong>Circuit</strong> Breaker Electrical Specifications<br />

Description<br />

Voltages Rated Service Voltage Ue [V] 690(ac) 250(dc)<br />

Rated Insulation Voltage Ui [V] 1000<br />

Rated Impulse Voltage Uimp [kV] 12<br />

E1<br />

E2<br />

Temperature Service °C -5...+70<br />

Storage °C -40...+70 N B N L<br />

Performance Level<br />

Rated uninterrupted current @ 40°VC Iu [A] 800 1600 1250 1250<br />

[A] 1250 2000 1600 1600<br />

[A] - - 2000 -<br />

[A] - - - -<br />

[A] - - - -<br />

Capacity of neutral on 4 pole breakers % Iu 100% 100%<br />

Rated ultimate short circuit breaking capacity Icu<br />

220/230/380/400/415 Vac [kA] 50 42 65 130<br />

440 Vac [kA] 50 42 65 110<br />

500/660/690 Vac [kA] 36 42 55 85<br />

250Vdc [kA] 36 40 55 -<br />

Rated duty short circuit breaking capacity Ics<br />

220/230/380/400/415 Vac [kA] 50 42 65 130<br />

440 Vac [kA] 50 42 65 110<br />

500/660/690 Vac [kA] 36 42 55 65<br />

250 Vdc [kA] 36 42 55 -<br />

Rated short time withstand current<br />

Icw<br />

1 sec [kA] 50 42 55 10<br />

3 secs [kA] 36 42 42 -<br />

Rated short circuit making capacity<br />

Icm<br />

220/230/380/400/415 Vac [kA] 105 88.2 143 286<br />

440 Vac [kA] 105 88.2 143 242<br />

500/600/690 Vac [kA] 75.6 88.2 121 187<br />

Utilisation category (according to BS EN 60947-2) B B B A<br />

Microprocessor-based releases for a.c. applications operating time<br />

Closing time (max) [mS] 80 80 80 80<br />

Break time for I < Icw (max) [mS] 70 70 70 70<br />

Break time for I > Icw (max) [mS] 30 30 30 12<br />

Dimensions<br />

Weight<br />

Fixed (H=418mm D=302mm W=3/4 pole) [mm] 296/386 296/386<br />

Drawout (H=461mm D=396.5mm W=3/4 pole) [mm] 324/414 324/414<br />

Fixed 3/4 pole [kg] 45/54 50/61 50/61 52/63<br />

Drawout 3/4 pole [kg] 70/82 78/93 78/93 8095<br />

Rated uninterrupted current @ 40°C Iu [A] 800/1250 1250 1600 2000<br />

Mechanical Life (with routine maintenance) [ops x 1000] 25 25(B-N) 10(L) 25(B-N) 20(L) 25<br />

Frequency [No. ops per Hr] 60 60 60 60<br />

Electrical Life [ops x 1000] 10 15(B-N) 4(L) 12(B-N) 3(L) 10<br />

Frequency [No. ops per Hr] 30 30 30 30<br />

ABB LIMITED 4/60


E3 E3 E4 E4 E6<br />

N S H/b H L S S/f H H H/f<br />

2500 1250 1250 1250 2000 4000 3200 3200 5000 5000<br />

3200 1600 1600 1600 2500 - 4000 4000 6300 6300<br />

- 2000 2000 2000 - - - - - -<br />

- 2500 2500 2500 - - - - - -<br />

- 3200 3200 3200 - - - - - -<br />

100% 50% 100% 50% 50% 100%<br />

65 75 80 100 130 75 80 100 100 100<br />

65 75 80 100 110 75 80 100 100 100<br />

65 75 75 85 85 75 75 85 100 100<br />

65 75 75 75 - 75 75 100 100 100<br />

65 75 80 85 130 75 80 100 100 100<br />

65 75 80 85 110 75 80 100 100 100<br />

65 75 75 85 65 75 75 85 100 100<br />

65 75 75 75 - 75 75 100 100 100<br />

65 75 80 75 15 75 80 100 100 100<br />

65 65 - 65 - 75 - 75 85 -<br />

143 165 176 220 286 165 176 220 220 220<br />

143 165 176 220 242 165 176 220 220 220<br />

143 165 165 187 187 165 165 187 220 220<br />

B B B B A B B B B B<br />

80 80 80 80 80 80 80 80 80 80<br />

70 70 70 70 70 70 70 70 70 70<br />

30 30 30 30 12 30 30 30 30 30<br />

404/530 556/656 757* 556/656 782/908 1045*<br />

432/558 594/684 778* 594/684 810/936 1062*<br />

66/80 66/80 66/80 66/80 72/83 97/117 132* 97/117 140/160 193*<br />

104/125 104/125 104/125 104/125 110/127 147/165 211* 147/165 210/240 295*<br />

1250 1600 2000 2500 3200 3200 4000 - 3200 4000<br />

20 20 20(N-S-H) 15(L) 20(N-S-H) 15(L) 20 15 12 - 12 12<br />

60 60 60 60 60 60 60 - 60 60<br />

12 10 9(N-S-H) 2(L) 8(N-S-H) 1.8(L) 6 7 5 - 5 4<br />

20 20 20 20 20 10 10 - 10 10<br />

ABB LIMITED 4/61


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

Microprocessor-based overcurrent releases<br />

General specificications of the microprocessor-based releases include:<br />

• operation without the need for an external power supply<br />

• microprocessor technology (8-bit for <strong>SACE</strong> PR111 and 16-bit for <strong>SACE</strong> PR112 and PR113)<br />

• high precision<br />

• sensitivity to the true r.m.s. value of the current<br />

• interchangeability among all types of releases<br />

• setting for neutral normally 50% of setting phases, with possibility of setting it to 100% (on request<br />

only for circuit -breakers E1, E2, E3 standard and £4/f, E6/f full size versions).<br />

For the release PR113, it is also possible to select neutral protection at 150% and 200% of the rated<br />

current of the phases, if compatible with the setting of the current transformers.<br />

The main performance features of the releases are listed in the tables below.<br />

<strong>SACE</strong> PR111<br />

Protection<br />

PR111/P PR111/P PR111/P<br />

L S I G L S I L I<br />

<strong>SACE</strong> PR112<br />

PR112/P PR112/P<br />

Protection L S I G L S I<br />

PR112/PD PR112/PD PR112/PD PR112/PD<br />

Protection & Modbus Modbus LON LON<br />

Communication L S I G L S I L S I G L S I<br />

<strong>SACE</strong> PR113<br />

Protection<br />

PR113/P<br />

L S I G<br />

D U OT UV OV RV RP M<br />

Protection &<br />

Communication<br />

PR113/PD<br />

Modbus<br />

L S I G<br />

D U OT UV OV RV RP M<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/62


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

Microprocessor-based overcurrent releases<br />

OV<br />

Protection Functions PR111 PR112 PR113<br />

L<br />

S<br />

I<br />

G<br />

D<br />

U<br />

OT<br />

UV<br />

RV<br />

RP<br />

M<br />

Inverse long time-delay trip overload protection<br />

Adjustable-slope curve (IEC 60255-3)<br />

Selective short-circuit protection with inverse or definite<br />

short time-delay trip<br />

Instantaneous short-circuit protection with adjustable<br />

trip current threshold<br />

Earth fault protection<br />

Directional short-circuit protection with adjustable delay<br />

Protection against phase umbalance<br />

Protection against over temperature<br />

Undervoltage and overvoltage protection<br />

Residual voltage protection / neutral displacement protection<br />

Reverse power protection<br />

Thermal memory for L and S functions<br />

residual (internal sensor)<br />

source ground return (external sensor)<br />

Measurements<br />

Currents (phases, neutral, earth fault)<br />

Voltage (phase-phase, phase-neutral, residual)<br />

<strong>Power</strong> (active, reactive, apparent)<br />

<strong>Power</strong> factor<br />

Frequency and peak factor<br />

Energy (active, reactive, apparent, counter)<br />

Harmonics calculation (displays waveform and module of the harmonics)<br />

Maintenance events and data<br />

Events stored in chronological order<br />

Counting number of operations and contact wear<br />

Communication with centralized supervision and control system<br />

Remote setting of parameters for protection functions, unit configuration and communication<br />

Transmission of measurements, states and alarms from circuit-breaker to system<br />

Transmission of maintenance events and data from circuit-breaker to system<br />

Self-test<br />

Alarm and tripping for release overtemperature<br />

Alarm for microprocessor fault<br />

User interface<br />

Parameters set using DIP switches<br />

Parameters set using keys and liquid crystal display<br />

Alarm signals for L, S, I and G functions<br />

Alarm signalling one of the following protections: undervoltage, overvoltage, residual voltage, reverse power<br />

Imbalance phase and overtemperature signal<br />

Complete management of pre-alarms and alarms for all protection and self monitoring functions<br />

Password for use with “READ” or “EDIT” mode<br />

Load control<br />

Connection-disconnection of loads in relation to the current flowing through the circuit breaker<br />

Zone selectivity<br />

May be activated for protection functions S or G<br />

May be activated for protection funcions S, G or D<br />

Number of programmable contacts 1 2<br />

Start-up function S, D, I and G<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/63


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

Automatic circuit-breakers with full-size neutral conductor<br />

The <strong>Emax</strong> range of automatic circuit-breakers with full size neutral conductor is used in special applications<br />

where the presence of triple-N harmonics on individual phases may lead to a very high current<br />

on the neutral conductor.<br />

Typical applications include installations with loads having high harmonics distortions (computers and<br />

electronic devices in general), lighting systems with a large number of fluorescent lamps, systems with<br />

inverters and rectifiers, UPS, systems for adjusting the speed of electric motors.<br />

This range includes standard circuit-breakers with full-size neutral conductor in sizes E1, E2, E3.<br />

Models E4 and E6 are available in the “full size” version up to rated currents of 6300A. Models E4/f<br />

and E6/f are available in fixed and withdrawable four-pole versions. These models may be fitted with<br />

all accessories available of the <strong>Emax</strong> range; the exception, on the E6/f model, are the mechanical<br />

interlocks made using flexible wires and 15 external auxiliary contacts, which are therefore incompatible.<br />

All the models may be fitted with all available version of electronic protection relays, in the standard<br />

version.<br />

E4S/f<br />

E6H/f<br />

Rated uninterrupted current (at 40ºC) Iu [A] 4000 5000<br />

[A] 6300<br />

Number of poles 4 4<br />

Rated service voltage Ue [V~] 690 690<br />

Rated ultimate short-circuit breaking capacity Icu<br />

220/230/380/400/415 V ~ [kA] 80 100<br />

440 V ~ [kA] 80 100<br />

500/660/690 V ~ [kA] 75 100<br />

Rated service short-circuit breaking capacity Ics<br />

220/230/380/400/415 V ~ [kA] 80 100<br />

440 V ~ [kA] 80 100<br />

500/660/690 V ~ [kA] 75 100<br />

Rated short-time withstand current Icw<br />

(1s) [kA] 80 100<br />

(3s) [kA] 75 85<br />

Rated short-circuit making capacity (peak value) Icm [kA] 176 220<br />

Application category (in accordance with IEC 60947-2) B B<br />

Isolation behavior (in accordance with IEC 60947-2)<br />

Overall dimensions<br />

Fixed: H= 418mm - D= 302mm L [mm] 746 1034<br />

Withdrawable: H=461 - D= 396.5mm L [mm] 774 1062<br />

Weights (circuit-breaker complete with releases and CT, not including accessories)<br />

Fixed [kg] 120 165<br />

Withdrawable (including fixed part) [kg] 170 250<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/64


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

Switch-disconnectors<br />

The switch-disconnectors are derived from the corresponding automatic circuit-breakers, of which<br />

they maintain the overall dimensions and the possibility of mounting accessories.<br />

This version differs from the automatic circuit-breakers only in the absence of overcurrent releases.<br />

The circuit-breaker is available in both fixed and withdrawable versions, three-pole and four-pole. The<br />

switch-disconnectors, identified by the label “/MS”, may be used according to the category of use AC-<br />

23A (switching motor loads or other highly inductive loads) in accordance with the standard IEC<br />

60947-3. The electrical specifications of the switch-disconnectors are listed below.<br />

E1B/MS E1N/MS E2B/MS E2N/MS E3N/MS E3S/MS E4S/MS E4S/fMS E4H/MS E6H/MS E6H/fMS<br />

Rated uninterrupted current (at 40ºC) Iu [A] 800 800 1600 1250 2500 1250 4000 4000 3200 5000 5000<br />

[A] 1250 1250 2000 1600 3200 1600 - - 4000 6300 6300<br />

[A] - - - 2000 - 2000 - - - - -<br />

[A] - - - - - 2500 - - - - -<br />

[A] - - - - - 3200 - - - - -<br />

Rated service voltage Ue [V ~] 690 690 690 690 690 690 690 690 690 690 690<br />

[V ~] 250 250 250 250 250 250 250 250 250 250 250<br />

Rated insulation voltage Ui [V ~] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000<br />

Rated impulse withstand voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12 12<br />

Rated short-time withstand current Icw (1s) [kA] 36 50 42 55 65 75 75 80 100 100 100<br />

(3s) [kA] 36 36 42 42 65 65 75 75 75 85 85<br />

Rated short-circuit making capacity (peak value) ICM<br />

220/230/380/400/415/440 V ~ [kA] 75.6 105 88.2 121 143 165 165 176 220 220 220<br />

500/660/690 V ~ [kA] 75.6 75.6 88.2 121 143 165 165 165 187 220 220<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/65


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E1 - Fixed Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E1N 50kA 50kA 50kA<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 53803 53804 - - - -<br />

42kA E1N 08 800A LSI - - 53754 53761 53757 53763<br />

LSIG - - 53755 53762 53758 53764<br />

LI 53805 53806 - - - -<br />

42kA E1N 12 1250A LSI - - 53767 53773 53769 53775<br />

LSIG - - 53768 53774 53770 53776<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/66


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E1 - Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E1N 50kA 50kA 50kA<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

LI 53807 53808 - - - -<br />

42kA E1N 08 800A LSI - - 53780 53786 53782 53788<br />

LSIG - - 53781 53787 53783 53789<br />

LI 53809 53810 - - - -<br />

42kA E1N 12 1250A LSI - - 53792 53798 53794 53800<br />

LSIG 53793 53799 53795 53801<br />

Refer to sales office for breakers fitted with PR113 release<br />

Fixed Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Front, Flat and mixed terminal versions available on request, refer to technical catalogue<br />

Terminal type 1SDA0 R1<br />

3 pole 4pole<br />

Rear Horizontal 37821 37826<br />

Rear Vertical 37872 37877<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/67


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E2 - Fixed Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E2N 65kA 65kA 55kA<br />

E2L 130kA 130kA 10kA<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS n/a n/a - - - -<br />

65kA E2N 12 800A LSI - - 39676 39791 39684 39799<br />

LSIG - - 39680 39795 39688 39803<br />

MS 37531 37559 - - - -<br />

65kA E2N12 1250A LSI - - 39677 39792 39685 39800<br />

LSIG - - 39681 39796 39689 39803<br />

MS 37532 37560 - - - -<br />

65kA E2N 16 1600A LSI 39906 39994 39912 40000<br />

LSIG 39909 39997 39915 40003<br />

MS 37533 37561 - - - -<br />

65kA E2N 20 2000A LSI - - 40082 40170 40088 40176<br />

LSIG - - 40085 40173 40091 40091<br />

MS n/a n/a - - - -<br />

130kA E2L 12 1250A LSI - - 43394 40341 43402 40349<br />

LSIG - - 43398 40345 43406 40353<br />

MS n/a n/a - - - -<br />

130kA E2L 16 1600A LSI - - 40455 40543 40461 40549<br />

LSIG - - 40458 40546 40464 40552<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/68


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E2 - Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E2N 65kA 65kA 55kA<br />

E2L 130kA 130kA 10kA<br />

Refer to sales office for breakers fitted with PR113 release<br />

Fixed Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Front, Flat and mixed terminal versions available on request, refer to technical catalogue<br />

Terminal type 1SDA0 R1<br />

3 pole 4pole<br />

Rear Horizontal 37822 37827<br />

Rear Vertical 37873 37886<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS n/a n/a - - - -<br />

65kA E2N 12 800A LSI - - 39762 39878 39770 39886<br />

LSIG - - 39766 39882 39774 39890<br />

MS 37648 37652 - - - -<br />

65kA E2N 12 1250A LSI - - 39763 39879 39771 39887<br />

LSIG - - 39767 39883 39775 39891<br />

MS 37647 37651 - - - -<br />

65kA E2N 16 1600A LSI - - 39972 40060 39978 40066<br />

LSIG - - 39975 40064 39981 40069<br />

MS 37649 37650 - - - -<br />

65kA E2N 20 2000A LSI - - 40148 40214 40154 40220<br />

LSIG - - 40151 40217 40157 40223<br />

MS n/a n/a - - - -<br />

130kA E2L 12 1250A LSI - - 40296 40428 40304 40436<br />

LSIG - - 40300 40432 40308 40440<br />

MS n/a n/a - - - -<br />

130kA E2L 16 1600A LSI - - 40521 40609 40527 40615<br />

LSIG - - 40524 40612 40530 40618<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/69


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E3N, S - Fixed Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E3N 65kA 65kA 65kA<br />

E3S 75kA 75kA 75kA<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS - - - - - -<br />

65kA E3N 25 2500A LSI - - 40651 40711 40655 40715<br />

LSIG - - 41653 41713 40657 40717<br />

MS - -<br />

65kA E3N 32 3200A LSI - - 40786 43375 40790 43379<br />

LSIG - - 40788 43377 40792 43381<br />

MS - - - - - -<br />

75kA E3S 12 1250A LSI - - 40891 40951 40895 40955<br />

LSIG - - 40893 40953 40897 40957<br />

MS - - - - - -<br />

75kA E3S 16 1600A LSI - - 41011 41071 41015 41075<br />

LSIG - - 41013 41073 41017 41077<br />

MS - - - - - -<br />

75kA E3S 20 2000A LSI - - 41131 41191 41135 41195<br />

LSIG - - 41133 41193 41137 41197<br />

MS - - - - - -<br />

75kA E3S 25 2500A LSI - - 41251 41311 41255 41315<br />

LSIG - - 41253 41313 41257 41317<br />

MS - - - - - -<br />

75kA E3S 32 3200A LSI - - 41371 41431 41375 41435<br />

LSIG - - 41373 41933 41377 41437<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/70


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E3H/b, H, L - Fixed Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E3H/b 80kA 80kA 80kA<br />

E3H 100kA 85kA 75kA<br />

E3L 130kA 130kA 15kA<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS TBC TBC<br />

80kA E3H/b 12 1250A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 16 1600A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 20 2000A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 25 2500A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 32 3200A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS - -<br />

100kA E3H 12 1250A LSI - - 41491 41551 41495 41555<br />

LSIG - - 41493 41553 41497 41557<br />

MS - -<br />

100kA E3H 16 1600A LSI - - 41611 41671 41615 41675<br />

LSIG - - 41613 41673 41617 41677<br />

MS - -<br />

100kA E3H 20 2000A LSI - - 41731 41791 41735 41795<br />

LSIG - - 41733 41793 41737 41797<br />

MS - -<br />

100kA E3H 25 2500A LSI - - 41851 41911 41855 41915<br />

LSIG - - 41853 41913 41857 41917<br />

MS - -<br />

100kA E3H 32 3200A LSI - - 41971 42031 41975 42035<br />

LSIG - - 41973 42033 41977 42037<br />

MS - -<br />

130kA E3L 20 2000A LSI - - 42091 42151 42095 42155<br />

LSIG - - 42093 42153 42097 42157<br />

MS - -<br />

130kA E3L 25 2500A LSI - - 42211 42271 42215 42275<br />

LSI - - 42213 42273 42217 42277<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/71


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E3N, S - Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E3N 65kA 65kA 65kA<br />

E3S 75kA 75kA 75kA<br />

Refer to sales office for breakers fitted with PR113 release<br />

Fixed Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Front, Flat and mixed terminal versions available on request, refer to technical catalogue<br />

Terminal type 1SDA0 R1<br />

3 pole 4pole<br />

Rear Horizontal 37822 37827<br />

Rear Vertical 37873 37886<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS 37656 37653 - - - -<br />

65kA E3N 25 2500A LSI - - 40696 40756 40700 40760<br />

LSIG - - 40698 40758 40702 40762<br />

MS 37655 37654 - - - -<br />

65kA E3N 32 3200A LSI - - 40831 40876 40835 40880<br />

LSIG - - 40833 40878 40837 40882<br />

MS 37657 37664 - - - -<br />

75kA E3S 12 1250A LSI - - 40936 40996 40940 41000<br />

LSIG - - 40938 40998 40942 41002<br />

MS 37660 37665 - - - -<br />

75kA E3S 16 1600A LSI - - 41056 41116 41060 41120<br />

LSIG - - 41058 41118 41062 41122<br />

MS 37658 37666 - - - -<br />

75kA E3S 20 2000A LSI - - 41176 41236 41180 41240<br />

LSIG - - 41178 41238 41182 41242<br />

MS 37661 37662 - - - -<br />

75kA E3S 25 2500A LSI - - 41296 41356 41300 41360<br />

LSIG - - 41298 41358 41302 41362<br />

MS 37659 37663 - - - -<br />

75kA E3S 32 3200A LSI - - 41416 41476 41420 41480<br />

LSIG - - 41418 41478 41422 41482<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/72


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E3H/b, H, L Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E3H/b 80kA 80kA 80kA<br />

E3H 100kA 85kA 75kA<br />

E3L 130kA 130kA 15kA<br />

Refer to sales office for breakers<br />

fitted with PR113 release<br />

Fixed Portions - Refer to page ????<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For version with FULLY RATED NEUTRAL, add /FRN to order reference<br />

eg 1SDA0 39676R1/FRN<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS TBC TBC<br />

80kA E3H/b 12 1250A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 16 1600A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 20 2000A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 25 2500A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS TBC TBC<br />

80kA E3H/b 32 3200A LSI TBC TBC TBC TBC<br />

LSIG TBC TBC TBC TBC<br />

MS - - - - - -<br />

100kA E3H 12 1250A LSI - - 41536 41596 41540 41600<br />

LSIG - - 41568 41598 41542 41602<br />

MS - - - - - -<br />

100kA E3H 16 1600A LSI - - 41656 41716 41660 41720<br />

LSIG - - 41658 41718 41662 41722<br />

MS - - - - - -<br />

100kA E3H 20 2000A LSI - - 41776 41836 41780 41840<br />

LSIG - - 41778 41838 41782 41842<br />

MS - - - - - -<br />

100kA E3H 25 2500A LSI - - 41896 41956 41900 41960<br />

LSIG - - 41898 41958 41902 41962<br />

MS - - - - - -<br />

100kA E3H 32 3200A LSI - - 42016 42076 42020 42080<br />

LSIG - - 42018 42078 42022 42082<br />

MS - - - - - -<br />

130kA E3L 20 2000A LSI - - 42136 42196 42140 42200<br />

LSIG - - 42138 42198 42142 42202<br />

MS - - - - - -<br />

130kA E3L 25 2500A LSI - - 42256 42316 42260 42320<br />

LSI - - 42258 42318 42262 42322<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/73


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E4S, S/f, H - Fixed - Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E4S 75kA 75kA 75kA<br />

E4S/f 80kA 80kA 80kA<br />

E4H 100kA 100kA 100kA<br />

Refer to sales office for breakers fitted with PR113 release<br />

* Available in 4 pole ( fully rated neutral) version only<br />

* Available with 50% rated neutral only<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order<br />

reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f<br />

part numbers<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS 37546 37574 - - - -<br />

75kA E4S 4000A LSI - - 42332 42392 42336 42396<br />

LSIG - - 42334 42394 42338 42398<br />

MS n/a 48737 n/a - n/a -<br />

80kA E4S/f 4000A LSI n/a - n/a 48675 n/a 48677<br />

LSIG n/a - n/a 48676 n/a 48678<br />

MS 37547 37575 - - - -<br />

100kA E4H 32 3200A LSI - - 42452 43419 42456 42423<br />

LSIG - - 42454 43421 42458 42425<br />

MS 37548 37576 - - - -<br />

100kA E4H 40 4000A LSI - - 42557 42617 42561 42621<br />

LSIG - - 42559 42619 42563 42623<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/74


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E4S, S/f, H Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E4S 75kA 75kA 75kA<br />

E4S/f 80kA 80kA 80kA<br />

E4H 100kA 100kA 100kA<br />

* Note: Available in 4 pole ( fully rated neutral) version only<br />

* Note: Available with 50% rated neutral only<br />

Refer to sales office for breakers fitted with PR113 release<br />

Fixed Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Front, Flat and mixed terminal versions available on request, refer to technical catalogue<br />

For E4S 4 pole fully rated neutral version use E4S/f part numbers<br />

Terminal type 1SDA0 R1<br />

3 pole 4pole<br />

Rear Horizontal<br />

Rear Vertical<br />

E4S & E4H 37824 37829<br />

E4S/f n/a 48702<br />

E4S & E4H 37875 37879<br />

E4S/f n/a 48707<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order<br />

reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f<br />

part numbers<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS 37677 37678 - - - -<br />

75kA E4S 4000A LSI - - 42377 42437 42381 42441<br />

LSIG - - 42379 42439 42383 42443<br />

MS n/a 48740 n/a - n/a -<br />

80kA E4S/f 4000A LSI n/a - n/a 48696 n/a 48698<br />

LSIG n/a - n/a 48697 n/a 48699<br />

MS 37682 37679 - - - -<br />

100kA E4H 32 3200A LSI - - 42497 42542 42501 42546<br />

LSIG - - 42499 42544 42503 42548<br />

MS 37681 37680 - - - -<br />

100kA E4H 40 4000A LSI - - 42602 42662 42606 42666<br />

LSIG - - 42604 42664 42608 42668<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/75


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E6H, H/f, V - Fixed Rear Horizontal Terminals<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E6H 100kA 100kA 100kA<br />

E6H/f 100kA 100kA 100kA * Note: This breaker * Note: is Available available in in 44 pole ( ( fully fully rated neutral) version only only<br />

E6V 150kA 125kA 100kA * Note: This breaker * Note: is Available available with with 50% 50% rated neutral only only<br />

With Rear Horizontal Terminals<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

For E6H 3 pole version for use with fully rated external neutral CT, add /FRN to order<br />

reference eg 1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f<br />

part numbers<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS 37549 37577 - - - -<br />

100kA E6H 50 5000A LSI - - 42677 42737 42681 42741<br />

LSIG - - 42679 42739 42683 42743<br />

MS 37550 37578 - - - -<br />

100kA E6H 63 6300A LSI - - 42797 42857 42801 42861<br />

LSIG - - 42799 42859 42803 42863<br />

MS n/a 50810 n/a - n/a -<br />

100kA E6H/f 50 5000A LSI n/a - n/a 50768 n/a 50770<br />

LSIG n/a - n/a 50769 n/a 50771<br />

MS n/a 50813 n/a - n/a -<br />

100kA E6H/f 63 6300A LSI n/a - n/a 50789 n/a 50791<br />

LSIG n/a - n/a 50790 n/a 50792<br />

MS - - - - - -<br />

150kA E6V 32 3200A LSI - - 42923 42955 42925 42957<br />

LSIG - - 42924 42956 42926 42958<br />

MS - - - - - -<br />

150kA E6V 40 4000A LSI - - 42996 43056 43000 43060<br />

LSIG - - 42998 43058 43002 43062<br />

MS - - - - - -<br />

150kA E6V 50 5000A LSI - - 43101 43161 43105 43165<br />

LSIG - - 43103 43163 43107 43167<br />

MS - - - - - -<br />

150kA E6V 63 6300A LSI - - 43221 43281 43225 43285<br />

LSIG - - 43223 43283 43227 43287<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/76


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> E6H, H/f, V Drawout<br />

Ratings @ 415V<br />

Icu Ics Icw (1sec)<br />

E6H 100kA 100kA 100kA<br />

E6H/f 100kA 100kA 100kA<br />

E6V 150kA 125kA 100kA<br />

* Note: Available in 4 pole ( fully rated neutral) version only<br />

* Note: Available with 50% rated neutral only<br />

Refer to sales office for breakers fitted with PR113 release<br />

Fixed Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1<br />

Front, Flat and mixed terminal versions available on request, refer to technical catalogue<br />

For E6H 4 pole fully rated neutral version use E6H/f part numbers<br />

1SDA0 R1<br />

Terminal type 3 pole 4pole<br />

Rear Horizontal<br />

Rear Vertical<br />

E6H & E6V 37825 37830<br />

E6H/f n/a 50816<br />

E6H & E6V 37876 37880<br />

E6H/f n/a 50821<br />

Moving Portions<br />

Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1. For<br />

E6H 3 pole version for use with fully rated external neutral CT, add /FRN to order reference<br />

eg:1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f part numbers<br />

Icu Model Current (A) Protection Non-Automatic PR111 PR112<br />

(415V) Ith 1SDA0 R1<br />

3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole<br />

MS 37683 37686 - - - -<br />

100kA E6H 50 5000A LSI - - 42722 42782 42726 42786<br />

LSIG - - 42742 42784 42728 42788<br />

MS 37684 37685 - - - -<br />

100kA E6H 63 6300A LSI - - 42842 42902 42846 42906<br />

LSIG - - 42844 42904 42848 42908<br />

MS n/a 50812 n/a - n/a -<br />

100kA E6H/f 50 5000A LSI n/a - n/a 50782 n/a 50784<br />

LSIG n/a - n/a 50783 n/a 50785<br />

MS n/a 50815 n/a - n/a -<br />

100kA E6H/f 63 6300A LSI n/a - n/a 50804 n/a 50806<br />

LSIG n/a - n/a 50805 n/a 50807<br />

MS - - - - - -<br />

150kA E6V 32 3200A LSI - - 42939 42971 42941 42973<br />

LSIG - - 42940 42972 42942 42974<br />

MS - - - - - -<br />

150kA E6V 40 4000A LSI - - 43026 43086 43030 43090<br />

LSIG - - 43028 43088 43032 43092<br />

MS - - - - - -<br />

150kA E6V 50 5000A LSI - - 43146 43206 43150 43210<br />

LSIG - - 43148 43208 43152 43212<br />

MS - - - - - -<br />

150kA E6V 63 6300A LSI - - 43266 43311 43270 43315<br />

LSIG - - 43268 43313 43272 43317<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/77


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> fixed part accessories<br />

Electrical Accessories<br />

1). Shunt opening/closing release<br />

E 1/6 1SDA0 R1<br />

24 V 38286<br />

30 V 38287<br />

48 V 38288<br />

60 V 38289<br />

110...120 V 38290<br />

120...127 V 38291<br />

220...240 V 38292<br />

240...250 V 38293<br />

380...400 V 38294<br />

440 V 38295<br />

the shunt opening release and closng release share the same construction and are therefore interchangable. Their function is determined by<br />

the position in which they are mounted on the circuit-breaker.<br />

2a). Undervoltage release<br />

E1/6 1SDA0 R1<br />

24 V 38306<br />

30 V 38307<br />

48 V 38308<br />

60 V 38309<br />

110...120 V 38310<br />

120...127 V 38311<br />

220...240 V 38312<br />

240...250 V 38313<br />

380...400 V 38314<br />

440...480 V 38315<br />

2b). Electronic time-delay device for undervoltage release<br />

E1/6 1SDA0 R1<br />

24...30 V 38316<br />

48 V 38317<br />

60 V 38318<br />

110...115 V 38319<br />

220...250 V 38320<br />

3). Geared motor for automatic charging of closing springs<br />

E1/6 1SDA0 R1<br />

24...30 V 38321<br />

48...60 V 38322<br />

100...130 V 38323<br />

220...250 V 38324<br />

supplied as standard with limit contact and microswitch for signalling the closing springs are charged<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/78


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> fixed part accessories<br />

Electrical Accessories cont...<br />

4). Signal for overload current releases tripped<br />

E 1/6 1SDA0 R1<br />

Mechanical 38337<br />

Electrical 1) 38338<br />

1)<br />

Requires mechanical signal as well.<br />

5a). Electrical signalling of circuit-breaker open/closed<br />

E1/6 1SDA0 R1<br />

4 auxilliary contacts 2) 38326<br />

10 auxilliary contacts 3) 4) 38327<br />

15 additional auxilliary contacts 5) 43475<br />

15 additional auxilliary contacts (special version for withdrawable) 5) 48827<br />

2)<br />

Order for MS-CS-MT-MTP version only. Already included for automatic circuit-breaker.<br />

3)<br />

Not available with PR112 release.<br />

4)<br />

Order for MS-CS-MT-MTP version. Order as a loose kit only for automatic circuit-breaker<br />

5)<br />

Outside circuit-breaker. Order as alternative to various types of interlock and to accessory 8e.<br />

For mounting on fixed circuit-breaker requires accessory 10.4 as well (interlock plate for fixed circuit-breaker)<br />

5b). Electrical signalling of connected/isolated/isolated for test position<br />

1SDA0<br />

E1/E6 - 5 auxilliary contacts 38361<br />

E1/E2 - 10 auxilliary contacts 3 poles 38360<br />

E1/E2 - 10 auxilliary contacts 4 poles 43467<br />

E3 - 10 auxilliary contacts 3 poles 43468<br />

E3 - 10 auxilliary contacts 4 poles 43469<br />

E4/E6 - 10 auxilliary contacts 3/4 poles 43470<br />

R1<br />

5c). Contact for signalling closing springs charged<br />

E1/6 1SDA0 R1<br />

- 38325<br />

Order as alternative to geared motor<br />

5d). Contact for signalling undervoltage release energised<br />

E1/6 1SDA0 R1<br />

1 normally open contact 38340<br />

1 normally closed contact 38341<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/79


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> fixed part accessories<br />

Electrical Accessories cont...<br />

6a). Current transformer for neutral conductor outside circuit-breaker<br />

E2 1SDA0 R1<br />

R250 38269<br />

R400 38270<br />

R800 38271<br />

R1250 38272<br />

R1600 38273<br />

R2000 38274<br />

E3 1SDA0 R1<br />

R250 48952<br />

R400 48953<br />

R800 38277<br />

R1250 38278<br />

R1600 38279<br />

R2000 38280<br />

R2500 38281<br />

R3200 38282<br />

E4 1SDA0 R1<br />

R2000 48957<br />

R3200 38275<br />

R4000 38276<br />

E6 1SDA0 R1<br />

R3200 48958<br />

R4000 38283<br />

R5000 38284<br />

R6300 38285<br />

6b). Homopolar toroid for the main power supply earthing conductor<br />

1SDA0<br />

In 100A 48067<br />

In 250A 48068<br />

In 400A 48069<br />

In 800A 48070<br />

R1<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/80


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> fixed part accessories<br />

Mechanical Accessories<br />

7). Mechanical operation counter<br />

E 1/6 1SDA0 R1<br />

38345<br />

1)<br />

Requires mechanical signal as well.<br />

8a). Lock in open position<br />

E1/6 - key lock 1SDA0 R1<br />

for 1 circuit-breaker (different keys) 38350<br />

for sets of circuit-breakers (same keys No. 3004222) 38346<br />

for sets of circuit-breakers (same keys No. 0025431) 38347<br />

for sets of circuit-breakers (same keys No. 0233424) 38348<br />

for sets of circuit-breakers (same keys No. 0335452) 38349<br />

padlock (as alternative to mechanical accessory 3a) 38351<br />

castell lock (not supplied please order from Castell International Ref: PDS01388(s))<br />

NONSTD161<br />

8b). <strong>Circuit</strong>-breaker lock in connected/isolated/isolated for test position<br />

E1/6 - key lock + padlock 1SDA0 R1<br />

for 1 circuit-breaker (different keys) 38356<br />

for sets of circuit-breakers (same keys No. 3004222) 38352<br />

for sets of circuit-breakers (same keys No. 0025431) 38353<br />

for sets of circuit-breakers (same keys No. 0233424) 38354<br />

for sets of circuit-breakers (same keys No. 0335452) 38355<br />

8c). Accessory for lock in isolated/isolated for test position<br />

E1/6 1SDA0 R1<br />

- 38357<br />

Order in addition to mechanical accessory 2b<br />

8d). Accessory for padlock device for shutters<br />

E1/6 1SDA0 R1<br />

- 38363<br />

8e). Mechanical lock for compartment door<br />

E1/6 1SDA0 R1<br />

- 1) 2) 3) 45039<br />

1) Order as an alternative to the various types of interlocks and electrical accessory 5a (15 auxilliary contacts)<br />

2) the use of accessory 10.2 is necessary for installation<br />

3) for fixed circuit-breaker, plate 10.4<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/81


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

<strong>Emax</strong> fixed part accessories<br />

Mechanical Accessories<br />

9a). Protection cover opening and closing pushbuttons<br />

E 1/6 1SDA0 R1<br />

- 38343<br />

9b). IP54 protective cover for door<br />

E1/6 - key lock 1SDA0 R1<br />

- 38344<br />

10a). Interlock cable set (order one per interlock set)<br />

E1/6 Horizontal Vertical<br />

Description 1SDA0 R1 1SDA0 R1<br />

A type cable set 38329 38333<br />

B type cable set 38330 38334<br />

C type cable set 38331 38335<br />

D type cable set 38332 38336<br />

10b). Interlock mechanism (order one per breaker)<br />

Type 1SDA0 R1<br />

E1 38366<br />

E2 38366<br />

E3 38367<br />

E4 - 3 poles 38368<br />

E5 - 4 poles / E6 - 3 poles 43466<br />

E6 - 4 poles 38369<br />

10c). Interlock mechanism (order one per breaker)<br />

Type 1SDA0 R1<br />

A E2 - E6 fixed or moving part 38364<br />

B E2 - E6 fixed or moving part 38364<br />

C E2 - E6 fixed or moving part 38365<br />

D E2 - E6 fixed or moving part 38364<br />

10d). Interlock plate for fixed breaker (order one per breaker)<br />

E1/6 1SDA0 R1<br />

- 38363<br />

Mechanical Interlock Ordering Example:<br />

C type horizontal interlock for 3 off E2N drawout pattern breakers<br />

1 off C type cable set (10a) 1SDA038331R1<br />

2 off Interlock mechanism (10c) 1SDA038366R1<br />

3 off Interlock mechanism (10b) 1SDA038365R1<br />

3 off E2Nfixed pattern breakers<br />

3 off Interlock mechanism (10d) 1SDA038358R1<br />

www.abb.com/lowvoltage email marketing.info@gb.abb.com Telephone 02476 368549 Facsimile 02476 368401<br />

ABB LIMITED 4/82


<strong>Emax</strong> Air <strong>Circuit</strong> <strong>Breakers</strong><br />

Conversion kit for fixed circuit-breaker or fixed parts<br />

Conversion Kits<br />

Kit for converting fixed circuit-breaker<br />

with horizontal rear terminals to vertical rear terminals<br />

Type 1SDA0 R1<br />

3 terminals for 3 poles 4 terminals for 4 poles<br />

E1 38052 38057<br />

E2 38053 38058<br />

E3 38054 38059<br />

E4 38055 38060<br />

E6 38056 38061<br />

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.<br />

Kit for converting fixed circuit-breaker<br />

with horizontal rear terminals to front terminals<br />

Type 1SDA0 R1<br />

3 terminals for 3 poles 4 terminals for 4 poles<br />

E1 38062 38067<br />

E2 38063 38068<br />

E3 38064 38069<br />

E4 38065 38070<br />

E6 38066 38071<br />

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.<br />

Kit for converting fixed parts<br />

with horizontal rear terminals to front terminals<br />

Type 1SDA0 R1<br />

3 terminals for 3 poles 4 terminals for 4 poles<br />

E1 38062 38067<br />

E2 45031 45035<br />

E3 45032 45036<br />

E4 45033 45037<br />

E6 45034 45038<br />

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.<br />