Troubleshooting Tips<br />
Problem # 1: Hot Surface Igniter Does Not Glow Red<br />
Possible Causes:<br />
• No main power<br />
• Faulty Transformer<br />
• Faulty Thermostat- check call for heat<br />
• Faulty Limit Switch<br />
• Faulty blower interlock switch<br />
• Faulty hot surface igniter<br />
• Faulty ignition control<br />
• Remember to wait for purge time, 17 or 34 seconds<br />
Troubleshooting:<br />
• With power on and thermostat at its highest position, check voltage between “TH” and<br />
“TR” on HS780 module.<br />
– If 24 Volts is not present, check transformer output<br />
– If no 24 Volts present on secondary side, change transformer<br />
• Check for 120 Volts at the igniter across “IGN” and “GND”<br />
– If voltage present, change igniter.<br />
– If no voltage present, change module.